Duct Fitting Equivalent Length

 

Duct Pipe:

6” Duct

7” Duct

8” Duct

9” Duct

90º

Elbow

8 feet

9 feet

10 feet

11 feet

90º

Long Radius Elbow

5 feet

5 feet

5 feet

6 feet

45º

Elbow

5 feet

5 feet

5 feet

5 feet

The following remote air duct information is provided for use in design calculations, if needed.

Remote Air Duct Specifications

Input Mbtu

Required

Max Duct Loss

Air (SCFM)

(inches Water)

 

 

 

 

1500

325

0.784

1800

390

1.11

2000

433

1.356

8.3Remote Combustion Air Cap

A UL Listed air intake vent termination cap MUST be attached to the remote combustion air vent termination to adequately protect the combustion air inlet from wind and weather. A UL Listed air intake termination cap is available from PVI Industries and may have shipped with the water heater as a purchased option.

8.4Vertical or Horizontal Remote Air Duct Termination

Air inlet and exhaust vents should terminate in the same wind pressure area whenever possible.

Air inlet must be located no less than 3 feet (0.91m) below the exhaust terminal if they are within 10 feet (3.05 m) of each other.

If terminating through the roof, the air inlet must terminate at least 12 inches (0.3 m) above roof level and at least 12 inches (0.3 m) above snow levels.

If terminating through a sidewall, the air inlet must terminate at least 12 inches (0.3 m) above grade and/or at least 12 inches (0.3 m) above normal snow levels.

Vertical Remote Air

 

 

 

 

Horizontal Remote Air

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8.5Remote Air Consideration for Combined Remote Air Ducting

Each water heater MUST have separate intake piping. Consult factory for common air intake pipe sizing.

17

PV500-47C 06/12

Image 17
Contents Installation & Maintenance Manual Table of Contents Troubleshooting Guide Replacement Parts Operating and Safety ControlsTemptrac Electronic Controller Panel Remote Connections Terminal StripProduct Safety Information Safety ConsiderationsBelow scalding temperatures Standard Features and Equipment Series Series Checking Equipment Before You Install Water Heater InstallationCodes Electrical RequirementsClearances To Combustible Surfaces Service ClearancesGeneral Piping Guidelines Inlet and Outlet ConnectionsPV500-47C 06/12 PV500-47C 06/12 Optional Condensate Neutralization System GAS Supply and Piping Single Unit Installation Suggested Pipe SizeInlet Pressure NAT. GAS Convert Fittings to Equivalent Straight PipeNominal Iron Length of Pipe in Straight Feet Multiple Unit Installations GAS Piping Size ChartInches Appliance Isolation during Gas Supply Piping Pressure TestEquipment Located In Confined Spaces Combustion and Ventilation AIR∙ All Air From Outdoors ∙ All Air From Inside The BuildingVertical or Horizontal Remote Air Duct Termination Duct Fitting Equivalent Length Duct PipeVenting the Tricon VentingMaximum Category IV Vent Length Equivalent Length Vent Fitting Equivalent Length Vent PipeCombining Category IV Vents Vertical or Horizontal Vent TerminationTemperature and Pressure Relief Valve s Operating and Safety ControlsHigh Water Temperature Limit Control Cathodic ProtectionSET Temptrac Electronic Controller PanelDown ClockTo Change Other Parameters To View The SetpointTo Change The Setpoint Alarm Cause Results of Alarm Condition Message LED Display Alarm MessagesRecommended Action Remote Connections Terminal StripIncoming 120VAC Sequence of OperationLED Indication Fault Mode Loss of Flame SignalInitial Startup Turn-on main gas shutoff valve PV500-47C 06/12 Alternate Gas Train Illustration Gas Train IllustrationProblem Probable Cause Corrective Action Troubleshooting GuideReplacement Parts Replacement PartsControl Panel FUSEHOLDER, Panel Type #HTB-28I Burner Assembly Optional components may or may not be shown SUPPORT, GAS Train FB14 Pvif Burner Assembly ComponentsContact factory for more information Burner GAS Train ComponentsPeriodic Maintenance PV500-47C 06/12 Recommended Maintenance Schedule PV500-47C 06/12

PV500-47C specifications

PVI Industries has established itself as a leading name in the manufacturing of innovative water heating solutions. Among its diverse product lineup is the PV500-47C, a well-regarded commercial water heater that exemplifies efficiency, reliability, and advanced technology. Designed for a variety of applications, the PV500-47C is particularly suitable for large commercial institutions, including hotels, hospitals, and educational facilities.

One of the standout features of the PV500-47C is its robust construction and high storage capacity. With a tank capacity of 500 gallons, it is designed to accommodate the high-demand hot water needs of large settings. The unit is engineered using resilient materials that provide long-lasting performance while also resists corrosion, ensuring the integrity of the tank over time.

The PV500-47C incorporates advanced heating technologies to improve energy efficiency. Its innovative design includes a highly efficient insulated tank that minimizes heat loss, allowing it to maintain water temperatures effectively. The water heater is typically powered by extensive heat exchangers that maximize energy transfer from the heating source to the water, which can help reduce energy costs and improve overall operational efficiency.

In addition, the PV500-47C boasts a state-of-the-art electronic control system that enables precise temperature management. This feature enhances not only safety but also the efficiency of the heating process, allowing users to program specific temperatures and schedules according to their operational needs. The unit also includes multiple safety features, such as high-temperature limit switches to prevent over-temperature situations, contributing to the overall safety of the water heating system.

Another notable characteristic of the PV500-47C is its ease of installation and maintenance. The unit is designed with accessibility in mind, allowing for straightforward installation in various commercial settings. Regular maintenance is simplified thanks to its accessible components, which makes it easier for technicians to service the system, ensuring minimal downtime.

In summary, the PVI Industries PV500-47C is a highly efficient and dependable solution for commercial water heating needs. Its impressive features, advanced technologies, and user-friendly design make it an optimal choice for businesses that require consistent hot water supply while managing energy costs effectively. This makes the PV500-47C not just a water heater, but an integral asset to any large-scale operation.