Goodman Mfg AMV8 instruction manual XIII. Operational Checks, XIII. Safety Circuit Description

Page 26

XIII. OPERATIONAL CHECKS

WARNING

TO AVOID PERSONAL INJURY OR DEATH, DO NOT REMOVE ANY INTERNAL COMPARTMENT COVERS OR ATTEMPT ANY ADJUSTMENT. ELECTRICAL COMPONENTS ARE CONTAINED IN BOTH COMPARTMENTS. TO PREVENT PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO EXPLOSION AND/OR FIRE, CONTACT A QUALIFIED SERVICE AGENT AT ONCE IF AN ABNORMAL FLAME APPEARS.

BURNER FLAME

The burner flames should be inspected with the burner compartment door installed. Flames should be stable, quiet, soft, and blue (dust may cause orange tips but they must not be yellow). Flames should extend directly outward from the burners without curling, floating, or lifting off. Flames must not impinge on the sides of the heat exchanger firing tubes.

Check the burner flames for:

1.Good adjustment

2.Stable, soft and blue

3. Not curling, floating, or lifting off.

Burner Flame

AUXILIARY LIMIT CONTROL

A uto reset limits are located on or near the blower. To access this auxiliary limit, disconnect the electrical power and remove the blower door. If the limit control opens, the air circulation blower will run continuously. The diagnostic light will flash one time. The auxiliary limit control is designed to prevent furnace operation in case of main blower failure on horizontal and counterflow installations. It may also open if the power supply is interrupted while the furnace is firing. The auxiliary limit control is suitable for both horizontal right and horizontal left installations. Regardless of airflow direction, it does not need to be relocated.

PRIMARY LIMIT

The primary limit control guards against overheating resulting from insufficient conditioned air passing over the heat exchanger. If the primary limit control does not function during this test, the cause must be determined and corrected. Function of this control should be verified by gradually blocking the furnace return air after the furnace has been operating (burners firing) for approximately ten minutes. Check the control as follows:

1.Allow the furnace to operate with burners firing continuously for approximately ten minutes.

2.Gradually block the return air to furnace. Remove airflow blockage when limit control is activated and turns off burners. Airflow blockage causes unit overheating and will produce the following reactions:

The gas valve to close and extinguish flame,

The induced draft blower to be de-energized after a fifteen second postpurge, and

The circulator blower to remain energized continuously until limit control resets.

3.Remove the return air blockage to clear overheating condition. After an acceptable temperature is reached during the cool down period, the limit control will reset and allow the furnace to resume normal operation.

WARNING

TO PREVENT PREMATURE FAILURE OF HEAT EXCHANGER, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, DO NOT ADJUST THE LIMIT CONTROL (FACTORY SET).

XIII. SAFETY CIRCUIT DESCRIPTION

IMPORTANT NOTE: This unit must not be used as a construction heater during the finishing phases of construction of a new structure. This type of use may result in premature failure due to extremely low return air temperatures and exposure to corrosive or very dirty atmospheres.

These checks establish that the primoary limit control is functioning and will respond to a restriction in the return air, or a circulator blower failure. If the primary limit control does not function during this test, the cause must be determined and corrected.

GENERAL

A number of safety circuits are employed to ensure safe and proper furnace operation. These circuits serve to control any potential safety hazards and serve as inputs in the monitoring and diagnosis of abnormal function. These circuits are continuously monitored during furnace operation by the integrated control module.

INTEGRATED CONTROL MODULE

The integrated control module is an electronic device which controls all furnace operations. Responding to the thermostat, the module initiates and controls normal furnace operation, and monitors and addresses all safety circuits. If a potential safety concern is detected, the module will take the necessary precautions and provide diagnostic information through an LED.

PRIMARY LIMIT

The primary limit control is located on the partition panel and monitors heat exchanger compartment temperatures. It is an automatic reset, temperature sensor. The limit guards against the overheating as a resulting of insufficient air passing over the heat exchanger.

AUXILIARY LIMIT

The auxiliary limit control is located either on or near the circulator blower and monitors heat exchanger compartment temperatures. The control is a temperature sensor. It guards against overheating resulting from insufficient air passing over the heat exchanger.

ROLLOUT LIMITS

The rollout limit controls are mounted on the burner/manifold assembly and monitor the burner flame. They are manual-reset, temperature sensors. This limit guards against burner flames not being properly drawn into the heat exchanger.

PRESSURE SWITCHES

The pressure switches are normally-open, negative air pressure- activated switches. They monitor the airflow (combustion air and flue products) through the heat exchanger via pressure taps located on the induced draft blower. These switches guard against insufficient airflow (combustion air and flue products) through the heat exchanger.

FLAME SENSOR

The flame sensor is a probe mounted to the burner/manifold assembly which uses the principle of flame rectification to determine the presence or absence of flame.

