Desa FVFM27NR AIR for Combustion Ventilation, Determining FRESH-AIR Flow for Heater Location

Page 5

OWNER’S MANUAL

AIR FOR

COMBUSTION AND

VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height).

Length x Width x Height = _____________ cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

_______________ (volume of space) ÷ 50 cu. ft. = (maximum Btu/Hr the space can support)

Example: 2560 cu. ft. (volume of space) ÷ 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

 

______________ Btu/Hr

Gas water heater*

 

______________ Btu/Hr

Gas furnace

 

______________ Btu/Hr

Vented gas heater

 

______________ Btu/Hr

Gas fireplace logs

 

______________ Btu/Hr

Other gas appliances* +

______________ Btu/Hr

Total

=

______________ Btu/Hr

Example:

 

 

 

Gas water heater

 

40,000

Btu/Hr

Vent-free heater

+

39,000

Btu/Hr

Total

=

79,000

Btu/Hr

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________________ Btu/Hr (maximum the space can support)

_________________ Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support) 79,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin- ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANS Z223.1, 1992, Section 5.3 or applicable local codes.

Continued

105223

5

Image 5
Contents FVFM27NR Millivolt Remote Control Ready ModelWhat to do if YOU Smell GAS Patent PendingSafety Information Remote Control Accessories Product FeaturesProduct Identification Local CodesProviding Adequate Ventilation AIR for Combustion and VentilationUnusually Tight Construction Confined and Unconfined SpaceDetermining if You Have a Confined or Unconfined Space AIR for Combustion VentilationDetermining FRESH-AIR Flow for Heater Location Ventilation Air From Inside Ventilation AIRBuilding Ventilation Air From OutdoorsCheck GAS Type InstallationMinimum Wall and Ceiling Clearances see Figure Log Size Side Wall CeilingIf Not Using Mantel If Using MantelMinimum Noncombustible Material Clearances Eration,Mantel Clearances Determining Minimum Mantel Clearance When Using a HoodFloor Clearances Determining Minimum Mantel ClearanceInstalling Heater Base Assembly Installing Damper Clamp Accessory for Vented OperationInstallation Items Needed Area of Various Standard Round FluesAttaching Flexible Gas Hose to Heater Connecting to GAS SupplyPressure Testing Heater Gas Connections Pressure Testing Gas Supply Piping SystemChecking GAS Connections Test Pressures In Excess Of 1/2 PsigInstalling Bottom Log #1 Installing LogsInstructions For Your Safety Read Before LightingOperating Heater Optional Remote Operation Manual Lighting ProcedureTo Turn OFF GAS To Appliance Pilot Flame Pattern Inspecting BurnersBurner Primary AIR Holes Main BurnerObserved Problem Possible Cause TroubleshootingMaintenance, Observed Problem Possible Cause RemedyGas leak. See Warning statement at top TopSpecifications Cleaning and MaintenanceService Hints Technical ServiceWiring Diagram AccessoriesReplacement Parts FVFM27NR Illustrated Parts BreakdownDescription QTY Parts ListLimited Warranty VENT-FREE Natural GAS LOG Heaters Warranty Information

FVFM27NR specifications

Desa FVFM27NR is a modern and innovative product that embodies cutting-edge technology and design aesthetics, making it a standout choice in its category. This versatile device is tailored to meet the demands of consumers who seek both efficiency and performance in their daily activities.

One of the key features of the FVFM27NR is its robust build quality, which ensures durability and longevity. Constructed using high-grade materials, the device is designed to withstand regular use while maintaining a sleek appearance. This attention to detail not only enhances its functionality but also contributes to an appealing visual presence.

The FVFM27NR is equipped with advanced technologies that elevate its performance. With a powerful engine, the device delivers superior results across various applications. The incorporation of smart technology allows users to control and customize settings according to their specific needs, providing an intuitive user experience. Ergonomic design elements further enhance usability, ensuring that the device is comfortable to handle even during extended use.

Energy efficiency is another hallmark of the FVFM27NR. It integrates eco-friendly technologies that minimize power consumption without sacrificing performance. The energy-efficient operation not only reduces utility costs for users but also contributes positively to environmental sustainability.

Along with its efficiency and power, the FVFM27NR features a range of specialized modes that cater to different tasks. This versatility makes it suitable for various environments, whether in a home, office, or outdoor setting. The ability to switch between modes with ease allows for quick adaptation, making it a practical tool for users with diverse requirements.

Additionally, the FVFM27NR is designed with user safety in mind. It incorporates multiple safety features, including automatic shut-off and thermal protection, ensuring peace of mind during operation.

In conclusion, Desa FVFM27NR stands out as a leading option in its market segment, thanks to its combination of robust design, advanced technology, energy efficiency, versatility, and user safety. Whether for professional or personal use, it delivers exceptional value, making it an ideal investment for anyone seeking a reliable and effective device. With its modern features and characteristics, the FVFM27NR is well-positioned to meet contemporary lifestyle needs while ensuring optimal performance and satisfaction.