Johnson Controls CM8M/CMLM*MP Adjustment of Manifold GAS Pressure, Adjustment of Temperature Rise

Page 23

368261-UIM-A-0508

ADJUSTMENT OF MANIFOLD GAS PRESSURE

Be sure to relight any gas appliances that were turned off at the start of this input check.

Table 11: Inlet Gas Pressure Range

INLET GAS PRESSURE RANGE

 

Natural Gas

Propane (LP)

Minimum*

4.5” W.C. (1.12 kPa)

8.0” W.C. (1.99 kPa)

Maximum

10.5” W.C. (2.61 kPa)

13.0” (3.24 kPa) W.C.

*The gas line pressure MUST BE

7” W.C. (1.74 kPA) for Natural Gas

11” W.C. (2.74 kPA) for Propane (LP) Gas

in order to obtain the BTU input specified on the rating plate and/or the nominal manifold pressure specified in these instructions and on the rating plate.

The inlet gas pressure operating range table specifies what the minimum and maximum gas line pressures must be for the furnace to operate safely.

Follow the appropriate section in the instructions below. Refer to Figure 29, "Gas Valve" for a drawing of the locations of the pressure ports on the gas valve.

Turn gas off at the ball valve or gas cock on gas supply line before the gas valve.

1.The manifold pressure must be taken at the port marked OUT PRESS TAP.

2.The inlet gas line pressure must be taken at the port marked IN PRESS TAP.

3.Using a 3/16” allen wrench, remove the plugs from the inlet and outlet pressure ports. Connect a 1/8” UPT barbed hose fitting to each pressure port.

The cap for the pressure regulator must be removed entirely to gain access to the adjustment screw. Loosening or tightening the cap does not adjust the flow of gas.

4.Refer to Figure 29, "Gas Valve" for location of pressure regulator adjustment cap and adjustment screws on main gas valve.

5.Turn gas and electrical supplies on and follow the operating instructions to place the unit back in operation.

6.Adjust manifold pressure by adjusting gas valve regulator screw for the appropriate gas per the following:

TABLE 12: Nominal Manifold Pressure

NOMINAL MANIFOLD PRESSURE

Natural Gas (Max)

3.5" w.c. (0.87 kPa)

Natural Gas (Min)

0.9" w.c. (0.22 kPa)

Propane (LP) Gas (Max)

10.0" w.c. (2.49 kPa)

Propane (LP) Gas (Min)

2.5" w.c. (0.62 kPa)

On/Off

 

Main

 

Regulator

Knob

 

 

Adjustment

 

 

 

Inlet

 

 

 

Outlet

 

 

Pressure

 

 

Pressure

Tap

 

 

Tap

 

 

 

 

 

FIGURE 29: Gas Valve

If gas valve regulator is turned in (clockwise), manifold pressure is increased. If screw is turned out (counterclockwise), manifold pres- sure will decrease.

7.After the manifold pressure has been adjusted, re-calculate the furnace input to make sure you have not exceeded the specified input on the rating plate. Refer to "CALCULATING THE FURNACE INPUT (NATURAL GAS)".

8.Once the correct BTU (kW) input has been established, turn the gas valve to OFF and turn the electrical supply switch to OFF; then remove the flexible tubing and fittings from the gas valve pressure tap and the pressure reference hose from the burner box and replace the pressure tap plugs. Replace the burner box front cover (if it was removed) and place the pressure reference hose back on the gas valve.

9.Turn the electrical and gas supplies back on, and with the burners in operation, check for gas leakage around the gas valve pressure port for leakage using an approved gas detector, a non-corrosive leak detection fluid, or other leak detection methods.

ADJUSTMENT OF TEMPERATURE RISE

The temperature rise, or temperature difference between the return air and the supply (heated) air from the furnace, must be within the range shown on the furnace rating plate and within the application limitations shown in Table 6, "Ratings & Physical / Electrical Data"

The supply air temperature cannot exceed the “Maximum Supply Air Temperature” specified in these instructions and on the fur- nace rating plate. Under NO circumstances can the furnace be allowed to operate above the Maximum Supply Air Temperature. Operating the furnace above the Maximum Supply Air Temperature will cause premature heat exchanger failure, high levels of Carbon Monoxide, a fire hazard, personal injury, property damage, and/or death.

After about 5 minutes of operation, determine the furnace temperature rise. Take temperature readings of both the return air and the heated air in the ducts about six feet away from the furnace, where they will not be affected by radiant heat. Increase or decrease the temperature rise by changing the ATR jumper on the furnace control board. The jumper is factory-set to deliver an air temperature rise near the midpoint of the nameplate temperature rise range. If more air is desired (lower temper- ature rise), move the jumper to the -10 position. If less air is desired (higher temperature rise), move the jumper to the +10 position.

Do not move the motor wires to different positions on the furnace control board!

