PVI Industries SU-3 manual Gas Burner Piping

Page 8

6.7Appliance Isolation During Gas Supply Piping Pressure

Warning: The gas valve must not be subjected to more than ½” psig (3.45 kPa). Subjecting the gas valve to pressure above ½” psig (3.45 kPa) can damage the valve and can cause gas leaks or loss of gas control, which can result in property damage, personal injury or death.

The burner must be isolated during gas leak tests. The burner and its combination gas valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of ½” psig (3.45 kPa). The appliance must be isolated from the gas supply piping by closing its individual manual shut off valve using the gas control knob on top of burner combination valve during any pressure testing of the gas supply piping system at test pressures equal to or less than ½” psig (3.45 kPa).

SU-3 GAS BURNER

THIS IS NOT PART OF

THE SU-3 BURNER

Gas Burner Piping

(Piping upstream of burner combination gas valve supplied by others)

7. SEQUENCE OF OPERATION - Honeywell S89F

Limits close.

Blower motor starts as the 24 Volt transformer powers the airflow switch.

When the airflow switch is proven, the S89F control initiates a pre-purge of approximately 34 seconds.

At the end of the pre-purge, the spark is energized for 4 seconds. At the same time, the 24 Volt transformer powers the gas valve, allowing the fuel to flow. (The combination gas valve contains two separate automatic safety shutoff valves, a pressure regulator and a manual shutoff valve)

Within 4 seconds, the flame should be established and proved. The spark will shut off and the control will hold power to the gas valve until the limits open and the burner stops firing.

If the flame is not established, the blower motor continuously runs.

To restart, power should be interrupted for five minutes. Then turn on the power to start this sequence again.

WARNING: Should overheat occur, shut off the manual gas shut off valve to control the appliance. Do not shut off the control switch to the pump or blower, which provides burner cooling and post purge. Failure to follow this warning may result in a fire or explosion, causing property damage, personal injury or death.

En cas de surchauffe : (1) fermez la commande manuelle de gaz à l'appareil, (2) ne pas fermer la commande de la pompe ou de la soufflerie.

8

PV500-56 06/12

Image 8
Contents Installation & Maintenance Manual Table of Contents Safety Considerations For Your SafetyElectrical Specifications CodesCombustion and Ventilation AIR  All Air From OutdoorsVenting GAS Supply and PipingInlet Pressure NAT. GASGas Burner Piping Burner Operation Electrode and Flame Sensor PositioningBurner Setup and Adjustment SU3 Gas ManifoldCommissioning Checklist PV500-56 06/12 Maintenance Instructions Troubleshooting Condition SolutionsMaterials List PartPV500-56 06/12