IO-247A

26

12/04

Image 26
Contents Installation & Operating Table of Contents XV. Troubleshooting XII. Start-up Procedure and AdjustmentXIV. Safety Circuit Description XVI. MaintenanceHomeowner Notice II. SafetyTo the Installer To the OwnerIII. Product Application Additional Safety ConsiderationsElectrostatic Discharge ESD Precautions American National Standards InstituteCSA International IV. Location Requirements and ConsiderationsNational Fire Protection Association National Fire Protection Association, IncThermostat Location Thermostat InfluencesFurnace Suspension Existing Furnace RemovalEquipment Located in Unconfined Spaces Combustion and Ventilation AIR RequirementsZ223.1 Section General Space, UnconfinedSpecially Engineered Installations Minimum Vent VI. Category I Venting Vertical VentingLouvers and Grilles Check 1 Proper Chimney Termination Checklist SummaryVII. Exterior Masonry Chimneys Category I Furnaces only Check 5 Liner Condition Check 4 Debris in CleanoutCheck 3 Chimney Crown Condition FIX 1 Liner Termination Check 7 Complete the InstallationCheck 6 Dilution AIR FIX 2 -CHANGE Venting ArrangementsVolt Line Connections Wiring HarnessVIII. Electrical Connections Junction BOX RelocationVolt Thermostat Wiring Single Stage Thermostat ApplicationSINGLE-STAGE Thermostat Application Setting the Heat AnticipatorVolt Dehumidistat Wiring Fossil Fuel ApplicationsAltitude NAT. GAS Orifice Size IX. GAS Supply and PipingHigh Altitude Derate GAS AT 0 2,000 Feet Altitude Meter Time in Minutes and Seconds for Normal InputRating of Furnaces Equipped for USE with Natural GAS Piping ConnectionsPropane GAS Tanks and Piping Upflow InstallationsGAS Piping Checks Ductwork AIR Propane GAS Piping ChartsCirculating AIR and Filters XI. Sequence of Operation Integrated Ignition Control XII. START-UP Procedure and Adjustment White-Rodgers Model 36E54 Connected to ManometerGAS Manifold Pressure Measurement and Adjustment GAS Input Rate Measurement Natural GAS onlyTemperature Rise Circulator Blower Speed AdjustmentAdjust Blower Heat OFF Delay Circulator Blower FAN Timing AdjustmentXIII. Safety Circuit Description XIII. Operational ChecksXV. Troubleshooting XVI. MaintenanceXVII. Before Leaving AN Installation XVIII. Repair and Replacement PartsTroubleshooting Chart Continuously Wiring Diagram Are Subject to Change Without Notice

AMV8 specifications

Goodman Manufacturing has long been recognized as a key player in the HVAC industry, and the Goodman AMV8 stands out as a remarkable addition to their lineup of high-efficiency air conditioning units. Designed with the latest technological advancements, the AMV8 focuses on providing enhanced performance, energy efficiency, and reliability, making it a popular choice among homeowners and contractors alike.

One of the primary features of the Goodman AMV8 is its high SEER (Seasonal Energy Efficiency Ratio) rating, which typically reaches up to 16 SEER. This impressive rating signifies that the unit is capable of delivering substantial energy savings compared to older models. By using less electricity to cool your home, the AMV8 not only impacts utility bills positively but also contributes to reducing your carbon footprint.

The Goodman AMV8 is built with a powerful and efficient scroll compressor, known for its ability to operate quietly while maintaining a smooth and reliable performance. The advanced design minimizes vibration, ensuring a quieter operation, which is particularly appealing for residential settings. Additionally, the unit features a multi-speed ECM blower motor that enhances airflow consistency and operational efficiency.

Construction quality is also noteworthy with the Goodman AMV8. The cabinet is made of durable galvanized steel, coated with a corrosion-resistant finish that protects against rust and weather-related wear and tear. This durability extends the lifespan of the unit and provides assurance of quality to consumers.

Another characteristic that elevates the AMV8 is its integrated comfort control system. This feature allows users to easily manage cooling settings, ensuring optimal comfort throughout the home. The intelligent design of the unit includes a communicator control board, which optimizes system performance and simplifies installation.

The Goodman AMV8 also incorporates environmentally conscious technologies, including the use of R-410A refrigerant. This refrigerant is known for its efficiency and lack of ozone depletion potential, aligning with standards for environmentally friendly HVAC options.

In summary, the Goodman AMV8 is a high-efficiency air conditioning unit that showcases impressive features such as a high SEER rating, a reliable scroll compressor, a durable exterior, and advanced comfort control capabilities. Its commitment to energy efficiency and environmental consideration make it an exemplary choice for those seeking a dependable and cost-effective cooling solution for their homes. Whether for new installations or replacements, the AMV8 stands as a testament to Goodman Manufacturing's dedication to quality and innovation in HVAC technology.