Goodman Mfg ACVC9/AMVC95, GCVC9/GMVC95 service manual Product Design, General Operation

Page 4

PRODUCT DESIGN

General Operation

Models covered by this manual come with a new 4-wire com- municating PCB. When paired with a compatible communi- cating indoor unit and a CTK01AA communicating thermo- stat, these models can support 4-wire communication pro- tocol and provide more troubleshooting information. These models are also backward compatible with the legacy ther- mostat wiring.

The GCVC9, GCVC95, GMVC95, AMVC95, ACVC9 and ACVC95 furnaces are equipped with an electronic ignition device to light the burners and an induced draft blower to exhaust combustion products.

An interlock switch prevents furnace operation if the blower door is not in place. Keep the blower access doors in place except for inspection and maintenance.

These furnaces are also equipped with a self-diagnosing elec- tronic control module. In the event a furnace component is not operating properly, the control module's dual 7-segment LED's will display an alpha-numeric code, depending upon the problem encountered. These LED's may be viewed through the observation window in the blower access door. Refer to the Troubleshooting Chart for further explanation of the LED codes and Abnormal Operation - Integrated Igni- tion Control section in the Service Instructions for an expla- nation of the possible problem.

The rated heating capacity of the furnace should be greater than or equal to the total heat loss of the area to be heated. The total heat loss should be calculated by an approved method or in accordance with “ASHRAE Guide” or “Manual J-Load Calculations” published by the Air Conditioning Con- tractors of America.

*Obtain from: American National Standards Institute 1430 Broadway New York, NY 10018

Location Considerations

The furnace should be as centralized as is practical with respect to the air distribution system.

Do not install the furnace directly on carpeting, tile, or combustible material other than wood flooring.

When suspending the furnace from rafters or joists, use 3/8" threaded rod and 2” x 2” x 1/8” angle as shown in the Installation and Service Instructions. The length of the rod will depend on the application and clearance necessary.

When installed in a residential garage, the furnace must be positioned so the burners and ignition source are located not less than 18 inches (457 mm) above the floor and protected from physical damage by ve- hicles.

Notes:

1.Installer must supply one or two PVC pipes: one for com- bustion air (optional) and one for the flue outlet (required). Vent pipe must be either 2” or 3” in diameter, depending upon furnace input, number of elbows, length of run and

installation (1 or 2 pipes). The optional Combustion Air Pipe is dependent on installation/code requirements and must be 2” or 3” diameter PVC.

2.Line voltage wiring can enter through the right or left side of the furnace. Low voltage wiring can enter through the right or left side of furnace.

3.Conversion kits for propane gas and high altitude natural and propane gas operation are available. See High Alti- tude Derate chart for details.

4.Installer must supply the following gas line fittings, de- pending on which entrance is used:

Left -- Two 90° Elbows, one close nipple, straight pipe Right -- Straight pipe to reach gas valve.

Accessibility Clearances (Minimum)

*MVC95* MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS

(INCHES)

POSITION*

FRONT

SIDES

REAR

TOP

FLUE

FLOOR

 

 

 

 

 

 

 

 

 

Upflow

3

0

0

1

0

C

Horizontal

Alcove

6

0

4

0

C

*=

All positioning is determined as installed unit is viewed from the front.

C=

If placed on combustible floor, floor MUST be wood only.

 

NC= For instalaltion on non-combustible floors only. A combustible

 

 

subbase must be used for installations on combustible flooring.

 

 

*CVC9 MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS

 

 

 

(INCHES)

 

 

 

POSITION*

FRONT

SIDES

REAR

TOP

FLUE

FLOOR

 

 

 

 

 

 

 

 

 

Upflow

1

0

0

1

0

NC

Horizontal

Alcove

6

0

4

0

C

*=

All positioning is determined as installed unit is viewed from the front.

C=

If placed on combustible floor, floor MUST be wood only.

 

NC= For instalaltion on non-combustible floors only. A combustible subbase must be used for installations on combustible flooring.

Alcove Illustration

 

REAR

E

S

I

D

D

I

E

S

 

 

ALCOVE

24" at front is required for servicing or cleaning.

