Madison Woodburning Stove
Madison 1655 Series Clearance Chart
Use the chart below together with the diagrams on the next page to determine the minimum clearance required for your particular installation. In any case, it is always advisable to locate the stove as far away from walls as pos- sible in order to take full advantage of the radiant properties of cast iron.
Stove clearances are measured between the cast iron Top Plate of the stove and the combustible surface. Note that the cast iron back on the Madison protrudes 5” (127mm) out from the stovetop, and will therefore be closer to the wall than the top of the stove.
Chimney Connector clearances are measured between the connector surface and the combustible surface. For
Use NFPA 211 default clearance or manufacturer’s installation specifications for those configurations not tested.
UNPROTECTED SURFACES | PROTECTED SURFACES |
|
|
|
| Parallel Installation | Corner | Parallel Installation | Corner |
|
| ||||
|
| STOVE CLEARANCE |
| Installation | Installation |
|
| ||||||
|
|
|
|
|
|
|
|
| |||||
|
|
| Side | Rear | Corner | Side | Rear | Corner |
|
| |||
|
|
|
|
|
| ||||||||
|
| Top exit, no heat shields |
| A 21” | B 24” | C 21” | D 12” | E 14” | F 10” |
|
| ||
|
|
|
| (533mm) | (610mm) | (533mm) | (305mm) | (356mm) | (250mm) |
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Top exit, heat shields on stove, |
| G 21” | H 24” | I 21” | J 12” | K 14” | L 10” |
|
| ||
|
| no shields on single wall |
|
|
| ||||||||
|
|
| (533mm) | (610mm) | (533mm) | (305mm) | (356mm) | (250mm) |
|
| |||
|
| connector |
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| Top exit, heat shield on stove, |
| M 21” | N 22” | O 18” | P 12” | Q 14” | R 8” |
|
| ||
|
| heat shield on single wall |
|
|
| ||||||||
|
|
| (533mm) | (559mm) | (457mm) | (305mm) | (356mm) | (203mm) |
|
| |||
|
| connector |
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| Top exit, heat shield on stove, |
| S 16” | T 12” | U 18” | V 12” | W 11” | X 8” |
|
| ||
|
| double wall chimney connector |
| (406mm) | (305mm) | (457mm) | (305mm) | (279mm) | (203mm) |
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Rear exit, no heat shields |
| Y 18” | Z 20” | N/A | AA 12” | BB 15” | N/A |
|
| ||
|
|
| (457mm) | (508mm) | (305mm) | (381mm) |
|
| |||||
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Rear exit, heat shields |
| CC 16” | DD 18” | N/A | EE 12” | FF 12” | N/A |
|
| ||
|
|
| (406mm) | (457mm) | (305mm) | (305mm) |
|
| |||||
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| CHIMNEY CONNECTOR |
| UNPROTECTED SURFACE / Vertical | PROTECTED SURFACE / Vertical |
|
| ||||||
|
| CLEARANCE |
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Without Connector Heat Shields |
|
| 19” (483mm) |
|
| 13” (330mm) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| With Connector Heat Shields |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
| UNPROTECTED SURFACE / Horizontal | PROTECTED SURFACE / Horizontal |
|
| ||||||
|
|
|
| 23” (584mm) |
|
| 23” (584mm) |
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| FRONT CLEARANCE |
|
|
| ALL INSTALLATIONS |
|
|
|
|
|
| |
|
| TO COMBUSTIBLES* |
|
|
| 48" (1220mm) |
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
*A distance of 48" must be maintained between the stove and moveable combustible items such as drying clothes, furniture, firewood, etc.
12 | 30001453 |