Johnson Controls Unitary Products

23

Image 23
Contents List of Figures Section I SafetyModels List of SectionsCombustion AIR Quality List of Contaminants Specific Safety Rules and PrecautionsSafety Requirements Ance to a 50 HZ Power Supply or a Voltage Above 130 VoltsInspection Codes and StandardsDuctwork General Information Section II DuctworkFurnace Location and Clearances Coil Flange Installation Floor Base and Ductwork Installation DownflowCOIL/FURNACE Assembly MC/FC/PC Series Coils Furnace Assembly MC & FC Series CoilsCritical Coil Projection Furnace Assembly PC Series CoilsCoil / Furnace Assembly HC Series Coils Downflow Duct ConnectorsHorizontal Application Bottom Return and Attic InstallationsAttic Installation Suspended Furnace / Crawl Space InstallationSide Return Filter InstallationAttempt to install filters inside the furnace Section III FiltersGAS Conversion for Propane LP GAS SafetyGAS Piping Installation Section IV GAS PipingHigh Altitude Natural GAS Orifice Conversion Section V Electrical PowerElectrical Power Connections Zoning Operation LOW Voltage Control Wiring ConnectionsSupply Voltage Connections AIR Conditioner ConnectionsID Models ThermostatModulating TWO Stage AIR Furnace Conditioner UIM-A-0508 Single Stage Heat Pump Modulating Furnace OD ModelsThermostat TWO Stage Heat Pump Modulating FurnaceSection VII Vent System Section VI Twinning and StagingFree Area Combustion Air Source From OutdoorsDampers, Louvers and Grilles Canada Only Air Supply Openings and DuctsNOx Screen Removal Lo-NOx Models Only Section Viii START-UP AdjustmentsVent and Supply Outside Air Safety Check Procedure Ventilated Combustion AirCalculating the Furnace Input Natural GAS Setup Test ModeGAS Piping Leak Check Revolution Cu Ft Seconds ForAdjustment of Temperature Rise Adjustment of Manifold GAS PressureRollout Switch Controls Section IX Safety ControlsAdjustment of FAN Control Settings Blower Door Safety SwitchLimit Controls Section X Normal Operation and DiagnosticsFurnace Control Diagnostics Pressure ControlsDiagnostic Fault Code Storage and Retrieval Fabricated Parts Section XI Replacement Parts ListJohnson Controls Unitary Products York Drive Norman, OK Section XII Wiring Diagram

LM8M/LMLM*MP, TM8M/TMLM*MP, CM8M/CMLM*MP, YM8M/YMLM*MP specifications

Johnson Controls TM8M/TMLM*MP, YM8M/YMLM*MP, LM8M/LMLM*MP, and CM8M/CMLM*MP are advanced temperature controllers designed for a wide range of applications in heating, ventilation, and air conditioning (HVAC) systems. These models stand out due to their robust features, cutting-edge technologies, and specific characteristics that cater to both residential and commercial environments.

One of the main features of the TM8M/TMLM*MP series is its user-friendly interface that incorporates a large, easy-to-read display. This allows for quick adjustments and monitoring of temperature settings, making it accessible for both skilled technicians and everyday users. The intuitive design ensures that users can efficiently navigate through various settings and configurations.

Another notable characteristic is the flexibility of these controllers. The series supports multiple sensor configurations, enabling the integration of both wired and wireless sensors. This adaptability allows users to customize their climate control systems according to specific needs and room layouts, ultimately enhancing comfort and energy efficiency.

The TM8M/TMLM*MP and its counterparts are equipped with sophisticated algorithms that optimize energy consumption. By utilizing predictive maintenance and intelligent analytics, these controllers can adjust settings dynamically based on real-time data. This not only helps in reducing operational costs but also prolongs the lifespan of HVAC equipment.

Incorporating advanced communication protocols is a hallmark of the Johnson Controls series. The TM8M and CM8M models support modern systems such as BACnet and Modbus, allowing seamless integration with building management systems (BMS). This compatibility ensures that users can maintain centralized control over multiple systems, enhancing overall operational efficiency.

Additionally, the series is robustly constructed to withstand harsh environmental conditions. Its durable casing and reliable components ensure long-term performance, making it suitable for a variety of settings, including industrial facilities and commercial properties.

Safety features are also integral to the design of the TM8M/TMLM*MP and related models. Built-in safeguards protect against over-temperature and other potential hazards, ensuring reliability and peace of mind for operators.

In summary, Johnson Controls TM8M/TMLM*MP, YM8M/YMLM*MP, LM8M/LMLM*MP, and CM8M/CMLM*MP controllers represent a convergence of user-friendly design, advanced technology, flexibility, and safety. Their ability to adapt to diverse applications while optimizing energy use makes them a critical component in modern HVAC systems, ensuring comfort and efficiency in every environment.