Vanguard Heating UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER Cleaning and Maintenance, Logs

Page 18
Injector Holder
(May Be Brass or Aluminum Depending on Model)

VANGUARD FLAME-MAX®

UNVENTED PROPANE/LP GAS LOG HEATER

CLEANING AND MAINTENANCE

WARNING: Turn off heater and let cool before cleaning.

CAUTION: You must keep control areas, burner, and circu- lating air passageways of heater clean. Inspect these areas of heater before each use. Have heater inspected yearly by a quali- fied service person. Heater may need more frequent cleaning due to excessive lint from carpeting, pet hair, bedding material, etc.

CLEANING BURNER INJECTOR HOLDER AND PILOT AIR INLET HOLE

The primary air inlet holes allow the proper amount of air to mix with the gas. This provides a clean burning flame. Keep these holes clear of dust, dirt, and lint. Clean these air inlet holes prior to each heating season. Blocked air holes will create soot. We rec- ommend that you clean the unit every 2,500 hours of operation or every three months.

We also recommend that you keep the burner tube and pilot assembly clean and free of dust and dirt. To clean these parts we recom- mend using compressed air no greater than 30 PSI. Your local computer store, hard- ware store, or home center may carry com- pressed air in a can. You can use a vacuum cleaner in the blow position. If using com- pressed air in a can, please follow the direc- tions on the can. If you don't follow direc- tions on the can, you could damage the pilot assembly.

1.Shut off the unit, including the pilot. Allow the unit to cool for at least thirty minutes.

2.Inspect burner, pilot, and primary air inlet holes on injector holder for dust and dirt (see Figure 25).

3.Blow air through the ports/slots and holes in the burner.

4.Check the injector holder located at the end of the burner tube again. Remove any large particles of dust, dirt, lint, or pet hairs with a soft cloth or vacuum cleaner nozzle.

5.Blow air into the primary air holes on the injector holder.

6.In case any large clumps of dust have now been pushed into the burner repeat steps 3 and 4.

Clean the pilot assembly also. A yellow tip on the pilot flame indicates dust and dirt in the pilot assembly. There is a small pilot air inlet hole about two inches from where the pilot flame comes out of the pilot assembly (see Figure 26). With the unit off, lightly blow air through the air inlet hole. You may blow through a drinking straw if compressed air is not available.

Burner

Tube

Primary Air Inlet Holes (Shape of Holes May Vary by Model)

Figure 25 - Injector Holder On Outlet Burner Tube

Ports/Slots

Burner

Tube

Pilot

Assembly

Pilot Air

Inlet Hole

LOGS

If you remove logs for cleaning, refer to Installing Logs, page 14, to properly re- place logs.

Replace log(s) if broken or chipped (dime-sized or larger).

MAIN BURNER

Periodically inspect all burner flame holes with the heater running. All slotted burner flame holes should be open with yellow flame present. All round burner flame holes should be open with a small blue flame present. Some burner flame holes may be- come blocked by debris or rust, with no flame present. If so, turn off heater and let cool. Either remove blockage or replace burner. Blocked burner flame holes will create soot.

Figure 26 - Pilot Inlet Air Hole

18

105274

Image 18
Contents 18, 24, 30, and 36 Remote Ready Model OWNER’S Operation and Installation ManualWhat to do if YOU Smell GAS Save this manual for future referenceSafety Information Vanguard FLAME-MAX Unvented PROPANE/LP GAS LOG HeaterLocal Codes Unpacking Product Features Remote Control AccessoriesProduct Identification Unusually Tight Construction AIR for Combustion and VentilationProviding Adequate Ventilation Confined and Unconfined SpaceAIR for Combustion Ventilation Determining FRESH-AIR Flow for Heater LocationDetermining if You Have a Confined or Unconfined Space Building Ventilation AIRVentilation Air From Inside Ventilation Air From OutdoorsLOG Sizing Requirements InstallationMinimum Fireplace Clearance to Combustible Materials Check GAS TypeIf Using Mantel If Not Using MantelMinimum Noncombustible Material Clearances Floor Clearances Determining Minimum Mantel Clearance When using a HoodMantel Clearances Determining Minimum Mantel ClearanceInstalling Damper Clamp Accessory for Vented Operation Installing Heater Base AssemblyChimney Minimum Permanent Height ft Flue Opening sq. ins Installation Items Needed Attaching Flexible Gas Hose to HeaterConnecting to GAS Supply External regulator not suppliedChecking GAS Connections Pressure Testing Heater Gas ConnectionsPressure Testing Gas Supply Piping System Test Pressures Equal To or Less Than 1/2 PsigInstalling Logs Place lava rock around base of heaterFor Your Safety Read Before Lighting Operating HeaterLighting Instructions Manual Lighting Procedure To Turn OFF GAS To ApplianceOptional Remote Operation Pilot Flame Pattern OperatingInspecting Burners Burner Primary AIR HolesCleaning and Maintenance Cleaning Burner Injector Holder and Pilot AIR Inlet HoleLogs Troubleshooting Observed Problem Possible CauseObserved Problem Possible Cause Remedy Gas leak. See Warning statement at TopIllustrated Parts Breakdown Parts List VYD18PRA, VYD24PRA VYD30PRA, and VYD36PRReplacement Parts Wiring DiagramSpecifications Service HintsAccessories Warranty Information International

UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER specifications

The Vanguard Heating Unvented (Vent-Free) Propane/LP Gas Log Heater is a remarkable home heating solution that combines efficiency, convenience, and aesthetic appeal. Designed to deliver warmth without the need for traditional venting, this heater stands out for its innovative technology and user-friendly features.

One of the main attractions of the Vanguard unvented gas log heater is its ability to provide consistent heat while conserving energy. The unit operates using propane or LP gas, making it an excellent option for homes without access to natural gas. With a high heat output, it efficiently warms spaces while potentially reducing heating costs compared to conventional systems.

The design of the Vanguard heater incorporates advanced catalyst technology, which ensures that combustion is clean and efficient. This technology minimizes emissions, making it an environmentally friendly choice for homeowners concerned about their carbon footprint. Furthermore, the heater is equipped with an oxygen depletion sensor (ODS) that automatically shuts off the gas supply if oxygen levels fall below safe thresholds, ensuring peace of mind for users.

Aesthetically, the Vanguard model features realistic log designs that replicate the appearance of a traditional wood-burning fireplace. This adds warmth and charm to any living space. The adjustable flame height allows users to customize their heating experience to suit their needs or mood. The controls are designed for ease of use, allowing for simple operation whether the heater is used for primary warmth or supplemental heat.

Safety is a key characteristic of the Vanguard unvented gas log heater. Besides the ODS mentioned earlier, the heater is built with durable materials that ensure longevity and reliability. It can be installed in various locations, including bedrooms and living rooms, as long as the manufacturer's guidelines are followed.

Installation of the Vanguard heater is relatively straightforward, requiring minimal modifications to existing spaces. This flexibility makes it appealing for both new constructions and retrofits. Additionally, the absence of venting means that installation costs are often lower than with vented units.

In summary, the Vanguard Heating Unvented Propane/LP Gas Log Heater combines advanced technology, stylish design, and crucial safety features, making it a viable choice for those seeking efficient indoor heating solutions. Its ease of installation and operation further enhances its attractiveness to modern homeowners. Whether for cozy family gatherings or quiet evenings at home, this heater is an excellent investment in comfort and warmth.