Wing Enterprises IOMWDF-1 Section III Installation, Locating the Unit, Location of Accessories

Page 3

SECTION III - INSTALLATION

This equipment must be installed and wired in accordance with regulations of the National Board of Fire Under- writers, National Electrical Code, and local governing bodies. The following recommendations are not intended to supplant any requirements of federal, state, or local codes having jurisdiction. Authorities having jurisdiction should be consulted before installations are made. Local codes may require additional safety controls and/or interlocks.

All installations in airplane hangers must be in accordance with current ANSI/NFPA No. 409. All installations in public garages must be in accordance with the current Standard for Parking Garages, NFPA No. 88A, or the Standard for Repair Garages, NFPA No. 88B, and with CAN/CGA B149 Installation Codes.

CAUTION: Do not install heating system in corrosive or flammable atmospheres! Premature failure of, or severe damage to the unit will result!

CAUTION: Heating system must not be installed

Recirculation of room air is not permitted. All air must be ducted from the outdoors.

If in doubt regarding the application of this appliance, consult the factory.

Locate the unit exactly level. Special attention should be given to the duct, electrical, and fuel connection points. Install duct work with adequate flexible connections to isolate vibrations from the duct work. All duct work should have taped or caulked seams. Duct work should be properly sized so as not to inhibit airflow. This information should be cross-checked with the position of support beams and stand pipes to insure that clearance dimensions coincide with those of the unit. The minimum clearance to combustible material must be maintained as listed in Table 1.

Table 1

Minimum clearance to combustible material and access

clearance (consult local codes and regulations)

Clearances to Combustible Material

in locations where air for combustion would contain chlorinated, halogenated or acidic vapors. If located in such an environment, premature failure of the unit will occur!

A. Handling the Equipment

The Direct Gas-Fired unit has been designed for rigging and handling through the use of special lifting lugs installed on the ends of each unit. As explained previously, the basic

 

Vertical Units

Front*

36 inches

Rear

6 inches

Right

6 inches

Left

6 inches

Top

12 inches

Floor

Zero

Horizontal Units

36inches

6 inches

6 inches

6 inches

12inches

6 inches

unit is designed for shipping in one piece where shipping limitations allow. Some optional accessories may require field mounting.

When unloading and setting the unit, use the lifting lugs provided or move the equipment on rollers. Hooks, jacks or chains must not be used around the casing, main control panel or exterior mounted controls.

During transit, unloading and setting of the unit, bolts and nuts may have become loosened, particularly in the pillow block ball bearing assemblies in the fan section. It is recommended that all nuts and set screws be tightened. Turn fan shaft by hand to make certain that blower does not rub against blower housing, and that bearing set screws are tight.

Open the cover on the electrical control box located on the unit. Inspect all wire terminals and wiring terminations to ensure that all connections are tight.

If this unit is not installed immediately, cover all openings that might be exposed to the weather. Rotate fan monthly.

B. Locating the Unit

Prior to locating the unit, authorities having jurisdiction should be consulted before installations are made. Approval permits should be checked against the unit received.

* Consider control side as front of unit.

On outdoor curb mounted installations, flash and seal roof curb to prevent leakage. The cross section of factory provided curb is formed to accept wood nailing strip and insulation provided by others.

C. Location of Accessories

Where applicable, standard or optional accessories will be placed inside the fan section of the unit for shipment, and must be removed and installed by the mechanical or electrical contractor.

Field provided discharge or inlet dampers must be equipped with an end switch and interlocked to insure maximum design opening before starting and running circuits may be energized.

Field constructed intake accessories should be properly designed to minimize the entry of rain and snow.

Adequate building relief must be provided, so as to not over-pressurize the building, when the heater is operating at its rated capacity. This can be accomplished by taking into account, through standard engineering methods, the struc- ture’s designed infiltration rate, by providing properly sized relief openings, by interlocking a powered exhaust system, or by a combination of these methods.

3

Image 3
Contents IOMWDF-1 Section II General Information Section I ForwardSection III Installation Location of AccessoriesLocating the Unit Field Piping Field Wiring and Remote Control InstallationLocating Temperature Controls Electrical ConnectionsPre Start-Up Suggested Tools and Instruments Section IV PRE START-UPSection V Unit START-UP Setting BurnerSetting Main Flame Safety Controls CheckSuggested Control Settings Section VI Unit ShutdownExtended Shutdown Emergency Shutdown only System without Pilot Symptom Cause Remedy Section VII TroubleshootingValve does not open, replace 001004 001003 Troubleshooting Guide Series 14 Discharge Temperature ControlSymptom Possible Cause Field Test Remedy Fire Electronics Remote Temperature Consult factory for other Series 44 Room Temperature Control Series 44 Room Temperature Control Check Safety Shutdown Performance Maintenance Schedule Speed Temperature Cleanliness Interval Lubrication Instructions Manufacturer Bearing TypeAir Filters Gaskets Belt Tension and Adjustment4.6 8.6Section IX Maxon NP-I Airlo Burners Inspection and Maintenance of Gas PortsHigh Fire Manifold Adjustments Low Fire or Bypass AdjustmentsMR212 Valve Section Preliminary Circuit Analysis SystemSection XI Replacement Parts Section XII Recirculation For Canadian Installations only