TROUBLESHOOTING GUIDE
1.Check to make sure 120VAC power is available at the electrical outlet.
2.Do not wire the unit into the appliance fan circuit. This will cause premature ballast or lamp failure and void the warranty. For proper operation, the unit requires 120VAC at all times.
3.Pull back metal washer on mounting base. If lamp comes on, the base needs tightening to ensure that the safety switch is fully engaged.
4.If lamp does not light up, rotate ballast slightly clockwise or counterclockwise.
5.If lamp does not light up after rotating ballast, replace lamp.
6.If unit still does not light up after replacing lamp, replace unit.
REPLACEMENT PARTS LIST
LAMP Replacement Part Number
46511200
For replacement parts, contact Field Controls at:
Phone: | Fax: |
Email: sales@fieldcontrols.com
UV lamps contain a small amount of mercury, like a typical fluorescent lamp. DO NOT touch any of the mercury with your bare hands.
1.While wearing disposable,
2.Then, vacuum the entire area with a standard household vacuum cleaner ensuring the removal of all lamp material.
3.Dispose of the pieces of glass, the vacuum cleaner bag, and the disposable gloves in a sealed garbage bag.
4.Check with your local waste management authority for local disposal or recycling requirements. According to the EPA's Universal Waste Rule, these types of lamps may be disposed of into household waste.
5.Wash hands and remove and wash clothes for added safety measures.
WARNING: Never expose eyes or skin to UVC light from any source. Looking directly at the UVC light may cause permanent eye damage or blindness. Never operate the
page 7