Monessen Hearth CFX32, CFX24 manual Connect Remote Receiver, Check System Operation

Page 19

ELECTRICAL WIRING (Milli-volt)

CFX Vent Free Fireplace System

Connect Remote Receiver

THESE INSTRUCTIONS SUPERSEDE THE SECTION ENTITLED “HEARTH MOUNT” IN THE MILLI-VOLT HAND-HELD REMOTE INSTRUCTIONS SUPPLIED WITH THE REMOTE.

1.Remove bottom louver door.

2.Connect the remote connectors located in the unit.

3.Apply Velcro® pads with self-adhesive backing to bottom of remote receiver and to floor of compart- ment behind access panel.

4.Attach remote receiver to firebox with Velcro® pads. Control switch must face forward.

Velcro® Pad

SKYTECH

OFF

 

FIREPLACE

REMOTE

REMOTE

 

ON

 

 

Remote Receiver

Figure 17 -

Velcro Pad

NOTICE

Install Remote Receiver

FP2113

Do not place remote in combustion chamber.

Check System Operation

The millivolt system and individual components may be checked with a millivolt meter having a 0-1000 mV range. Conduct each check shown in chart below by connection meter test leads to terminals as indicated.

 

 

Connect Meter

Switch or

Meter

Check

To

Leads to

Thermostat

Reading

Test

Test

Terminals

Contacts

Should Be

A

Complete

2 & 3

Closed

Closed

 

System

 

 

 

B

Thermopile

1 & 2

Open

Open

 

Output

 

 

 

 

 

 

 

 

A.Complete Millivolt System Check

(“A” Reading - Thermostat contacts CLOSED - Control Knob “ON” - Main burner should be come ON)

a.If the reading is more than 100 millivolts and the automatic valve still does not come on, replace the control.

b.If the closed circuit reading (“A” reading) is less than 100 milli-volts, determine cause for low read- ing, proceed to Section B below.

B.Thermopile Output Reading Check

(“B” Reading - Thermostat contacts OPEN - Main burner OFF)

1. Check gas pressure to the unit. If gas pressure is within minimum and maximum on data plate, then check pilot voltage, 325 millivolts minimum. If the minimum milli-volt reading is not obtainable, replace pilot.

20301726

19

Image 19
Contents What to do if YOU Smell GAS Vent-free Fireplace Systems Models CFX24, CFX32CFX Vent Free Fireplace System ContentsInstaller Important Safety InformationOwner Codes Important Safety InformationGAS pressures Product Features & specificationsGas Specifications OperationCFX24 CFX32 Fireplace & System DimensionsHandle with care Getting StartedAdequate Combustion and Ventilation AIR Do not Install the CFX Model in a Bedroom or Bathroom Fireplace InstallationClearances and Height Requirements Remove Screen General Installation InformationInstall Mantel Firebox to Mantel Installation General Installation Information Install Optional Firebrick PanelsCheck gas type Installing gas piping to fireplace / burner system locationInstallation Items Needed Connect the GASConnect the GAS Check GAS Pressure Connecting Optional Wall Switch or Thermostat Electrical Wiring Milli-voltCheck System Operation Connect Remote ReceiverProper installation sequence CFX24 LOG PlacementCFX32 LOG & Rockwool PlacementProper installation sequence CleanCheck the pilot flame Flame appearanceCorrect log flame appearance Operating Instructions Check the Burner FlameOperating Instructions What to do if YOU Smell GASMILLI-VOLT Control Lighting Instructions Match Lighting Instructions Cleaning and ServicingFirebricks Blower and Other Optional EquipmentOptional Equipment Forced Air KitObserved Problem Possible Cause Remedy TroubleshootingTroubleshooting CFX24 CFX32 Replacement PartsReplacement Parts Replacment Parts Replacement Parts are Available Through Your RetailerCFX Vent Free Fireplace System CFX Vent Free Fireplace System If Warranty Service is Needed Lifetime WarrantyFive Year Warranty Basic WarrantyMhsc