Water temperature below

Faulty thermostat.

Check thermostat adjustment.

settings at all times

 

Monitor thermostat as described in

 

 

Section III, Quarterly Inspection.

 

 

Replace if necessary.

 

Blown fuse in element fuse

Replace fuse.

 

block, if installed.

 

 

Heating element not working

Check to see that heating element

 

on all phases

is working on all phases, by

 

 

checking the resistance (ohms)

 

 

value for each element and

 

 

comparing with the chart included

 

 

in Section VI.

 

Heater improperly sized

Verify heater is properly sized for

 

 

the flow rate and temperature rise

 

 

of your system. See formulas

 

 

included in Section VI. Replace

 

 

elements with proper size as

 

 

necessary.

Relief valve discharges

Excessive temperature or

Temperature and pressure relief

continuously

pressure in tank

valves are made to operate if the

 

 

water temperature exceeds 210°F

 

 

or water pressure exceeds the

 

 

pressure rating of the safety relief

 

 

valve. If trouble is excessive

 

 

temperature, then thermostat is not

 

 

shutting off at the right setting and

 

 

thermostat must be replaced.

17

Image 17
Contents Electric Heater Company STRATFORD, CT Hubbell Electric Heater CompanyBOX Table of Contents Section Title Page Tank Section I General Description and ConstructionTank Connections Heating ElementControl Thermostat Temperature High Limit SwitchOuter Shell and Insulation Magnetic ContactorOptions Low Water Cut-OffVacuum Relief Valve Dial Temperature and Pressure GaugeFused Low Voltage Transformer Electro-Mechanical Timer On/Off SwitchIndividually Fused Elements Built-in Circuit BreakerSecuring of Heater Water Heater PlacementMounting Dimensions Filling the Heater Piping InstallationFinal Checks Electrical InstallationMaintenance and Operation Section III Scheduled Maintenance and OperationFreezing Quarterly InspectionAnnual Inspection Symptom Probable Cause Corrective Action / Remedy Section IV TroubleshootingPage Surface Temperature High Limit CUT-OFF Section V Servicing & Replacement of PartsImmersion Temperature High Limit CUT-OFF Heating Element Page Surface Mounted Thermostat Immersion Thermostat Magnetic Contactor Relief Valve Formulas Section VI Miscellaneous Charts and Formulas Element ChartTorque Values Section VII ABS Type Approval Program Page Page