MINIMUM AIR TERMINAL INSTALLATIONS

C E

Figure 8

K

 

J

D BI B F

A

L G H

E

Illustration dimensions are to the center and the exhaust exit point of the vent.

CLEARANCE

A

24 INCHES

Clearance above grade, veranda porch, deck or balcony.

(Including Vegetation and Mulch)

 

 

 

 

 

B

48 INCHES

Clearance beside or below any windows or doors that open.

 

 

 

 

12 INCHES*

Clearance above any window or door that opens.

 

 

 

C

18 INCHES

Vertical clearance to ventilated soffit located above the terminal within a horizontal

distance of 2 feet from the centerline of the terminal.

 

 

 

 

 

D

0 INCHES

Clearance to an outside corner wall.

 

 

 

E

3 INCHES

Clearance to an inside combustible corner wall or protruding combustible ob-

structions ( vent chase, etc.).

 

 

 

 

 

F

9 INCHES

Clearance to a non-mechanical air supply inlet to the building or a combustion

air inlet to any other appliance.

 

 

 

 

 

G

3 FEET

Clearance to a mechanical air supply inlet.

 

 

 

H

7 FEET**

Clearance above a paved sidewalk or paved driveway located on public property.

 

 

 

I

12INCHES**

Clearance under a veranda, porch, deck or balcony.

 

 

 

 

 

 

J

24 INCHES

Clearance above the roof.

 

 

 

K

2 FEET

Clearance from an adjacent wall including neighbouring buildings.

 

 

 

 

 

 

L

3 FEET within a

Clearance to each side of center line extended above natural gas or porpane

 

height of 15 FEET

meter/regulator assembly or mechanical vent.

 

above the meter/

 

 

regulator assembly

 

 

 

 

*Recommended to prevent condensation on windows and thermal breakage

**This is a recommended distance. For additional requirements check local codes.

W415-0616 / B / 02.18.08

Image 13
Contents W415-0616 / B $10.00 Table of Contents Napoleon Pellet Heaters Presidents Lifetime Limited Warranty W415-0616 / B W415-0616 / B Heating Specifications SpecificationsGeneral Introduction General InstructionsFigures 1a-b DimensionsFigures 3a-c Figures 4a-c General Installation Outside AIR Safety FeaturesMobile Home General Venting Installing the Pellet VentType of Vent Venting the Pellet HeaterI B F Minimum Clearance to Combustibles Straight Installation NPS40 InstallationCorner Installation Venting Installation Examples Class a Chimney Retrofit Minimum Inside Vertical ClearancesNPI40 Installation Installation Into a BUILT-IN Enclosure NPI40 Installation OverviewVertical Liner Installation Installation Into a Masonry Fireplace Prior to InstallationInstallation Into a Masonry Fireplace Liner Installation W415-0616 / B Minimum Enclosure Clearances Install Viewing Door NPS40 and NPI40 Flashing InstallationNPI40 Finishing Trivet NPI40SHUT-DOWN Operating InstructionsSTART-UP Lighting Heater ManuallyCleaning Glass Door General Maintenance NPS40 and NPI40Cleaning the Heat Exchange Tubes Disposal of Ashes Open Main Viewing DoorMake Sure Pellets are not Piling UP Cleaning the Burn POTVacuum Firebox Clean Exhaust Housing Insert only Clean the Vertical Exhaust DuctVacuum Hopper Soot and FLY ASH FormationClean the Vent Clean the Exhaust BlowerCheck ALL Seals Normal Operating Sounds Wiring Diagram Replacements Common Replacements Parts NPS40 Replacements Parts NPI40 Replacements Parts NPI40 Accessory Parts Symptom Test Solution TroubleshootingHeater will General Has tripped Heater will Service Date Service Technician Service Description Service and Maintenance LOGOwnership Records W415-0616 / B