Goodman Mfg GMH95 Thermostats, Filters, Product Design, Disposable Minimum Filter Area in2

Page 10
Thermostats:

PRODUCT DESIGN

Thermostats:

NOTE: Complete lineup of thermostats can be found in the Thermostat Specification Sheets.

Filters:

Filters are required with this furnace and must be provided by the installer. The filters used must comply with UL900 or CAN/ULCS111 standards. Installing this furnace without filters will void the unit warranty.

Upflow Filters

This furnace has provisions for the installation of return air filters at the side and/or bottom return. The furnace will accommodate the following filter sizes depending on cabinet size:

SIDE RETURN

 

Cabinet

Nominal

Approx.

 

 

Width

Filter Size

Flow Area

 

 

(in.)

(in.)

(in2)

 

 

 

 

 

 

 

All

16 x 25 x 1

400

 

 

 

 

 

 

BOTTOM RETURN (1)

Cabinet

Nominal

Approx.

Width

Filter Size

Flow Area

(in.)

(in.)

(in2)

 

 

 

17-1/2

14 x 25 x 1

350

21

16 x 25 x 1

400

24-1/2

20 x 25 x 1

500

(1) Flanges on bottom return must be unfolded

Refer to Minimum Filter Area tables to determine filter area requirement. NOTE: Filters can also be installed elsewhere in the duct system such as a central return.

Input__Airflow

 

COOLING AIRFLOW REQUIREMENT (CFM)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

600

800

1000

1200

1400

1600

2000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0453BXA*

388*

388*

480

576

---

---

---

 

 

 

 

 

 

 

 

0703BXA*

---

647*

647*

647*

672

---

---

 

 

 

 

 

 

 

 

0704CXA*

---

---

583*

583*

672

768

---

 

 

 

 

 

 

 

 

0904CXA*

---

---

863*

863*

863*

863*

---

 

 

 

 

 

 

 

 

0905DXA*

---

---

---

777*

777*

777*

960

 

 

 

 

 

 

 

 

1155DXA*

---

---

---

971*

971*

971*

971*

 

 

 

 

 

 

 

 

Input__Airflow

 

COOLING AIRFLOW REQUIREMENT (CFM)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

600

800

1000

1200

1400

1600

2000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0453BXA*

194*

194*

240

288

---

---

---

 

 

 

 

 

 

 

 

0703BXA*

---

324*

324*

324*

336

---

---

 

 

 

 

 

 

 

 

0704CXA*

---

---

291*

291*

336

384

---

 

 

 

 

 

 

 

 

0904CXA*

---

---

432*

432*

432*

432*

---

 

 

 

 

 

 

 

 

0905DXA*

---

---

---

388*

388*

388*

480

 

 

 

 

 

 

 

 

1155DXA*

---

---

---

486*

486*

486*

486*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Minimum filter area dictated by heating airflow requirement.

*Minimum filter area dictated by heating airflow requirement.

Disposable Minimum Filter Area (in2)

Permanent Minimum Filter Area (in2)

[Based on a 300 ft/min filter face velocity]

[Based on 600 ft/min filter face velocity]

10

Image 10
Contents GMH95 40 95% Gas Furnace TECHNICAL MANUALPRODUCT IDENTIFICATION 0453 A X A AHIGH VOLTAGE GMH950453BXA GMH950703BXA GMH950704CXA PRODUCT IDENTIFICATIONGMH950904CXA GMH950905DXA GMH951155DXA General Operation PRODUCT DESIGNAccessibility Clearances Minimum Location ConsiderationsCOMPONENT IDENTIFICATION Upflow/HorizontalCOMPONENT IDENTIFICATION GMH95*****XACabinet Size PRODUCT DESIGN T.O.D. PRIMARY LIMITAUXILIARY LIMIT SWITCHES PRODUCT DESIGNPRODUCT DESIGN Coil Matches1824 EXPANSIONPRODUCT DESIGN ThermostatsFilters Disposable Minimum Filter Area in2FURNACE SPECIFICATIONS GMH95BLOWER PERFORMANCE SPECIFICATIONS BLOWER PERFORMANCEPERFORMANCE SPECIFICATIONS BLOWERGMH950703,0904,1155*XAC WIRING DIAGRAMSGMH950453,0704,0905*XAB 0140F00592 REV. AWIRING DIAGRAMS GMH950453,0704,0905*XACGMH950703,0904,1155*XAD INSTALLING THIS FAILURE TO INJURY OR DEATH