Termination 10 Feet Or Less From Ridge, Wall or Parapet

Termination More Than 10 Feet From Ridge, Wall or Parapet

CHECK 2 - ANY SOLID OR LIQUID FUEL APPLIANCES VENTED INTO THIS CHIMNEY CHANNEL

Solid fuel appliances include fireplaces, wood stoves, coal furnaces, and incinerators.

Liquid fuel appliances include oil furnaces, oil-fired boilers and oil- fired water heaters.

Appliances which burn propane (sometimes referred to as LP (liquefied petroleum)) gas are considered gas-fired appliances.

CHECK 3 - CHIMNEY CROWN CONDITION.

Damage from condensate usually shows up first in the crown. If any of the following trouble signs are present, the condition of the crown is not satisfactory:

a)Crown leaning

b)Bricks missing

c)Mortar missing

d)Tile liner cracked

e)No tile liner

f)Salt staining at mortar joints. (White stains, and mortar becomes sandy and/or erodes.)

For problems a, b, or c, see Fix 3. If problems d, e, or f are present, see Fix 4. IMPORTANT: It may be necessary to follow both Fix 3 and Fix 4.

CHECK 4 - DEBRIS IN CLEANOUT

A cleanout (dropleg) must be present such that the upper edge of the cleanout cover is at least 12 inches below the lower edge of the lowest chimney inlet opening.

A chimney without a cleanout could become partially blocked by debris. If no cleanout is present, the chimney must be refined (Fix 4). Remove the cleanout cover, and examine the cleanout for debris. If significant amounts of any of the following are found:

Fuel oil residue

Bricks

Mortar or sand

Pieces of the tile liner

Rusted pieces of the metallic liner - reline the chimney (Fix 4).

CHECK 5 - LINER CONDITION.

If a metal liner is present, it must be checked. It cannot be assumed that all existing metal liners are correctly installed and in good condition.

Remove the lowest existing vent connector, and examine the inside of the elbow or tee at the base of the liner. A small amount of soot may be considered acceptable, provided the installer vacuums it away. If rusted pieces of the liner have collected here, the metal liner must be removed and replaced (Fix 4).

Next, gently tap the inside of the liner with a Phillips screwdriver. If the screwdriver perforates the liner, or if the tapping does not sound like metal hitting metal, the liner must be removed and replaced (Fix 4).

Remember that all appliances must be vented inside the liner. Venting one appliance inside the liner and another appliance outside the liner is not acceptable.

Next, use a flashlight and small mirror to sight up the liner. B vent must be supported so as to not come into direct contact with the chimney walls or tile liner. If it is not, it can probably be rehung so as to be acceptable. A thimble or fire stop may be helpful here.

Flexible liners should be hung straight or nearly straight. If it is spiraled in the chimney and in good condition, it should be rehung. To do this, break the top seal; pull up and cut off the excess liner length, and refit the top seal. Use caution when doing this, as the cut edges of flexible liners may be sharp.

The surfaces of the liner must be physically sound. If gaps or holes are present, the metal liner must be removed and replaced (Fix 4). Finally, confirm that the metal liner is the correct size for the appliances to be installed. Use the GAMA tables and rules.

