CHECKING GAS PRESSURE AND ELECTRICAL INSTALLATION

1.Check gas type. The gas supply must be the same as stated on the appliance’s rating decal. If the gas supply is different from the fireplace, STOP! Do not install the appliance. Contact your dealer immediately.

2.To ease installation, a 24" (mm) flex line with manual shut-off valve has been provided with on this appli- ance. Install and attach 3/8" gas line onto shut-off valve.

3.After completing gas line connection, purge air from gas line and test all gas joints from the gas meter to the fireplace for leaks. Use a solution of 50/50 water and soap solution or a gas sniffer.

4.To adjust flame height, turn HI/LO knob to HI to get maximum pressure to burner. Turn HI/LO knob to LO to get minimum pressure. NOTE: To make the process of checking the gas pressure easier, unfasten the two screws which secure the gas valve to the side of the firebox and bring forward. [Remove the glass to allow the valve to come forward. (See page 29 for glass removal.)] When done, you must refasten the gas valve into place.

5.To check gas pressures at valve, turn captured screw counter clockwise 2 or 3 turns and then place tubing to pressure gauge over test point. Turn unit to high. See Figure 25. After taking pressure reading, be sure and turn captured screw clockwise firmly to reseal. Do not over torque. Check test points for gas leaks.

Pressure

Test “IN”

Pressure

Test “OUT”

HI/LO

Knob Pilot Adjustment

Screw

Figure 25 - Gas Pressure Check at Gas Valve

WARNING

Do not use open flame to check for

 

 

gas leaks.

 

 

ELECTRICAL WIRING

This fireplace will work without any electrical supply. Electricity is only needed to operate the blower and the light located behind the logs inside the firebox.

NOTE: If installed in mobile home, fireplace must be bolted securely to floor.

CAUTION WARNING

Electrical connections should only be performed by a qualified, licensed electrician. Main power must be off when connecting to main electrical power supply or performing service. All wiring shall be in compliance with all local, city, and state codes. The appliance, when installed, must be electrically grounded in accordance with local codes, or in the absence of local codes, with the National Electrical Code ANSI/ NFPA 70 (latest edition) and Canadian Electrical Code, CSA C22.1.

Label all wires before disconnecting when servicing controls. Wiring errors can cause improper and dangerous operation.

Verify proper operation after servicing.

73D0024

25

Image 25
Contents Khldv Series Direct Vent GAS Fireplace Contents Installer Important Safety InformationOwner Non-utility gas wells. This Never connect unit to privateGas is commonly known as Wellhead gasProduct Specifications Product Features and Code ApprovalCode Approval Listed Vented GAS Fireplace HeaterInstalling Above 2000 Feet PRE-INSTALLATION InformationOrifice SIZES, Pressures and BTUs Before YOU StartFirebox Framing Fireplace Dimensions Fireplace DimensionsFireplace Location Cold Climate InsulationClearances to Combustibles ClearancesMantel Clearances Securing Fireplace to Floor and Framing Studs Securing Fireplace to Floor or FramingVent Installation Installation InformationInstallation Precautions Finishing MaterialCombustible Clearances for Vent Pipe Vent InstallationInstalling a Vent System in AN Outside Chase Installation PlanningFor Horizontal Termination For Vertical TerminationMinimum Distances Horizontal Vent Termination LocationFeet HOW to USE the Vent GraphMaximum Three 3 90 Elbows VERTICAL/HORIZONTAL Termination ConfigurationsHorizontal Run Reduction VERTICAL/HORIZONTAL Termination ConfigurationsBelow Grade Installation Below Grade InstallationsSupport Straps for Horizontal Runs Vertical THROUGH-THE-ROOF ApplicationsFlat Ceiling Installation Installation for Vertical TerminationRoof Pitch Termination Heights for Vents Above Flat or Sloped RoofsInstalling GAS Piping to Fireplace / Burner System Location Fireplace InstallationCheck GAS Type Gas piping may make the necessary Only persons licensed to work withGas connections to this appliance Electrical Wiring Checking GAS Pressure and Electrical InstallationDo not use open flame to check for Gas leaksRemote Wall Mounted Switch Remote Wall Switch InstallationOptional FAN/BLOWER System Optional FAN/BLOWER System Junction Box Wiring DiagramBlower Access Plates Glass Frame Removal Glass RemovalBRICK, Light BULB, and Lens Placement Final InstallationRock Wool Placement Burner Grate Assembly Step LOG PlacementFinal Installation Operating Instructions MILLI-VOLT Leak TestingWhat to do if YOU Smell GAS Initial LightingApproved Leak Testing Method Lighting the Burner Main Burner SwitchPilot Position BURNER, Pilot and Control Compartment Cleaning and MaintenancePilot Flame BurnerGlass Door Vent SystemLogs Rock WoolSymptom Possible Cause Action TroubleshootingStanding Pilot Ignition Troubleshooting Firebox Components and Accessories Illustrated Parts ListsDescription Qty Standing Pilot Millivolt Control KHLDV400NV KHLDV400PV KHLDV500NV KHLDV500PV Vent Components for 5 X Illustrated Parts ListLogs Special Requirements Special Requirements 73D0024 73D0024 73D0024 73D0024 Five Year Warranty Lifetime WarrantyBasic Warranty

KHLDV SERIES specifications

The Monessen Hearth KHLDV Series is a standout line of direct vent gas fireplaces designed to elevate both the aesthetics and functionality of residential spaces. Distinguished by their contemporary design and impressive heating capabilities, these units cater to homeowners seeking a modern solution for efficient warmth and ambiance.

One of the primary features of the KHLDV Series is its versatile design options. Available in various sizes and styles, these fireplaces can seamlessly integrate into diverse interior décor themes. The clean face design allows for a wide viewing area of the flames, providing an unobstructed view that enhances the overall experience. The elegant finish options, ranging from sleek black to decorative trim, make it easy for consumers to customize their unit to suit their personal style.

The KHLDV Series is also noted for its advanced heating technology. Utilizing direct venting, it ensures efficient operation while minimizing heat loss. This technology allows the fireplace to draw air from outside for combustion, which not only improves energy efficiency but also maintains optimal indoor air quality by preventing the depletion of oxygen in the living area. The balanced flue design further ensures that harmful gases are vented safely outside, giving homeowners peace of mind.

Control is another significant advantage of the KHLDV Series. Equipped with a multi-function remote control system, users can easily adjust the flame height and heat output to achieve their desired ambiance and comfort levels. This intuitive control system enhances the overall user experience, allowing homeowners to create a cozy environment with minimal effort.

Safety features are also a crucial consideration in the design of the KHLDV Series. Each unit comes with a built-in safety pilot system that ensures the fireplace operates reliably and safely, providing an additional layer of security for families. The high-quality materials used in construction further enhance durability, ensuring that the fireplace can withstand the test of time.

In summary, the Monessen Hearth KHLDV Series is a perfect blend of style, efficiency, and safety. With its sleek design, advanced heating technology, user-friendly control, and robust safety features, this series transforms any living space into a warm and inviting sanctuary. Ideal for modern homes, the KHLDV Series stands out as a compelling choice for those looking to enhance their home with a functional and elegant fireplace.