OWNER’S MANUAL
INSTALLATION
Continued
MANTEL CLEARANCES
In addition to meeting noncombustible mate- rial clearances, you must also meet required clearances between fireplace opening and mantel shelf. If you do not meet the clear- ances listed below, you will need a hood.
Determining Minimum Mantel Clearance
If you meet minimum clearance between mantel shelf and top of fireplace opening, a hood is not required (see Figure 6, page 9).
Determining Minimum Mantel Clear- ance When using a Hood
If minimum clearances in Figure 6 are not met, you must have a hood. When using a hood there are still certain minimum mantel clear- ances required. Follow minimum clearances shown in Figure 7, page 9 when using hood.
|
|
| 10" | Mantel Shelf |
|
|
|
| ||||
|
|
|
|
|
|
|
| Underside of | ||||
|
|
| 8" |
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| Mantel Shelf | |||
|
|
|
|
|
|
|
|
|
|
| ||
|
|
| 6" |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| ||
|
|
| 2 1/2" |
|
|
|
|
|
| All minimum | ||
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| distances are |
Minimum Non- |
|
| (A) |
|
|
|
|
|
| in inches | ||
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
| ||||
Combustible |
|
|
|
|
|
|
|
| Log Set | |||
|
|
|
|
|
|
|
|
| ||||
Material |
|
|
|
|
|
|
|
|
| |||
|
| 12" | 18" |
| 20" | 22" | 24" |
| 24"/30"/36" Models | |||
|
|
|
|
|
|
| ||||||
|
|
|
|
| 8" | 8" |
| 14" | 163/4" | 20" |
| 18" Model |
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
| Top of Fireplace | |
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| Opening | |
|
|
|
| Minimum Non- | Distances to |
|
|
| ||||
|
|
|
| Combustible |
| Underside of |
|
|
| |||
|
|
|
| Material Height | Mantel |
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Figure 6 - Minimum Mantel Clearances Without Using Hood
Mantel Shelf
NOTICE: If your installation does not meet the minimum clearances shown, you must do one of the following:
•operate the logs only with the flue damper open
•raise the mantel to an accept- able height
•remove the mantel
FLOOR CLEARANCES
12"
10"
8"
6"
2 1/2"
Minimum Non-
Combustible
Material
8"
Min.
12"
15"
18"
Underside of
Mantel Shelf
All minimum distances are in inches
Log Sets
20" All Models
Top of Fireplace Opening
A.If installing appliance on the floor level, you must maintain the minimum dis- tance of 14" to combustibles (see Fig- ure 8, page 9).
B.If combustible materials are less than 14" to the fireplace, you must install appliance at least 5" above the combus- tible flooring (see Figure 9, page 9).
Hood (GA6050, | Distances to |
GA6052 or GA6053) | Underside of |
| Mantel |
Figure 7 - Minimum Mantel Clearances When Using Hood
14"
Combustible Material
Hearth Combustible
Min.
5”
Material
Min.
Figure 8 - Minimum Fireplace Clearances | Figure 9 - Minimum Fireplace Clearances |
If Installed at Floor Level | Above Combustible Flooring |
| Continued |
104309 | 9 |