PVI Industries PV500-47C manual Service Clearances, Clearances To Combustible Surfaces

Page 10

8.Do not install on carpet or other combustible floor coverings. If installation over a combustible floor is required, follow these guidelines:

Use a base of hollow clay tile or concrete blocks from 8" to 12" thick and extending 24" beyond the sides.

Place the blocks in line so that the holes line up horizontally to provide a clear passage through the blocks.

Install 1/2” fireproof millboard with a 20-gage sheet metal cover over the block base.

Center the unit on the base. Also follow this procedure if electrical conduit runs through the floor, and beneath the appliance. A field-installed base must meet all local fire and safety code requirements.

4.5Service Clearances

Allow sufficient space to provide adequate clearances on all sides for service and inspection. At least 24” above the water heater is required for filter replacement (if equipped) and burner/gas control service, 18” at left and right sides of the appliance. Optional equipment may increase the clearance requirements. Allow sufficient space for installing and servicing connections such as water, gas, vent, combustion air, electrical, pump and other auxiliary equipment.

4.6Clearances To Combustible Surfaces

Minimum 1” clearance must be provided from any vent surface to adjacent combustible material. The minimum clearances to unprotected combustible material are 24” be provided at the front, 8” be provided at the rear and 8” at top, left and right sides of the appliance.

5 GENERAL PIPING GUIDELINES

5.1Inlet and Outlet Connections

1.Use only non-ferrous water piping and fittings. Do not use galvanized pipe or fittings. Use of ferrous or galvanized pipe or fittings can cause rust to form.

2.Install shut-off valves and unions on the inlet and outlet water piping for servicing. Use caution when threading pipe nipples into tank connections to prevent cross threading, or over-tightening. Always use a back-up wrench on tank nipples when tightening unions, valves, etc.

3.Insulate hot water and return circulation lines. Insulate cold water supply lines if subject to freezing during shutdown periods. IMPORTANT: Do not use the plumbing connected to the appliance as a ground for welding or any other purpose.

4.Pipe the drain valve to a suitable open drain.

5.2Building Return Piping

To maximize water heater efficiency, connect the building return (≈ 5 gpm) directly to the return fitting located at the rear of the tank.

10

PV500-47C 06/12

Image 10
Contents Installation & Maintenance Manual Table of Contents Temptrac Electronic Controller Panel Operating and Safety ControlsTroubleshooting Guide Replacement Parts Remote Connections Terminal StripSafety Considerations Product Safety InformationBelow scalding temperatures Standard Features and Equipment Series Series Codes Water Heater InstallationChecking Equipment Before You Install Electrical RequirementsGeneral Piping Guidelines Service ClearancesClearances To Combustible Surfaces Inlet and Outlet ConnectionsPV500-47C 06/12 PV500-47C 06/12 Optional Condensate Neutralization System Inlet Pressure NAT. GAS Single Unit Installation Suggested Pipe SizeGAS Supply and Piping Convert Fittings to Equivalent Straight PipeInches Multiple Unit Installations GAS Piping Size ChartNominal Iron Length of Pipe in Straight Feet Appliance Isolation during Gas Supply Piping Pressure Test∙ All Air From Outdoors Combustion and Ventilation AIREquipment Located In Confined Spaces ∙ All Air From Inside The BuildingDuct Fitting Equivalent Length Duct Pipe Vertical or Horizontal Remote Air Duct TerminationMaximum Category IV Vent Length Equivalent Length VentingVenting the Tricon Vent Fitting Equivalent Length Vent PipeVertical or Horizontal Vent Termination Combining Category IV VentsHigh Water Temperature Limit Control Operating and Safety ControlsTemperature and Pressure Relief Valve s Cathodic ProtectionDown Temptrac Electronic Controller PanelSET ClockTo Change The Setpoint To View The SetpointTo Change Other Parameters Recommended Action LED Display Alarm MessagesAlarm Cause Results of Alarm Condition Message Remote Connections Terminal StripSequence of Operation Incoming 120VACLoss of Flame Signal LED Indication Fault ModeInitial Startup Turn-on main gas shutoff valve PV500-47C 06/12 Gas Train Illustration Alternate Gas Train IllustrationTroubleshooting Guide Problem Probable Cause Corrective ActionReplacement Parts Replacement PartsControl Panel FUSEHOLDER, Panel Type #HTB-28I Burner Assembly Optional components may or may not be shown Burner Assembly Components SUPPORT, GAS Train FB14 PvifBurner GAS Train Components Contact factory for more informationPeriodic Maintenance PV500-47C 06/12 Recommended Maintenance Schedule PV500-47C 06/12

PV500-47C specifications

PVI Industries has established itself as a leading name in the manufacturing of innovative water heating solutions. Among its diverse product lineup is the PV500-47C, a well-regarded commercial water heater that exemplifies efficiency, reliability, and advanced technology. Designed for a variety of applications, the PV500-47C is particularly suitable for large commercial institutions, including hotels, hospitals, and educational facilities.

One of the standout features of the PV500-47C is its robust construction and high storage capacity. With a tank capacity of 500 gallons, it is designed to accommodate the high-demand hot water needs of large settings. The unit is engineered using resilient materials that provide long-lasting performance while also resists corrosion, ensuring the integrity of the tank over time.

The PV500-47C incorporates advanced heating technologies to improve energy efficiency. Its innovative design includes a highly efficient insulated tank that minimizes heat loss, allowing it to maintain water temperatures effectively. The water heater is typically powered by extensive heat exchangers that maximize energy transfer from the heating source to the water, which can help reduce energy costs and improve overall operational efficiency.

In addition, the PV500-47C boasts a state-of-the-art electronic control system that enables precise temperature management. This feature enhances not only safety but also the efficiency of the heating process, allowing users to program specific temperatures and schedules according to their operational needs. The unit also includes multiple safety features, such as high-temperature limit switches to prevent over-temperature situations, contributing to the overall safety of the water heating system.

Another notable characteristic of the PV500-47C is its ease of installation and maintenance. The unit is designed with accessibility in mind, allowing for straightforward installation in various commercial settings. Regular maintenance is simplified thanks to its accessible components, which makes it easier for technicians to service the system, ensuring minimal downtime.

In summary, the PVI Industries PV500-47C is a highly efficient and dependable solution for commercial water heating needs. Its impressive features, advanced technologies, and user-friendly design make it an optimal choice for businesses that require consistent hot water supply while managing energy costs effectively. This makes the PV500-47C not just a water heater, but an integral asset to any large-scale operation.