Goodman Mfg AMV8 Upflow Installations, GAS Piping Checks, Propane GAS Tanks and Piping

Page 19

Install a drip leg to trap dirt and moisture before it can enter the gas valve. The drip leg must be a minimum of three inches long.

Install a 1/8" NPT pipe plug fitting, accessible for test gage connection, immediately upstream of the gas supply connection to the furnace.

Use two pipe wrenches when making connection to the gas valve to keep it from turning. The orientation of the gas valve on the manifold must be maintained as shipped from the factory.

Install a manual shutoff valve between the gas meter and unit within six feet of the unit. If a union is installed, the union must be downstream of the manual shutoff valve, between the shutoff valve and the furnace.

Tighten all joints securely.

Connect the furnace to the building piping by one of the following methods:

Rigid metallic pipe and fittings.

Semi-rigid metallic tubing and metallic fittings.

Aluminum alloy tubing must not be used in exterior locations.

Use listed gas appliance connectors in accordance with

their instructions. Connectors must be fully in the same room as the furnace.

Protect connectors and semi-rigid tubing against

physical and thermal damage when installed. Ensure aluminum-alloy tubing and connectors are coated to protect against external corrosion when in contact with masonry, plaster, or insulation, or subjected to repeated wetting by liquids such as water (except rain water), detergents, or sewage.

Location of Manual Valve

(Installed Ahead of Ground

Joint Pipe Union)

Height Required

By Local Code

Ground Joint Pipe Union

To Be Installed Ahead Of

Gas Valve

Drip Leg

 

 

 

 

 

 

 

 

``

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Reducing Coupling 1/2" x 1/8" with 1/8" Pipe Plug To Measure Line Gas Pressure

General Furnace Layout

UPFLOW INSTALLATIONS

When the gas piping enters through the right side of the furnace, the installer must supply the following fittings (starting from the gas valve):

90 degree elbows (2).

Close nipple.

Straight pipe to reach the exterior of the furnace .

A ground joint union, drip leg, and manual shutoff valve must also be supplied by the installer. In some cases, the installer may also

need to supply a transition piece from 1/2" to another pipe size.

When the gas piping enters through the left side of the furnace, the installer must supply the following fittings (starting from the gas valve):

Straight pipe to reach the exterior of the furnace.

A ground joint union, drip leg, and manual shutoff valve must also be supplied by the installer. In some cases, the installer may also need to supply a transition piece from 1/2 inch to another pipe size.

GAS PIPING CHECKS

Before placing unit in operation, leak test the unit and gas connections.

WARNING

TO AVOID THE POSSIBILITY OF EXPLOSION OR FIRE, NEVER USE A MATCH OR OPEN FLAME TO TEST FOR LEAKS.

Check for leaks using an approved chloride-free soap and water solution, an electronic combustible gas detector, or other approved testing methods.

CAUTION

TO PREVENT PROPERTY DAMAGE OR PERSONAL INJURY DUE TO FIRE, THE FOLLOWING INSTRUCTIONS MUST BE PERFORMED REGARDING GAS CONNECTIONS, PRESSURE TESTING, LOCATION OF SHUTOFF VALVE AND INSTALLATION OF GAS PIPING.

NOTE: Never exceed specified pressures for testing. Higher pressure may damage the gas valve and cause subsequent overfiring, resulting in heat exchanger failure.

Disconnect this unit and shutoff valve from the gas supply piping system before pressure testing the supply piping system with pressures in excess of 1/2 psig (3.48 kPa).

This unit must be isolated from the gas supply system by closing its manual shutoff valve before pressure testing of gas supply piping system with test pressures equal to or less than 1/2 psig (3.48 kPa).

PROPANE GAS TANKS AND PIPING

WARNING

IF THE GAS FURNACE IS INSTALLED IN A BASEMENT, AN EXCAVATED AREA OR A CONFINED SPACE, IT IS STRONGLY RECOMMENDED TO CONTACT A PROPANE SUPPLIER TO INSTALL A GAS DETECTING WARNING DEVICE IN CASE OF A GAS LEAK.

SINCE PROPANE GAS IS HEAVIER THAN AIR, ANY LEAKING GAS CAN SETTLE IN ANY LOW AREAS OR CONFINED SPACES.

PROPANE GAS ODORANT MAY FADE, MAKING THE GAS UNDETECTABLE EXCEPT WITH A WARNING DEVICE.

A gas detecting warning system is the only reliable way to detect a propane gas leak. Rust can reduce the level of odorant in propane gas. Do not rely on your sense of smell. Contact a local propane gas supplier about installing a gas detecting warning system. If the presence of gas is suspected, follow the instructions on Page 4 of this manual.

All propane gas equipment must conform to the safety standards of the National Board of Fire Underwriters, NBFU Manual 58.

