Johnson Controls LM8M/LMLM*MP Specific Safety Rules and Precautions, Safety Requirements

Page 2

368261-UIM-A-0508

SPECIFIC SAFETY RULES AND PRECAUTIONS

1.Only Natural gas or Propane (LP) gas are approved for use with this furnace.

2.Install this furnace only in a location and position as specified in these instructions.

3.A gas-fired furnace for installation in a residential garage must be installed as specified in these instructions.

4.Provide adequate combustion and ventilation air to the furnace space as specified in these instructions.

5.Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specified in SEC- TION VII of these instructions.

6.Test for gas leaks as specified in these instructions.

FIRE OR EXPLOSION HAZARD

Failure to follow the safety warnings exactly could result in serious injury, death or property damage.

Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for detection of leaks to check all connections. A fire or explosion may result causing prop- erty damage, personal injury or loss of life.

7.Always install the furnace to operate within the furnace’s intended temperature rise range. Only connect the furnace to a duct system which has an external static pressure within the allowable range, as specified on the furnace rating plate.

8.When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the fur- nace casing and terminating outside the space containing the fur- nace.

9.It is permitted to use the furnace for heating of buildings or struc- tures under construction where the application and use must com- ply with all manufacturer’s installation instructions including:

Proper vent installation;

Furnace operating under thermostatic control;

Return air duct sealed to the furnace;

Air filters in place;

Set furnace input rate and temperature rise per rating plate marking;

Means for providing outdoor air required for combustion;

Return air temperature maintained between 55ºF (13ºC) and 80ºF (27ºC);

The air filter must be replaced upon substantial completion of the construction process;

Clean furnace, duct work and components upon substantial completion of the construction process, and verify furnace- operating conditions including ignition, input rate, temperature rise and venting, according to the manufacturer’s instructions.

10.When installed in a Non-HUD-Approved Modular Home or building constructed on-site, combustion air shall not be supplied from occupied spaces.

11.The size of the unit should be based on an acceptable heat loss calculation for the structure. ACCA, Manual J or other approved methods may be used.

SAFETY REQUIREMENTS

This product must be installed in strict compliance with the installa- tion instructions and any applicable local, state, and national codes including, but not limited to building, electrical, and mechanical codes.

Refer to the unit rating plate for the furnace model number, and then see the dimensions page of this instruction for return air ple- num dimensions in Figure 14, "Dimensions". The plenum must be installed according to the instructions.

Provide clearances from combustible materials as listed under Clearances to Combustibles.

Provide clearances for servicing ensuring that service access is allowed for both the burners and blower.

These models ARE NOT CSA listed or approved for installation into a HUD Approved Modular Home or a Manufactured (Mobile) Home.

This furnace is not approved for installation in trailers or recre- ational vehicles.

Furnaces for installation on combustible flooring shall not be installed directly on carpeting, tile or other combustible material other than wood flooring.

Check the rating plate and power supply to be sure that the elec- trical characteristics match. All models use nominal 115 VAC, 1 Phase, 60-Hertz power supply. DO NOT CONNECT THIS APPLI-

ANCE TO A 50 HZ POWER SUPPLY OR A VOLTAGE ABOVE 130 VOLTS.

Furnace shall be installed so the electrical components are pro- tected from water.

Installing and servicing heating equipment can be hazardous due to the electrical components and the gas fired components. Only trained and qualified personnel should install, repair, or service gas heating equipment. Untrained service personnel can perform basic maintenance functions such as cleaning and replacing the air filters. When working on heating equipment, observe precau- tions in the manuals and on the labels attached to the unit and other safety precautions that may apply.

COMBUSTION AIR QUALITY (LIST OF CONTAMINANTS)

The furnace requires OUTDOOR AIR for combustion when the furnace is located in any of the following environments.

Restricted Environments

Commercial buildings

Buildings with indoor pools

Furnaces installed in laundry rooms

Furnaces installed in hobby or craft rooms

Furnaces installed near chemical storage areas

Chemical exposure

The furnace requires OUTDOOR AIR for combustion when the furnace is located in an area where the furnace is being exposed to the follow- ing substances and / or chemicals.

Permanent wave solutions

Chlorinated waxes and cleaners

Chlorine based swimming pool chemicals

Water softening chemicals

De-icing salts or chemicals

Carbon tetrachloride

Halogen type refrigerants

Cleaning solvents (such as perchloroethylene)

Printing inks, paint removers, varnishes, etc.

Hydrochloric acid

Cements and glues

Antistatic fabric softeners for clothes dryers

Masonry acid washing materials

When outdoor air is used for combustion, the combustion air intake duct system termination must be located external to the building and in an area where there will be no exposure to the substances listed above.