IO-247A

12

12/04

Image 12
Contents Installation & Operating Table of Contents XII. Start-up Procedure and Adjustment XIV. Safety Circuit DescriptionXV. Troubleshooting XVI. MaintenanceII. Safety To the InstallerHomeowner Notice To the OwnerAdditional Safety Considerations Electrostatic Discharge ESD PrecautionsIII. Product Application American National Standards InstituteIV. Location Requirements and Considerations National Fire Protection AssociationCSA International National Fire Protection Association, IncThermostat Influences Furnace SuspensionThermostat Location Existing Furnace RemovalCombustion and Ventilation AIR Requirements Z223.1 Section GeneralEquipment Located in Unconfined Spaces Space, UnconfinedSpecially Engineered Installations VI. Category I Venting Vertical Venting Louvers and GrillesMinimum Vent Checklist Summary VII. Exterior Masonry Chimneys Category I Furnaces onlyCheck 1 Proper Chimney Termination Check 4 Debris in Cleanout Check 3 Chimney Crown ConditionCheck 5 Liner Condition Check 7 Complete the Installation Check 6 Dilution AIRFIX 1 Liner Termination FIX 2 -CHANGE Venting ArrangementsWiring Harness VIII. Electrical ConnectionsVolt Line Connections Junction BOX RelocationVolt Thermostat Wiring Single Stage Thermostat ApplicationSetting the Heat Anticipator Volt Dehumidistat WiringSINGLE-STAGE Thermostat Application Fossil Fuel ApplicationsIX. GAS Supply and Piping High Altitude DerateAltitude NAT. GAS Orifice Size Meter Time in Minutes and Seconds for Normal Input Rating of Furnaces Equipped for USE with NaturalGAS AT 0 2,000 Feet Altitude GAS Piping ConnectionsUpflow Installations GAS Piping ChecksPropane GAS Tanks and Piping Propane GAS Piping Charts Circulating AIR and FiltersDuctwork AIR XI. Sequence of Operation Integrated Ignition Control XII. START-UP Procedure and Adjustment White-Rodgers Model 36E54 Connected to ManometerGAS Manifold Pressure Measurement and Adjustment GAS Input Rate Measurement Natural GAS onlyTemperature Rise Circulator Blower Speed AdjustmentAdjust Blower Heat OFF Delay Circulator Blower FAN Timing AdjustmentXIII. Safety Circuit Description XIII. Operational ChecksXV. Troubleshooting XVI. MaintenanceXVII. Before Leaving AN Installation XVIII. Repair and Replacement PartsTroubleshooting Chart Continuously Wiring Diagram Are Subject to Change Without Notice

AMV8 specifications

Goodman Manufacturing has long been recognized as a key player in the HVAC industry, and the Goodman AMV8 stands out as a remarkable addition to their lineup of high-efficiency air conditioning units. Designed with the latest technological advancements, the AMV8 focuses on providing enhanced performance, energy efficiency, and reliability, making it a popular choice among homeowners and contractors alike.

One of the primary features of the Goodman AMV8 is its high SEER (Seasonal Energy Efficiency Ratio) rating, which typically reaches up to 16 SEER. This impressive rating signifies that the unit is capable of delivering substantial energy savings compared to older models. By using less electricity to cool your home, the AMV8 not only impacts utility bills positively but also contributes to reducing your carbon footprint.

The Goodman AMV8 is built with a powerful and efficient scroll compressor, known for its ability to operate quietly while maintaining a smooth and reliable performance. The advanced design minimizes vibration, ensuring a quieter operation, which is particularly appealing for residential settings. Additionally, the unit features a multi-speed ECM blower motor that enhances airflow consistency and operational efficiency.

Construction quality is also noteworthy with the Goodman AMV8. The cabinet is made of durable galvanized steel, coated with a corrosion-resistant finish that protects against rust and weather-related wear and tear. This durability extends the lifespan of the unit and provides assurance of quality to consumers.

Another characteristic that elevates the AMV8 is its integrated comfort control system. This feature allows users to easily manage cooling settings, ensuring optimal comfort throughout the home. The intelligent design of the unit includes a communicator control board, which optimizes system performance and simplifies installation.

The Goodman AMV8 also incorporates environmentally conscious technologies, including the use of R-410A refrigerant. This refrigerant is known for its efficiency and lack of ozone depletion potential, aligning with standards for environmentally friendly HVAC options.

In summary, the Goodman AMV8 is a high-efficiency air conditioning unit that showcases impressive features such as a high SEER rating, a reliable scroll compressor, a durable exterior, and advanced comfort control capabilities. Its commitment to energy efficiency and environmental consideration make it an exemplary choice for those seeking a dependable and cost-effective cooling solution for their homes. Whether for new installations or replacements, the AMV8 stands as a testament to Goodman Manufacturing's dedication to quality and innovation in HVAC technology.