Vermont Casting RDVOD 3369 manual Fan Override During Auto Mode, Disable Thermostat Function

Page 27

Auto Mode

In the AUTO mode, the room temperature, set tem- perature, flame and fan levels will be shown. AUTO will appear next to both the flame and fan icons.

When the control is in the AUTO mode, the main burner will turn on/off or modulate based on the heat needed to maintain the set temperature. The flame level will change automatically to optimize the heat output needed to maintain the set temperature. To change the set temperature, press the up or down key. Pushing a key once will change the temperature by one degree.

In the AUTO mode, the fan speed will increase with increasing flame height or decrease with decreasing flame height. “AUTO” is displayed next to the flame and fan icons.

Fan Override During Auto Mode

If a lower or higher fan speed is desired when operating in the AUTO mode, the fan speed can be overridden by pushing the fan button followed by the up or down key. Pushing a key once will change the fan level by one unit. In this mode “AUTO” is displayed next to the flame icon and “MANUAL” is displayed next to the fan icon.

Change Between F/C Temperature Units

Push the up and down arrow keys simultaneously for at least 3 seconds to toggle between Fahrenheit and Celsius units.

Disable Thermostat Function

To disable the thermostat function in the AUTO mode, push the time and down keys simultaneously for at least 3 seconds.

To Change Batteries

1.Remove cover on the backside of the transmitter. Install 3 AAA batteries as shown and reattach cover.

2.Once steps 1-3 in OPERATION are completed, receiver/valve and transmitter are now ready. Press any button on transmitter for recognition process to occur between the receiver/valve and transmitter.

3.Use functions as described in TRANSMITTER sec- tion.

Troubleshooting

1.Locate LED light on valve.

2.LED will blink after every valid command received by the transmitter; this is not an error.

3.Failure codes may occur anytime after pilot burner is lit.

4.Sequence is failure code followed by light not blink- ing for 30 seconds.

5.In the event of multiple failure codes, next failure code follows previous failure code by approximately 3 seconds.

Radiance Direct Vent /Natural Vent Gas Heater

 

 

Pilot As-

 

 

 

sembly

 

 

 

 

Blower

 

 

Red

FAN

 

 

 

 

Red

White

 

 

 

 

 

White

 

 

 

 

White Dots

 

 

Antenna

 

FP1038

 

 

Valve

 

 

(Bottom View)

Fig. 51 Comfort Valve wiring diagram.

If an Error Code 3 is observed while performing the testing, complete the following:

1.Make sure the spade connectors are pushed all the way on. If rhe Error Code 3 is still showing, then go to the next step.

2.Switch the front two thermopile leads with the back two. Be sure the white lead is connected to the spade with the white dot next to it. If the Error Code 3 is still showing, replace the thermopiles.

If an Error Code 8 is observed while performing the testing, complete the following:

1.Confirm the valve is not in REMOTE mode.

If the valve is producing Error Code 8 and in RE- MOTE mode, the valve is defective and should be replaced.

If the valve is in LOCAL mode and producing Error Code 8, then go to the next step.

2.Slide the Remote/Local switch to REMOTE and teach the valve a transmitter (see item 6, page 32). The Error Code will clear itself after approximately 1.5 minutes and return to normal operation.

LED Count

Service Action

8Replace valve

7Confirm stepper motor connection exists

5 Confirm fan connection exists and works

4 Confirm gas type; jumper in place

3 Replace thermopiles

2 Turn fan ON

NOTE: Some keys are not active.

