Langley/Empire DV-20E-5, DV-40E-5 Installing Wall Bracket Figures 5, Venting Figures 7, 8

Page 10

Installing Wall Bracket (Figures 5 and 6)

After finding a location for the furnace, gas supply and vent, the wall bracket must be positioned and installed. The bracket should be mounted to the wall studs, if possible, or anchored solidly to the wall. Use the (2) 10 x 1" (25mm) hex-head screws or (2) plastic anchors provided. Drill (2) 5/16" (8mm) diameter holes in wall if plastic anchors are used. Attach the two wall mounting brackets to the casing back by using (4) 10 x 1/2" (13mm) hex-head screws provided.

 

Figure 5

 

CASING

4" (102mm)

WALL

WALL MOUNTING BRACKET

BACK

 

 

#10 X 1"

 

#10 X 1/2"

WALL

BRACKET

#10 X 1/2"

Figure 6

EXHAUST AIR

ORANGE SILICONE

ELBOW CONNECTOR

 

INTAKE AIR

 

BLACK FLEXIBLE HOSE

 

Figure 8

VENT TUBING

SILICONE COUPLING

 

 

HOSE CLAMP

EDGE

HOSE CLAMP

EXHAUST CONNECTIONS

INTAKE FLEX HOSE CONNECTION

WITH INTERNAL METAL COUPLING

VENT COUPLING CONNECTIONS

EXTENDED VENT

Figure 9

Venting (Figures 7, 8 and 9)

This unit is vented directly out the back using the concentric vent tube assembly provided. See Figure 2 for vent hole location. This hole location can be conveniently moved closer to unit exhaust outlet tube to avoid wall stud interference if necessary. The orange silicone exhaust elbow would need to be cut to length. Do not

KEEP CAP ON

UN-USED AIR

INTAKE OPENING

EXHAUST ELBOW MAY BE CUT TO LENGTH TO FIT VENT BOX. SECURE IN PLACE USING HOSE CLAMPS PROVIDED.

WALL

MOUNTING PLATE

INTAKE AIR

EXHAUST

INTAKEFLEX HOSE WITH CLAMPS

locate vent directly behind the exhaust outlet. Do not use the orange silicone elbow for extended vent runs where the possibility of flue condensate exists unless the run is horizontal and the elbow is sloped downward away from the heater. See Figure 12 for extended vertical venting.

The vent provided will accommodate walls up to 10" thick and can be cut shorter for thinner walls if desired by using a hacksaw or cut-off saw. Be sure to leave the minimum 3/4" of tube length extending beyond the outside wall plate. Both the inner and outer tube will be cut to the same length as the inner exhaust tube has an extension piece which is added during final outside assembly.

Figure 7

Page 10

19562-1-0606

Image 10
Contents Installation Instructions What to do if YOU Smell GASTable of Contents Important Safety Information Do not Operate this Appliance Without Front Panel InstalledLP-GAS Warning Odor Safety Informtion for Users of LP-GASNo Odor Detected Odor Fade Requirements for Massachusetts Clear of ALL ObstructionsSpecifications IntroductionRecommended Gas Pipe Diameter Pressure Testing of the Gas Supply SystemGAS Supply Checking Manifold PressureConversion Instructions from LP Propane GAS to Natural GAS GAS Conversion InstructionsConversion Instructions from Natural GAS to LP Propane GAS Clearances Furnace InstallationInstallation on Rugs and Tile Locating Wall Opening Figures 2, 3Installing Wall Bracket Figures 5 Venting Figures 7, 8Furnace Installation Vent Terminal FigureReassembly and Resealing Vent-Air Intake System Condensate Removal Figures 11For Your Safety Read Before Operating Lighting InstructionsReplacement of Thermistor with 24 Volt Wall Thermostat WiringInternal Electronic Thermostat/Temperature Control Board Maintenance Operation and TroubleshootingFurnace Control Board Diagnostics # of Blinks Fault Condition Fault CorrectionHOW to Order Repair Parts Parts ListParts View Service Notes