2

Johnson Controls Unitary Products

Image 2
Contents List of Sections Section I SafetyModels List of FiguresAnce to a 50 HZ Power Supply or a Voltage Above 130 Volts Specific Safety Rules and PrecautionsSafety Requirements Combustion AIR Quality List of ContaminantsCodes and Standards InspectionDuctwork General Information Section II DuctworkFurnace Location and Clearances Furnace Assembly MC & FC Series Coils Floor Base and Ductwork Installation DownflowCOIL/FURNACE Assembly MC/FC/PC Series Coils Coil Flange InstallationDownflow Duct Connectors Furnace Assembly PC Series CoilsCoil / Furnace Assembly HC Series Coils Critical Coil ProjectionSuspended Furnace / Crawl Space Installation Bottom Return and Attic InstallationsAttic Installation Horizontal ApplicationSection III Filters Filter InstallationAttempt to install filters inside the furnace Side ReturnSection IV GAS Piping GAS SafetyGAS Piping Installation GAS Conversion for Propane LPHigh Altitude Natural GAS Orifice Conversion Section V Electrical PowerElectrical Power Connections AIR Conditioner Connections LOW Voltage Control Wiring ConnectionsSupply Voltage Connections Zoning OperationThermostat ID ModelsModulating TWO Stage AIR Furnace Conditioner UIM-A-0508 Modulating Furnace OD Models Single Stage Heat PumpThermostat Modulating Furnace TWO Stage Heat PumpSection VI Twinning and Staging Section VII Vent SystemAir Supply Openings and Ducts Combustion Air Source From OutdoorsDampers, Louvers and Grilles Canada Only Free AreaVentilated Combustion Air Section Viii START-UP AdjustmentsVent and Supply Outside Air Safety Check Procedure NOx Screen Removal Lo-NOx Models OnlyCalculating the Furnace Input Natural GAS Setup Test ModeGAS Piping Leak Check Seconds For Revolution Cu FtAdjustment of Manifold GAS Pressure Adjustment of Temperature RiseBlower Door Safety Switch Section IX Safety ControlsAdjustment of FAN Control Settings Rollout Switch ControlsPressure Controls Section X Normal Operation and DiagnosticsFurnace Control Diagnostics Limit ControlsDiagnostic Fault Code Storage and Retrieval Section XI Replacement Parts List Fabricated PartsSection XII Wiring Diagram Johnson Controls Unitary Products York Drive Norman, OK

LM8M/LMLM*MP, TM8M/TMLM*MP, CM8M/CMLM*MP, YM8M/YMLM*MP specifications

Johnson Controls TM8M/TMLM*MP, YM8M/YMLM*MP, LM8M/LMLM*MP, and CM8M/CMLM*MP are advanced temperature controllers designed for a wide range of applications in heating, ventilation, and air conditioning (HVAC) systems. These models stand out due to their robust features, cutting-edge technologies, and specific characteristics that cater to both residential and commercial environments.

One of the main features of the TM8M/TMLM*MP series is its user-friendly interface that incorporates a large, easy-to-read display. This allows for quick adjustments and monitoring of temperature settings, making it accessible for both skilled technicians and everyday users. The intuitive design ensures that users can efficiently navigate through various settings and configurations.

Another notable characteristic is the flexibility of these controllers. The series supports multiple sensor configurations, enabling the integration of both wired and wireless sensors. This adaptability allows users to customize their climate control systems according to specific needs and room layouts, ultimately enhancing comfort and energy efficiency.

The TM8M/TMLM*MP and its counterparts are equipped with sophisticated algorithms that optimize energy consumption. By utilizing predictive maintenance and intelligent analytics, these controllers can adjust settings dynamically based on real-time data. This not only helps in reducing operational costs but also prolongs the lifespan of HVAC equipment.

Incorporating advanced communication protocols is a hallmark of the Johnson Controls series. The TM8M and CM8M models support modern systems such as BACnet and Modbus, allowing seamless integration with building management systems (BMS). This compatibility ensures that users can maintain centralized control over multiple systems, enhancing overall operational efficiency.

Additionally, the series is robustly constructed to withstand harsh environmental conditions. Its durable casing and reliable components ensure long-term performance, making it suitable for a variety of settings, including industrial facilities and commercial properties.

Safety features are also integral to the design of the TM8M/TMLM*MP and related models. Built-in safeguards protect against over-temperature and other potential hazards, ensuring reliability and peace of mind for operators.

In summary, Johnson Controls TM8M/TMLM*MP, YM8M/YMLM*MP, LM8M/LMLM*MP, and CM8M/CMLM*MP controllers represent a convergence of user-friendly design, advanced technology, flexibility, and safety. Their ability to adapt to diverse applications while optimizing energy use makes them a critical component in modern HVAC systems, ensuring comfort and efficiency in every environment.