Desa VP10TA VN6D AIR for Combustion, Ventilation AIR, Ventilation Air From Inside Building

Page 5

AIR FOR COMBUSTION AND VENTILATION

5

Determining Fresh-Air Flow For Heater Location (Cont.)

Ventilation Air

 

 

 

AIR FOR COMBUSTION AND

VENTILATION AIR

VENTILATION

 

Ventilation Air From Inside Building

Continued

 

 

This fresh air would come from an adjoining unconfined space.

3. Add the Btu/Hr of all fuel burning appliances in the space.

When ventilating to an adjoining unconfined space, you must

provide two permanent openings: one within 12" of the ceiling and

 

Vent-free heater

 

_____________ Btu/Hr

one within 12" of the floor on the wall connecting the two spaces

 

Gas water heater*

 

_____________ Btu/Hr

(see options 1 and 2, Figure 2). You can also remove door into

 

Gas furnace

 

_____________ Btu/Hr

adjoining room (see option 3, Figure 2). Follow the National Fuel

 

Vented gas heater

 

_____________ Btu/Hr

Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion

 

Gas fireplace logs

 

_____________ Btu/Hr

and Ventilation for required size of ventilation grills or ducts.

 

 

 

 

 

 

 

 

Other gas appliances* +

_____________ Btu/Hr

 

 

 

 

 

 

 

 

 

 

 

 

Total

=

_____________ Btu/Hr

 

 

12"

 

 

* Do not include direct-vent gas appliances. Direct-vent draws com-

 

 

 

 

 

 

bustion air from the outdoors and vents to the outdoors.

 

 

 

Ventilation Grills

 

Example:

 

 

 

 

 

 

 

 

Ventilation

 

 

Into Adjoining Room,

 

Gas water heater

 

40,000

Or

 

Option 2

 

 

Grills

 

 

 

 

 

_____________ Btu/Hr

into Adjoining

Remove

 

 

 

 

 

 

10,000

 

 

 

 

Vent-free heater

+

Room,

Door into

 

 

 

 

_____________ Btu/Hr

Option 1

Adjoining

 

 

 

 

Total

=

50,000

 

Room,

 

 

 

 

_____________ Btu/Hr

 

Option 3

 

 

 

4.

Compare the maximum Btu/Hr the space can support with the actual

 

 

 

 

 

 

amount of Btu/Hr used.

 

 

 

 

 

 

 

 

__________________ Btu/Hr (maximum the space can support)

 

 

 

 

 

 

 

 

 

 

 

 

 

12"

 

 

 

 

 

 

 

 

 

 

__________________ Btu/Hr (actual amount of Btu/Hr used)

 

 

 

 

 

 

 

 

 

 

 

 

Example: 51,200 Btu/Hr (maximum the space can support)

 

 

 

 

 

 

50,000 Btu/Hr (actual amount of Btu/Hr used)

 

 

 

 

 

The space in the above example is a confined space because the actual Btu/

Figure 2 - Ventilation Air from Inside Building

Hr used is more than the maximum Btu/Hr the space can support. You must

Ventilation Air From Outdoors

provide additional fresh air. Your options are as follows:

A.

Rework worksheet, adding the space of an adjoining room. If the ex-

Provide extra fresh air by using ventilation grills or ducts. You must

 

 

 

 

tra space provides an unconfined space, remove door to adjoining

provide two permanent openings: one within 12" of the ceiling and

room or add ventilation grills between rooms. See Ventilation Air From

one within 12" of the floor. Connect these items directly to the

Inside Building.

outdoors or spaces open to the outdoors. These spaces include attics

 

B.Vent room directly to the outdoors. See Ventilation Air From and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/

Outdoors.

NFPA 54, Section 5.3, Air for Combustion and Ventilation for

C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room un-

required size of ventilation grills or ducts.

confined.

IMPORTANT: Do not provide openings for inlet or outlet air into

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can

attic if attic has a thermostat-controlled power vent. Heated air

support, the space is an unconfined space. You will need no additional fresh

entering the attic will activate the power vent.

air ventilation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WARNING: If the area in which the heater may be operated is smaller than that defined as an uncon- fined space or if the building is of unusually tight construction, provide adequate combustion and ven- tilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Sec- tion 5.3 or applicable local codes.