20004188

27

Image 27
Contents Radiance Table Of Contents Verify proper operation after servicing Installation & Operating InstructionsRadiance dimensions Radiance Direct Vent/Natural Vent Stove DimensionsInstallation Requirements Locating The StoveClearance Requirements Wall Centerline from Floor Wall and Ceiling ClearancesHearth Requirements Horizontal Termination Direct Vent only Gas SpecificationsGas Inlet and Manifold Pressures High ElevationsRestictor Plate is used on Direct Vent installations only Vertical Termination Direct Vent onlyVent Termination Clearances Location of Vent Termination General Venting Information Termination Location Canadian Installations1 US Installations2Plate supplied with the stove is not used Venting Requirements Natural Vent OnlyVenting Requirements and Options Direct Vent only Unpack and Assemble Legs Assembly ProceduresParts Bag Contents Tools RequiredFan kit components Install the Optional FanAttach the Inner Vent Assembly to the stove Venting System Assembly Direct Vent General InformationInstall the Vent Adapter Pipe For Canadian installations The venting system mustSide Wall Termination Assembly Install the Outer Adapter Pipe. Orient the vertiDiscard the inner starter pipe shipped with the log Measure the horizontal length Vent Termination Below Grade Vertical Through the Roof Vent AssemblyInstall firestops and attic insulation shield Venting System Assembly Natural Vent General InformationInstall Log Set Install the Vent PipeConnect the Gas Supply Line Install the left and right rear logs and the right logThermostat Connection optional Install ON/OFF SwitchInstall the Mesh and Grille Burner InformationYour First Fire Flame & Temperature AdjustmentFlame Characteristics OperationTo Turn Off Gas To Heater Lighting and Operating InstructionsSymptom Possible Causes Corrective Action Troubleshooting / Honeywell #8420 Gas Control SystemDelay Timer Mode Shut Off ProcedureTransmitter Operation Off Mode On Manual ModeDisable Thermostat Function Auto ModeFan Override During Auto Mode Change Between F/C Temperature UnitsLocal Path On Path Auto Path Models 3350, 3351, 3360 thru 3369 R Models Only Conversion PrecautionsConversion Procedure Fuel Conversion InstructionsPilot Type 1 SIT Pilot Pilot type 2 Honeywell PilotModels 3352, 3354, 3390 thru 3399 RF Models Only Conversion to Natural Gas Input BTU/h Air Shutter AdjustmentInjector Orifice Size Matrix All ModelsMaintenance Gasket Replacement Inspect the Vent System AnnuallyCheck the Gas Flame Regularly BLK Wiring DiagramsDescription Radiance Direct Vent/Natural Vent Gas Heater RdvodRadiance Direct Vent/Natural Vent Gas Heater Rdvod Optional Accessories Limited Lifetime Warranty Model EnerGuide Ratings Fireplace Efficiency % Efficiency Ratings

RDVOD 3360, RDVOD 3369, RDVOD 3354, RDVOD 3350, RDVOD 3399 specifications

Vermont Castings is renowned for its exceptional wood stoves and fireplaces, and the RDVOD series stands as a testament to their commitment to craftsmanship, efficiency, and innovative technology. The RDVOD 3399, RDVOD 3350, RDVOD 3360, RDVOD 3390, and RDVOD 3369 models embody a blend of traditional aesthetics and modern functionality, making them standout choices for homeowners seeking warmth and style.

One of the main features of the RDVOD series is its high-efficiency rating. These models utilize Vermont Castings' advanced combustion technology, which optimizes fuel usage, resulting in more heat output from less wood. This not only reduces overall wood consumption but also minimizes emissions, making these stoves environmentally friendly options for heating.

The RDVOD stoves are designed with robust cast iron construction, ensuring durability and longevity. The cast iron provides excellent heat retention and leads to a more consistent warmth in the home. Additionally, the stylish design of these models allows them to seamlessly integrate into various home decors, from rustic to contemporary.

Key technologies incorporated into these stoves include the patented "Biltmore" technology, which enhances the efficiency of the burning process. This technology ensures that the fire burns hotter and cleaner, providing more heat while reducing the pollutants released into the atmosphere. The adjustable air controls allow users to easily manage the flame and heat output, ensuring personalized comfort.

The RDVOD 3399, RDVOD 3350, RDVOD 3360, RDVOD 3390, and RDVOD 3369 also feature large glass doors that showcase the fire, adding visual appeal to any living space. The seamless integration of the glass doors with the cast iron design contributes to the overall aesthetic while allowing for easy monitoring of the fire.

Safety is another priority in the design of the RDVOD stoves. They come equipped with features like a removable ash pan, which simplifies cleanup and maintenance, and the air-wash system, which keeps the glass clean, providing an unobstructed view of the flames.

In summary, the Vermont Castings RDVOD series – including models 3399, 3350, 3360, 3390, and 3369 – exemplifies high efficiency, exquisite craftsmanship, and thoughtful technology. With their combination of aesthetic appeal and functional performance, they offer an optimal heating solution for today’s homeowners seeking comfort and elegance in their living spaces.