PVI Industries SU-3 manual SU3 Gas Manifold, Burner Setup and Adjustment

Page 10

10.BURNER SETUP AND ADJUSTMENT

WARNING: The burner supplied with this water heater has been factory adjusted to operate on the type gas, gas pressure, manifold pressure and firing rate identified on the burner data decal and must be verified after installation and adjusted as required to obtain those values. Firing this burner above the burner decal specified firing rate will void the warranty, and may result in improper operation, a fire or explosion, or dangerous carbon monoxide, causing property damage, personal injury or death.

See the burner and water heater data decals for the proper firing rate, gas pressure requirements and other important information.

Head Adjustment

Air Adjustment

Manifold Pressure Tap

Top View of Gas Valve

Top View of Gas Valve

Adjusting the Firing Rate

SU3 Gas Manifold

10

PV500-56 06/12

Image 10
Contents Installation & Maintenance Manual Table of Contents Safety Considerations For Your SafetyElectrical Specifications CodesCombustion and Ventilation AIR  All Air From OutdoorsVenting GAS Supply and PipingInlet Pressure NAT. GASGas Burner Piping Burner Operation Electrode and Flame Sensor PositioningBurner Setup and Adjustment SU3 Gas ManifoldCommissioning Checklist PV500-56 06/12 Maintenance Instructions Troubleshooting Condition SolutionsMaterials List PartPV500-56 06/12