Note: In all cases accessibility clearance shall take precedence over clearances from the enclosure where accessibility clearances are greater. All dimensions are given in inches.

High Altitude Derate

When this furnace is installed at high altitude, the appropri- ate High Altitude orifice kit must be installed. This is re-

4

Image 4
Contents Technical Manual Product Identification 070Do not connect or use any device Product Design General OperationSingle Stage Thermostat Component Identification Cabinet Units Size Cabinet Units Size DATA2 Product Primary Limit Auxiliary Limit Switches 1824 Coil MatchesThermostats FiltersCounterflow Filters GMVC95 ModelFurnace Specifications AMVC95 Furnace Specifications GCVC9 GCVC90704CX GCVC90905DX GCVC91155DXFurnace Specifications GCVC95 D E LFurnace Specifications ACVC9 Furnace Specifications ACVC95 Blower Performance Specifications GMVC95/AMVC95 Heating Speed ChartsESP GMVC95/AMVC95 High Single Stage Cooling Speed Charts GMVC95/AMVC95 Low Stage Cooling Speed Charts GCVC9/ACVC9 Continuous Fan Speed Chart GMVC95/AMVC95 Continuous Fan Speed ChartGCVC95/ACVC95 Continuous Fan Speed Chart GCVC9/ACVC9 Heating Speed Charts GCVC95/ACVC95 Heating Speed Charts ESPGCVC9/ACVC9 High Single Stage Cooling Speed Charts GCVC9/ACVC9 Low Stage Cooling Speed ChartsGCVC95/ACVC95 High Single Stage Cooling Speed Charts GCVC95/ACVC95 Low Stage Cooling Speed ChartsCirculator Blower Speed Adjustment Switches Dehumidification Enable SwitchRamping Profile Performance Wiring Diagrams CVC9/*MVC95AA 24V HUMWiring Diagrams CVC9/*MVC95AB 24VHUMSchematics TerminalSchematicwiring

Goodman 90%-95% Gas Furnace Units, ACVC9/AMVC95, GCVC9/GMVC95 specifications

Goodman Manufacturing is a prominent name in the HVAC industry, known for providing energy-efficient solutions that cater to both residential and commercial environments. Among its offerings, the Goodman GCVC9/GMVC95 and ACVC9/AMVC95 models stand out as top-tier gas furnace units, with efficiency ratings between 90% and 95%. These furnaces provide an excellent balance of performance, reliability, and affordability.

The GCVC9 and GMVC95 gas furnace units are designed with advanced features that ensure optimal heating and comfort. One of the key characteristics of these models is their energy efficiency. With Annual Fuel Utilization Efficiency (AFUE) ratings of up to 95%, these furnaces convert nearly all the fuel they consume into heat, resulting in significant cost savings on energy bills. This makes them an ideal choice for homeowners looking to reduce their carbon footprint while maintaining a comfortable indoor environment.

These units are equipped with a two-stage gas valve and a variable-speed blower motor. The two-stage gas valve allows for precise temperature control by providing two levels of heating output, ensuring that the furnace runs at lower capacities during milder conditions and ramping up when more heat is needed. The variable-speed blower motor enhances comfort by providing consistent airflow, reducing temperature fluctuations, and operating more quietly than single-speed motors.

Another notable feature is the firing system, which utilizes a hot surface igniter for reliable operation. This technology enhances safety and performance, eliminating the need for a pilot light and minimizing gas waste. Additionally, both models are designed for easy installation and maintenance, with features like a compact design and convenient access to internal components.

Durability is also a hallmark of Goodman furnaces. The units are constructed with high-quality materials, including a heavy-gauge steel cabinet and a durable powder-coated finish to resist corrosion. Furthermore, Goodman offers exceptional warranties, including a lifetime heat exchanger warranty, providing peace of mind for homeowners.

In conclusion, the Goodman GCVC9/GMVC95 and ACVC9/AMVC95 gas furnace units are engineered for efficient heating with advanced technologies that enhance performance and comfort. Their high AFUE ratings, reliable ignition system, and durable construction make them excellent choices for anyone looking to invest in a reliable heating solution. With Goodman at the helm, homeowners can enjoy efficient heating without compromising on comfort or cost.