Wing Enterprises IOMWDF-1 specifications Section VI Unit Shutdown, Suggested Control Settings

Page 7

C.Gas Pressure Switches - Operate unit in Heat mode. The low pressure switch will trip out and must be reset before resuming operation when the inlet gas valve is turned off during operation.The high pressure switch may be checked out by reducing the setting of its trip point below unit operating pressure. It should then trip out and shut off the burner. Return the adjustment to its original setting and reset to resume operation.

When checking operation of gas pressure switches on systems without pilot the heat switch will have to be turned off for approximately five seconds to reset the ignition control.

D.Air Pressure Switches - The high air pressure switch is checked by removing the sensing tube from the enter- ing air side of the burner. Switch operation will shut off the burner. Recycle is automatic when the sensing tube is replaced.The low air pressure switch is checked by removing the sensing tube from the leaving air side of the burner. Switch operation will shut off the burner. Recycle is automatic when the sensing tube is replaced.

When checking operation of air pressure switches on systems without pilot the heat switch will have to be turned off approximately five seconds to reset the igni- tion control.

E.Temperature Controls – These controls are checked by adjusting control settings to a lower temperature setting while the unit is operating on high fire and observing cutoff. The controls should be reset to settings shown below:

 

Suggested Control Settings

TC-01

Room Thermostat

Customer Discretion

TC-03

On-Off Inlet Ductstat

 

65°F

TC-08

Freeze Thermostat

 

3 min.,...45°F

PS-04

Low Gas Pressure Switch

1.0”w.c

PS-07

High Gas Pressure Switch

 

125% of firing rate

TC-09

Night Set Back Room

Customer Discretion

TC-52

Remote Temperature Selector ....

Customer Discretion

FL-02

High Temperature Limit (manual)

........ Not adjustable

RE-26

High Limit Discharge Ductstat

................................

95°F

RE-26

Low Limit Discharge Ductstat

................................

55°F

PS-12

Clogged Filter Switch

Adjust to Field Conditions

PS-13

Building Pressure Switch ..

Adjust to Field Conditions

SECTION VI - UNIT SHUTDOWN

A. Extended Shutdown -

B. Emergency Shutdown ONLY -

1.Set the Heat OFF/ON switch to the OFF, then turn the Fan switch to the OFF position.

2.Close all manual gas valves.

3.Open the main electrical disconnect switch.

1.Open the main electrical disconnect switch.

2.Close all manual gas valves.

7

Image 7
Contents IOMWDF-1 Section II General Information Section I ForwardLocation of Accessories Section III InstallationLocating the Unit Field Piping Field Wiring and Remote Control InstallationLocating Temperature Controls Electrical ConnectionsPre Start-Up Suggested Tools and Instruments Section IV PRE START-UPSection V Unit START-UP Setting BurnerSetting Main Flame Safety Controls CheckSection VI Unit Shutdown Suggested Control SettingsExtended Shutdown Emergency Shutdown only System without Pilot Symptom Cause Remedy Section VII TroubleshootingValve does not open, replace 001004 001003 Series 14 Discharge Temperature Control Troubleshooting GuideSymptom Possible Cause Field Test Remedy Fire Electronics Remote Temperature Consult factory for other Series 44 Room Temperature Control Series 44 Room Temperature Control Check Safety Shutdown Performance Maintenance Schedule Lubrication Instructions Manufacturer Bearing Type Speed Temperature Cleanliness IntervalAir Filters Gaskets Belt Tension and Adjustment4.6 8.6Section IX Maxon NP-I Airlo Burners Inspection and Maintenance of Gas PortsLow Fire or Bypass Adjustments High Fire Manifold AdjustmentsMR212 Valve Section Preliminary Circuit Analysis SystemSection XI Replacement Parts Section XII Recirculation For Canadian Installations only