 

 

 

 

Outlet

Ventilated

 

 

 

 

Attic

 

 

 

 

Air

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outlet

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To Attic

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Crawl

Inlet

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Space

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inlet Air

 

 

Ventilated

 

 

 

 

 

 

 

Crawl Space

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 3 - Ventilation Air from Outdoors

For more information, visit www.desatech.com

110720-01B

Image 5
Contents What to do if YOU Smell GAS VENT-FREE GAS HeaterSafety Information Table of ContentsUnpacking Product FeaturesProduct Identification Local CodesProviding Adequate Ventilation AIR for Combustion and VentilationDetermining FRESH-AIR Flow for Heater Location Confined and Unconfined SpaceVentilation AIR for CombustionVentilation AIR Ventilation Air From Inside BuildingInstallation Items InstallationCheck GAS Type Locating HeaterInstalling Two Mounting Screws Installing Heater to WallMarking Screw Locations Placing Heater On Mounting ScrewsInstalling Bottom Mounting Screw Connecting to GAS SupplyChecking GAS Connections Pressure Testing Gas Supply Piping SystemLighting Instructions Pressure Testing Heater Gas ConnectionsOperating Heater To Turn OFF GAS To Appliance Manual Lighting ProcedureShutting Off Heater Shutting Off Burner Only pilot stays litBurner Patterns To Select Heating LevelOFF Position Shown Thermostat Control Operation Inspecting BurnerBurner Flame Pattern Blue Flame Models Pilot Flame PatternCleaning Burner Pilot AIR Inlet Hole Cleaning MaintenanceBurner Flame Pattern Infrared Models ODS/PILOT and Burner OrificeObserved Problem Possible Cause Remedy TroubleshootingMaintenance, Gas leak. See Warning statement at VP600BA VP5D VP10A VP10TA VP1000BTA SpecificationsVN600BA VP600BA Pilot Illustrated Parts BreakdownParts Available not Shown Parts ListKEY Part Number for VP600BA VN600BA Description QTY VP10A VN10A KEY Part Number VP10A VN10A Description QTY VP10TA VN10TA KEY Part Number VP10TA VN10TA Description QTY VP5D VN6D ODS/PILOT KEY Part Number VP5D VN6D Description QTY VP1000BTA VN1000BTA Pilot NJF 8C KEY Part Number VP1000BTA VN1000BTA Description QTYTechnical Service Replacement PartsService Publications Service Hints AccessoryOwners Registration Form Postage Required Baltimore Electric Parts CentralsWarranty Information

VP10TA VN6D, VP10A VN10TA specifications

Desa VP10A, VN10TA, VP10TA, and VN6D are noteworthy models in the realm of cutting-edge technology, designed to cater to modern industrial and consumer needs. Each model boasts unique features and characteristics, making them suitable for various applications.

The Desa VP10A is recognized for its robust performance and high reliability. It typically includes advanced air filtration systems that ensure optimal air quality while maintaining efficient operation. Its energy-efficient design minimizes power consumption without compromising performance, making it an environmentally friendly choice. This model often incorporates user-friendly controls, allowing for effortless adjustments and monitoring of operations.

Moving on to the VN10TA, this unit excels in terms of versatility and adaptability. It is built with a modular design, allowing users to customize the configuration based on specific requirements. This feature enhances its applicability across different sectors, such as manufacturing and logistics. The VN10TA also integrates sophisticated connectivity options, enabling seamless integration with existing systems while providing data analytics capabilities for better operational insights.

The VP10TA model places a strong emphasis on performance efficiency. It includes state-of-the-art technologies such as variable speed drives, which optimize energy use and enhance overall system performance. Moreover, the VP10TA is often equipped with smart sensors that monitor operational parameters in real time, ensuring maximum efficiency and longevity of the unit.

Lastly, the VN6D model stands out with its compact design, perfect for environments with space constraints. Despite its smaller footprint, the VN6D does not compromise on power or efficiency. The unit is designed for quick installation and maintenance, streamlining processes in busy settings. Additionally, it incorporates noise-reduction technologies, making it an excellent choice for applications in noise-sensitive areas.

All models feature high-quality construction materials, ensuring durability and resistance to wear and tear, which is critical in demanding environments. The combination of innovative features and superior technologies in the Desa VP10A, VN10TA, VP10TA, and VN6D makes them valuable assets for any industrial or commercial setup, effectively catering to the intricate demands of today’s economy. Their exceptional performance, adaptability, and efficiency are testaments to Desa's commitment to quality and innovation in technology.