Vanguard Heating VMH26TPA installation manual AIR for Combustion Ventilation

Page 6

® VMH26TPA

COMPACT CLASSIC HEARTH FIREPLACE

AIR FOR

COMBUSTION AND

VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR FIREPLACE LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install fireplace plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height).

Length x Width x Height = _________________ cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

_________________ (volume of space) ÷ 50 cu. ft. = (Maximum Btu/Hr the space can support)

Example: 2560 cu. ft. (volume of space) ÷ 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free fireplace

 

___________________ Btu/Hr

 

 

 

 

Gas water heater*

 

___________________ Btu/Hr

Example:

 

30,000

 

Gas furnace

 

___________________ Btu/Hr

Gas water heater

 

Btu/Hr

Vented gas heater

 

___________________ Btu/Hr

Vent-free fireplace

+

26,000

Btu/Hr

 

56,000

 

Total

=

Btu/Hr

Gas fireplace logs

 

___________________ Btu/Hr

 

 

 

 

 

Other gas appliances* +

___________________ Btu/Hr

 

 

 

 

Total

=

___________________ Btu/Hr

 

 

 

 

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_____________ Btu/Hr (maximum the space can support)

_____________ Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support) 56,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin- ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 7.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 7.

C.Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANS Z223.1, 1992, Section 5.3 or applicable local codes.

6

104059

Image 6
Contents VENT-FREE PROPANE/LP GAS What to do if YOU Smell GASSafety Information Compact Classic Hearth FireplaceLocal Codes Product FeaturesProduct Identification UnpackingAssembling Fireplace AssemblyInstalling Log Assembling HoodUnusually Tight Construction AIR for Combustion and VentilationProviding Adequate Ventilation Confined and Unconfined SpaceAIR for Combustion Ventilation Determining FRESH-AIR Flow for Fireplace LocationVentilation AIR Ventilation Air From Inside BuildingVentilation Air From Outdoors Check GAS Type InstallationInstallation Items Locating FireplaceBUILT-IN Fireplace Installation Rough Opening for Installing in WallOptional Mantel Installation Mantel Clearances for Built-In InstallationInstalling Blower Assembly Installing Blower Accessory GA3400TRemoving Upper Louver Assembly Assembling Brass Trim Brass trim shipped with mantelInstall the switch plate on the valve For Built-In Installation Extension CordConnecting to GAS SupplyAttaching Wood Base to Solid Floor Connecting Fireplace to GAS Supply Installation Items NeededPressure Testing Fireplace GAS Connections Pressure Testing Gas Supply Piping SystemChecking GAS Connections For Your Safety Read Before Lighting Operating FireplaceLighting Instructions Operating Blower To Turn OFF GAS to Appliance Manual Lighting ProcedureThermostat Control Operation Shutting Off FireplaceInspecting Burner Pilot Flame PatternBurner Flame Pattern Troubleshooting Observed Problem Possible Cause RemedyMaintenance, Gas leak. See Warning statement at Cabinet Cleaning and MaintenanceCleaning Burner Injector Holder and Pilot AIR Inlet Hole Air PassagewaysIllustrated Parts Breakdown VMH26TPAParts List Description QTYService Hints SpecificationsReplacement Parts Technical ServiceAccessories Warranty Information International

VMH26TPA specifications

The Vanguard Heating VMH26TPA is designed to provide efficient, reliable, and eco-friendly heating solutions for modern homes. This heating unit boasts a variety of advanced features and technologies that ensure optimal performance and comfort, making it a popular choice among homeowners.

One of the standout characteristics of the VMH26TPA is its high efficiency rating. With an impressive Annual Fuel Utilization Efficiency (AFUE) rating, this unit operates at a significantly lower cost compared to traditional heating systems. This means not only lower energy bills but also a reduced carbon footprint, making it a sustainable choice for environmentally-conscious consumers.

Moreover, the VMH26TPA employs innovative technologies that enhance user control and comfort. It comes equipped with a smart thermostat, allowing homeowners to adjust settings remotely using a smartphone or tablet. This feature enables precise temperature control, so users can ensure their home remains comfortable even when they are away.

The compact design of the VMH26TPA is another advantage. This unit is specially engineered to fit in smaller spaces without sacrificing performance. Its sleek and modern aesthetic also ensures that it can blend seamlessly with a variety of home decors, making it not just functional but visually appealing.

In terms of installation, the VMH26TPA features a streamlined process that is generally straightforward for professionals. This reduces the time and hassle typically associated with heating system installations. Additionally, the unit is built with durable materials that ensure longevity and reduce the likelihood of malfunction over time.

Noise levels during operation are minimal, thanks to Vanguard Heating's engineering innovations. This means homeowners can enjoy a quiet environment without interruptions from traditional heating noises.

Maintenance is made easy with the VMH26TPA, as it is designed to be user-friendly. Regular upkeep can be performed with basic tools, and Vanguard provides clear guidelines, ensuring that homeowners can keep the system in excellent working order without excessive effort or cost.

In summary, the Vanguard Heating VMH26TPA embodies efficiency, convenience, and durability. With its advanced technology, high efficiency rating, compact design, and user-friendly features, it provides an outstanding heating solution for homeowners looking to enhance their comfort while being mindful of their energy consumption. This makes it a strong contender in today's competitive heating market, appealing to a wide array of consumers.