These options may be incorporated with one another. If the optional blowers are to be installed, make provision dur- ing framing to route a 110 volt power line to the fireplace. Detailed installation instructions are included with each venting kit.
FIGURE 4
LOCATION AND CLEARANCES
The fireplace must be installed against finished walls. Do not install against a vapour barrier or exposed insu- lation.
While the fireplace can be installed directly on the floor, a
MAINTAIN THESE MINIMUM CLEARANCES TO COMBUSTIBLES:
0" - FIREPLACE
1" - HOT AIR GRAVITY DUCTWORK
SEE 'FRAMING' SECTION:
top of unit to ceiling: 32½" -
Clearance from combustibles to furnace hot air duct work as specified by the furnace manufacturer is satis- factory. No additional clearances are required.
Do not pack air space, created between the
Objects placed in front of the fireplace must be kept a minimum of 48" away from the front face of the unit.
INSTALL ATION / FRAMING
FRAMING
The fireplace should be framed using 2x4 lumber as shown in Figure 5. The fireplace should be secured to the floor. Use the pallet packing brackets to accomplish this. If ducting is to be installed, the minimum enclosure ceiling height is 7 feet. Without ducting, the ceiling height may be brought down to a minimum of 6 feet. However a fireplace enclosure with a height less than 7 feet must be provided with sufficient air circulation to avoid a fire hazard. Install ventilation grilles (minimum openings of 40 sq. inches) at both floor and ceiling levels of the enclosure. These grilles must not restrict the flow of heat by more than 25%.