CHECK GAS PRESSURE | CFX Vent Free Fireplace System |
1.Check gas type. The gas supply must be the same as stated on the appliance’s rating decal. If the gas supply is different from the fireplace, STOP! Do not install the appliance. Contact your dealer immediately.
2.To ease installation, a 24" (610 mm) flex line with
manual
3. After completing gas line connection, purge air from |
|
|
gas line and test all gas joints from the gas meter to |
|
|
the fireplace for leaks. Use a solution of 50/50 water |
|
|
and soap solution or a gas sniffer. | Pressure |
|
|
| |
4. To adjust flame height, turn HI/LO knob to HI to get | Test “IN” |
|
maximum pressure to burner. Turn HI/LO knob to LO |
|
|
to get minimum pressure. | Pressure |
|
5. To check gas pressures at valve, turn captured screw Test “OUT” | FP1979 | |
counter clockwise 2 or 3 turns and then place tubing | HI/LO Knob |
|
to pressure gauge over test point. Turn unit to high. |
| |
Pilot Adjustment Screw |
| |
Figure 15 After taking pressure reading, be sure and |
| |
turn captured screw clockwise firmly to reseal. Do not | Figure 15 - |
|
over torque. Check test points for gas leaks. | Gas Pressure Check at Gas Valve |
|
WARNING
Do not use open flame to check for gas leaks.
20301726 | 17 |