Desa VYM27NR AIR for Combustion Ventilation, Determining FRESH-AIR Flow for Heater Location

Page 5

OWNER’S MANUAL

AIR FOR

COMBUSTION AND

VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height).

Length x Width x Height = _____________ cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

_______________ (volume of space) ÷ 50 cu. ft. = (maximum Btu/Hr the space can support)

Example: 2560 cu. ft. (volume of space) ÷ 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

 

______________ Btu/Hr

Gas water heater*

 

______________ Btu/Hr

Gas furnace

 

______________ Btu/Hr

Vented gas heater

 

______________ Btu/Hr

Gas fireplace logs

 

______________ Btu/Hr

Other gas appliances* +

______________ Btu/Hr

Total

=

______________ Btu/Hr

Example:

Gas water heater 40,000 Btu/Hr Vent-free heater + 39,000 Btu/Hr

Total= 79,000 Btu/Hr

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

____________ Btu/Hr (maximum the space can support)

____________ Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support) 79,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin- ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANS Z223.1, 1992, Section 5.3 or applicable local codes.

Continued

104674

5

Image 5
Contents Remote Control Ready Model OWNER’S Operation and Installation ManualWhat to do if YOU Smell GAS Patent PendingVanguard Flame MAX Unvented Natural GAS LOG Heater Safety InformationRemote Control Accessories Product FeaturesProduct Identification Local CodesProviding Adequate Ventilation AIR for Combustion and VentilationUnusually Tight Construction Confined and Unconfined SpaceDetermining if You Have a Confined or Unconfined Space AIR for Combustion VentilationDetermining FRESH-AIR Flow for Heater Location Ventilation Air From Inside Ventilation AIRBuilding Ventilation Air From OutdoorsInstallation Clearances InstallationCheck GAS Type Minimum Fireplace Clearance to Combustible MaterialsMinimum Noncombustible Material Clearances If Not Using MantelIf Using Mantel Mantel Clearances Determining Minimum Mantel Clearance When Using a HoodFloor Clearances Determining Minimum Mantel ClearanceInstalling Heater Base Assembly Installing Damper Clamp Accessory for Vented OperationInstallation Items Needed Chimney Minimum Permanent Height ft Flue Opening sq. insAttaching Flexible Gas Hose to Heater Connecting to GAS SupplyPressure Testing Heater Gas Connections Pressure Testing Gas Supply Piping SystemChecking GAS Connections Test Pressures In Excess Of 1/2 PsigInstalling Bottom Log #1 Installing LogsInstructions For Your Safety Read Before LightingOperating Heater Optional Remote Operation Manual Lighting ProcedureTo Turn OFF GAS To Appliance Pilot Flame Pattern Inspecting BurnersBurner Primary AIR Holes Main BurnerObserved Problem Possible Cause TroubleshootingMaintenance, Observed Problem Possible Cause RemedyGas leak. See Warning statement at top TopSpecifications Wiring Diagram Replacement PartsService Hints Technical ServiceLogs Cleaning and MaintenanceCleaning Burner Injector Holder and Pilot AIR Inlet Hole VYM27NR Illustrated Parts BreakdownDescription QTY Parts ListAccessories 104674 International Limited Warranty VENT-FREE Natural GAS LOG Heaters

VYM27NR specifications

Desa VYM27NR is a cutting-edge piece of technology designed to meet the demanding needs of modern users while ensuring energy efficiency and superior performance. This innovative device integrates advanced features and smart technologies that make it a popular choice among professionals and consumers alike.

One of the main features of the Desa VYM27NR is its robust performance powered by a high-efficiency motor. This motor is capable of delivering exceptional power output while minimizing energy consumption, which contributes to lower operational costs. The unit operates quietly, making it suitable for use in residential areas without causing disruption.

In addition to its powerful motor, the Desa VYM27NR is equipped with smart sensors that automatically adjust performance based on user requirements. This intelligent adjustment ensures optimal operation, resulting in enhanced user experience. The device also includes an intuitive control panel that allows users to easily monitor and manage settings, further simplifying its use.

Another noteworthy characteristic of the Desa VYM27NR is its compact and lightweight design. This portability allows users to easily move it between different locations or store it without taking up much space. It is constructed from durable materials that ensure longevity and reliability, making it a sound investment for any user.

The technology behind Desa VYM27NR also includes enhanced safety features. It is equipped with multiple safety sensors that provide protection against overheating and electrical surges, ensuring the device operates within safe parameters at all times.

Furthermore, the Desa VYM27NR boasts environmental responsibility with its eco-friendly operating capabilities. It adheres to stringent regulations regarding emissions and energy use, thus aligning with global efforts towards sustainability.

In summary, the Desa VYM27NR showcases a blend of powerful performance, user-friendly features, and safety technologies. Its compact design, efficient energy use, and eco-friendly attributes make it stand out in the market, appealing to a diverse range of users who seek efficiency and reliability in their devices. Whether for personal or professional use, the Desa VYM27NR promises to deliver exceptional performance and value, making it a top choice in its category.