IO-247A

19

12/04

 

 

Image 19
Contents Installation & Operating Table of Contents XVI. Maintenance XII. Start-up Procedure and AdjustmentXIV. Safety Circuit Description XV. TroubleshootingTo the Owner II. SafetyTo the Installer Homeowner NoticeAmerican National Standards Institute Additional Safety ConsiderationsElectrostatic Discharge ESD Precautions III. Product ApplicationNational Fire Protection Association, Inc IV. Location Requirements and ConsiderationsNational Fire Protection Association CSA InternationalExisting Furnace Removal Thermostat InfluencesFurnace Suspension Thermostat LocationSpace, Unconfined Combustion and Ventilation AIR RequirementsZ223.1 Section General Equipment Located in Unconfined SpacesSpecially Engineered Installations Louvers and Grilles VI. Category I Venting Vertical VentingMinimum Vent VII. Exterior Masonry Chimneys Category I Furnaces only Checklist SummaryCheck 1 Proper Chimney Termination Check 3 Chimney Crown Condition Check 4 Debris in CleanoutCheck 5 Liner Condition FIX 2 -CHANGE Venting Arrangements Check 7 Complete the InstallationCheck 6 Dilution AIR FIX 1 Liner TerminationJunction BOX Relocation Wiring HarnessVIII. Electrical Connections Volt Line ConnectionsSingle Stage Thermostat Application Volt Thermostat WiringFossil Fuel Applications Setting the Heat AnticipatorVolt Dehumidistat Wiring SINGLE-STAGE Thermostat ApplicationHigh Altitude Derate IX. GAS Supply and PipingAltitude NAT. GAS Orifice Size GAS Piping Connections Meter Time in Minutes and Seconds for Normal InputRating of Furnaces Equipped for USE with Natural GAS AT 0 2,000 Feet AltitudeGAS Piping Checks Upflow InstallationsPropane GAS Tanks and Piping Circulating AIR and Filters Propane GAS Piping ChartsDuctwork AIR XI. Sequence of Operation Integrated Ignition Control White-Rodgers Model 36E54 Connected to Manometer XII. START-UP Procedure and AdjustmentGAS Input Rate Measurement Natural GAS only GAS Manifold Pressure Measurement and AdjustmentCirculator Blower Speed Adjustment Temperature RiseCirculator Blower FAN Timing Adjustment Adjust Blower Heat OFF DelayXIII. Operational Checks XIII. Safety Circuit DescriptionXVI. Maintenance XV. TroubleshootingXVIII. Repair and Replacement Parts XVII. Before Leaving AN InstallationTroubleshooting Chart Continuously Wiring Diagram Are Subject to Change Without Notice

AMV8 specifications

Goodman Manufacturing has long been recognized as a key player in the HVAC industry, and the Goodman AMV8 stands out as a remarkable addition to their lineup of high-efficiency air conditioning units. Designed with the latest technological advancements, the AMV8 focuses on providing enhanced performance, energy efficiency, and reliability, making it a popular choice among homeowners and contractors alike.

One of the primary features of the Goodman AMV8 is its high SEER (Seasonal Energy Efficiency Ratio) rating, which typically reaches up to 16 SEER. This impressive rating signifies that the unit is capable of delivering substantial energy savings compared to older models. By using less electricity to cool your home, the AMV8 not only impacts utility bills positively but also contributes to reducing your carbon footprint.

The Goodman AMV8 is built with a powerful and efficient scroll compressor, known for its ability to operate quietly while maintaining a smooth and reliable performance. The advanced design minimizes vibration, ensuring a quieter operation, which is particularly appealing for residential settings. Additionally, the unit features a multi-speed ECM blower motor that enhances airflow consistency and operational efficiency.

Construction quality is also noteworthy with the Goodman AMV8. The cabinet is made of durable galvanized steel, coated with a corrosion-resistant finish that protects against rust and weather-related wear and tear. This durability extends the lifespan of the unit and provides assurance of quality to consumers.

Another characteristic that elevates the AMV8 is its integrated comfort control system. This feature allows users to easily manage cooling settings, ensuring optimal comfort throughout the home. The intelligent design of the unit includes a communicator control board, which optimizes system performance and simplifies installation.

The Goodman AMV8 also incorporates environmentally conscious technologies, including the use of R-410A refrigerant. This refrigerant is known for its efficiency and lack of ozone depletion potential, aligning with standards for environmentally friendly HVAC options.

In summary, the Goodman AMV8 is a high-efficiency air conditioning unit that showcases impressive features such as a high SEER rating, a reliable scroll compressor, a durable exterior, and advanced comfort control capabilities. Its commitment to energy efficiency and environmental consideration make it an exemplary choice for those seeking a dependable and cost-effective cooling solution for their homes. Whether for new installations or replacements, the AMV8 stands as a testament to Goodman Manufacturing's dedication to quality and innovation in HVAC technology.