PRODUCT DESIGN
Thermostats:
NOTE: Complete lineup of thermostats can be found in the Thermostat Specification Sheets.
Filters:
Filters are required with this furnace and must be provided by the installer. The filters used must comply with UL900 or CAN/ULCS111 standards. Installing this furnace without filters will void the unit warranty.
Upflow Filters
This furnace has provisions for the installation of return air filters at the side and/or bottom return. The furnace will accommodate the following filter sizes depending on cabinet size:
SIDE RETURN
| Cabinet | Nominal | Approx. |
|
| Width | Filter Size | Flow Area |
|
| (in.) | (in.) | (in2) |
|
|
|
|
|
|
| All | 16 x 25 x 1 | 400 |
|
|
|
|
|
|
BOTTOM RETURN
Cabinet | Nominal | Approx. |
Width | Filter Size | Flow Area |
(in.) | (in.) | (in2) |
|
|
|
14 x 25 x 1 | 350 | |
21 | 16 x 25 x 1 | 400 |
20 x 25 x 1 | 500 | |
|
|
|
Refer to Minimum Filter Area tables to determine filter area requirement. NOTE: Filters can also be installed elsewhere in the duct system such as a central return.
|
| COOLING AIRFLOW REQUIREMENT (CFM) | |||||||
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| |
|
| 600 | 800 | 1000 | 1200 | 1400 | 1600 | 2000 | |
|
|
|
|
|
|
|
|
| |
| 0453_X* | 376* | 384 | 480 | 576 | ||||
|
|
|
|
|
|
|
|
| |
Airflow | 0703_X* | 564* | 564* | 564* | 672 | ||||
|
|
|
|
|
|
|
| ||
0704_X* | 564* | 564* | 672 | 768 | |||||
| |||||||||
|
|
|
|
|
|
|
|
| |
Input | 0904_X* | 752* | 752* | 752* | 768 | ||||
|
|
|
|
|
|
|
| ||
0905_X* | 752* | 752* | 768 | 800 | |||||
| |||||||||
|
|
|
|
|
|
|
|
| |
| 1155_X* | 940* | 940* | 940* | 800 | ||||
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
*Minimum filter area dictated by heating airflow requirement.
|
|
|
|
|
|
|
|
| |
|
| COOLING AIRFLOW REQUIREMENT (CFM) | |||||||
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| |
|
| 600 | 800 | 1000 | 1200 | 1400 | 1600 | 2000 | |
|
|
|
|
|
|
|
|
| |
| 0453_X* | 188* | 192 | 240 | 288 | ||||
|
|
|
|
|
|
|
|
| |
Airflow | 0703_X* | 282* | 282* | 282* | 336 | ||||
|
|
|
|
|
|
|
| ||
0704_X* | 260* | 260* | 336 | 384 | |||||
| |||||||||
|
|
|
|
|
|
|
|
| |
Input | 0904_X* | 376* | 376* | 376* | 384 | ||||
|
|
|
|
|
|
|
| ||
0905_X* | 376* | 376* | 384 | 480 | |||||
| |||||||||
|
|
|
|
|
|
|
|
| |
| 115_X* | 470* | 470* | 470* | 480 | ||||
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
*Minimum filter area dictated by heating airflow requirement.
Disposable Minimum Filter Area (in2) | Permanent Minimum Filter Area (in2) |
[Based on a 300 ft/min filter face velocity] | [Based on 600 ft/min filter face velocity] |
10