PVI Industries PV500-47C Vertical or Horizontal Vent Termination, Combining Category IV Vents

Page 19

9.3Vertical or Horizontal Vent Termination:

1.The vent terminal must have a minimum clearance of 4 feet (1.22 m) horizontally from, and in no case be located above or below, unless a 4 foot (1.22 m) horizontal distance is maintained from electric meters, gas meters, regulators and relief equipment.

2.The vent cap must terminate at least 3 feet (0.91 m) above any forced air inlet within 10 feet (3.05 m).

3.The vent shall terminate at least 4 feet (1.22 m) below, 4 feet (1.22 m) horizontally from or 1 foot (0.3 m) above any door, window or building air inlet to the building.

4.The vent system shall terminate at least 1 foot (0.3 m) above grade and at least 1 foot (0.3m) above possible snow accumulation levels and shall terminate at least 7 feet (2.13 m) above grade when located adjacent to public walkways or gathering areas.

5.To avoid a blocked flue condition, keep the vent cap clear of snow, ice, leaves, debris, etc.

6.The vent must not exit over a public walkway, near soffit vents or crawl space vents or other areas where condensate or vapor could create a nuisance or hazard or cause property or could be detrimental to the operation of regulators, relief valves or other equipment.

7.A horizontal vent must extend one foot beyond the wall.

8.A horizontal vent terminal must not be installed closer than 3 feet (0.91m) from an inside corner of an L-shaped structure.

9.A vertical vent must exhaust outside the building at least 3 feet (0.91m) above the point of the exit and at least 2 feet (0.61 m) above the highest point of the roof within a 10-foot (3.05 m) radius of the termination.

10.A vertical termination less than 10 feet (0.91 m) from a parapet wall must be a minimum of 2 feet (0.61 m) higher than the parapet wall.

9.4Combining Category IV Vents

Combined TRICON Category IV gas vent systems must incorporate an Exhausto or Tjernlund variable speed, modulating, mechanical draft inducer capable of maintaining the appropriate negative draft at the end of the common flue, to assure that all water heaters in the combined vent system operate with a negative draft. Do not exceed negative 0.25” W.C. See “Combining Vents with a Draft Inducerillustration below.

WARNING: Do not connect multiple water heaters vents into a single unpowered or fixed speed powered vent. This could cause unsafe operation and the potential for poisonous carbon monoxide to enter occupied areas. Such improper installation can cause property damage, personal injury, exposure to hazardous materials or loss of life.

Conventional Venting

Through the Wall Venting

Combining Vents with a Draft Inducer

19

PV500-47C 06/12

Image 19
Contents Installation & Maintenance Manual Table of Contents Remote Connections Terminal Strip Operating and Safety ControlsTroubleshooting Guide Replacement Parts Temptrac Electronic Controller PanelProduct Safety Information Safety ConsiderationsBelow scalding temperatures Standard Features and Equipment Series Series Electrical Requirements Water Heater InstallationChecking Equipment Before You Install CodesInlet and Outlet Connections Service ClearancesClearances To Combustible Surfaces General Piping GuidelinesPV500-47C 06/12 PV500-47C 06/12 Optional Condensate Neutralization System Convert Fittings to Equivalent Straight Pipe Single Unit Installation Suggested Pipe SizeGAS Supply and Piping Inlet Pressure NAT. GASAppliance Isolation during Gas Supply Piping Pressure Test Multiple Unit Installations GAS Piping Size ChartNominal Iron Length of Pipe in Straight Feet Inches∙ All Air From Inside The Building Combustion and Ventilation AIREquipment Located In Confined Spaces ∙ All Air From OutdoorsVertical or Horizontal Remote Air Duct Termination Duct Fitting Equivalent Length Duct PipeVent Fitting Equivalent Length Vent Pipe VentingVenting the Tricon Maximum Category IV Vent Length Equivalent LengthCombining Category IV Vents Vertical or Horizontal Vent TerminationCathodic Protection Operating and Safety ControlsTemperature and Pressure Relief Valve s High Water Temperature Limit ControlClock Temptrac Electronic Controller PanelSET DownTo Change The Setpoint To View The SetpointTo Change Other Parameters Remote Connections Terminal Strip LED Display Alarm MessagesAlarm Cause Results of Alarm Condition Message Recommended ActionIncoming 120VAC Sequence of OperationLED Indication Fault Mode Loss of Flame SignalInitial Startup Turn-on main gas shutoff valve PV500-47C 06/12 Alternate Gas Train Illustration Gas Train IllustrationProblem Probable Cause Corrective Action Troubleshooting GuideReplacement Parts Replacement PartsControl Panel FUSEHOLDER, Panel Type #HTB-28I Burner Assembly Optional components may or may not be shown SUPPORT, GAS Train FB14 Pvif Burner Assembly ComponentsContact factory for more information Burner GAS Train ComponentsPeriodic Maintenance PV500-47C 06/12 Recommended Maintenance Schedule PV500-47C 06/12

PV500-47C specifications

PVI Industries has established itself as a leading name in the manufacturing of innovative water heating solutions. Among its diverse product lineup is the PV500-47C, a well-regarded commercial water heater that exemplifies efficiency, reliability, and advanced technology. Designed for a variety of applications, the PV500-47C is particularly suitable for large commercial institutions, including hotels, hospitals, and educational facilities.

One of the standout features of the PV500-47C is its robust construction and high storage capacity. With a tank capacity of 500 gallons, it is designed to accommodate the high-demand hot water needs of large settings. The unit is engineered using resilient materials that provide long-lasting performance while also resists corrosion, ensuring the integrity of the tank over time.

The PV500-47C incorporates advanced heating technologies to improve energy efficiency. Its innovative design includes a highly efficient insulated tank that minimizes heat loss, allowing it to maintain water temperatures effectively. The water heater is typically powered by extensive heat exchangers that maximize energy transfer from the heating source to the water, which can help reduce energy costs and improve overall operational efficiency.

In addition, the PV500-47C boasts a state-of-the-art electronic control system that enables precise temperature management. This feature enhances not only safety but also the efficiency of the heating process, allowing users to program specific temperatures and schedules according to their operational needs. The unit also includes multiple safety features, such as high-temperature limit switches to prevent over-temperature situations, contributing to the overall safety of the water heating system.

Another notable characteristic of the PV500-47C is its ease of installation and maintenance. The unit is designed with accessibility in mind, allowing for straightforward installation in various commercial settings. Regular maintenance is simplified thanks to its accessible components, which makes it easier for technicians to service the system, ensuring minimal downtime.

In summary, the PVI Industries PV500-47C is a highly efficient and dependable solution for commercial water heating needs. Its impressive features, advanced technologies, and user-friendly design make it an optimal choice for businesses that require consistent hot water supply while managing energy costs effectively. This makes the PV500-47C not just a water heater, but an integral asset to any large-scale operation.