Wing Enterprises IOMWDF-1 specifications MR212 Valve, High Fire Manifold Adjustments

Page 21

SECTION X - MAXITROL VALVE ADJUSTMENTS

AND PRELIMINARY CIRCUIT ANALYSIS

MR212 Valve

M411, 511, 611 Valve

High Fire Manifold Adjustments

1.Disconnect wires from amplifier terminal #4 (Series 14), or #2 and #4 (Series 44). This causes the valve to call for continuous high fire.

2.Remove seal cap (A) and turn regulator pressure adjusting screw to obtain desired manifold pressure. (Clockwise rotation increases pressure.)

3.Reconnect the wires to amplifier terminal #4 (Series 14), or #2 and #4 (Series 44).

NOTE: If low bypass is on maximum, the desired high fire outlet pressure may not be achieved.

Low Fire or Bypass Adjustments

1.Disconnect wire from amplifier terminal #8. This causes valve to call for continuous low fire.

2.Remove cap (B) and loosen lock screw (C). Turn (D) to desired low fire adjustment. (Clockwise rotation reduces minimum flow rate.)

3.Tighten screw (C), replace cap (B) and reconnect wire to amplifier to terminal #8.

High Fire Manifold Adjustments

1.Disconnect wires from amplifier terminal #4 (Series 14), or #2 and #4 (Series 44). This causes the valve to call for continuous high fire.

2.Adjust the pressure regulator to obtain the rating plate manifold pressure.

3.Reconnect the wires to amplifier terminal #4 (Series 14) or #2 and #4 (Series 44).

Low Fire or Bypass Adjustments

1.Disconnect wire from amplifier terminal #8. This causes the valve to call for continuous low fire.

2.Remove cap (A) and turn adjusting screw (B) to desired low fire adjustment. (Clockwise rotation reduces minimum flow rate.)

3.Replace cap (A) and reconnect wire to amplifier terminal #8.

21

Image 21
Contents IOMWDF-1 Section II General Information Section I ForwardSection III Installation Location of AccessoriesLocating the Unit Locating Temperature Controls Field Wiring and Remote Control InstallationElectrical Connections Field PipingPre Start-Up Suggested Tools and Instruments Section IV PRE START-UPSetting Main Flame Setting BurnerSafety Controls Check Section V Unit START-UPSuggested Control Settings Section VI Unit ShutdownExtended Shutdown Emergency Shutdown only System without Pilot Symptom Cause Remedy Section VII TroubleshootingValve does not open, replace 001004 001003 Troubleshooting Guide Series 14 Discharge Temperature ControlSymptom Possible Cause Field Test Remedy Fire Electronics Remote Temperature Consult factory for other Series 44 Room Temperature Control Series 44 Room Temperature Control Check Safety Shutdown Performance Maintenance Schedule Speed Temperature Cleanliness Interval Lubrication Instructions Manufacturer Bearing TypeAir Filters 4.6 Belt Tension and Adjustment8.6 GasketsSection IX Maxon NP-I Airlo Burners Inspection and Maintenance of Gas PortsHigh Fire Manifold Adjustments Low Fire or Bypass AdjustmentsMR212 Valve Section Preliminary Circuit Analysis SystemSection XI Replacement Parts Section XII Recirculation For Canadian Installations only