Johnson Controls TM8M/TMLM*MP, YM8M/YMLM*MP, LM8M/LMLM*MP GAS Piping Leak Check, Setup Test Mode

Page 21

368261-UIM-A-0508

6.Remove the burner assembly. It should be possible to swing the burner assembly out of the way without disconnecting the remain- ing wires.

7.With the burner assembly out of the way, simply slide the NOx screens out of the heat exchanger tubes and discard the screens.

8.Replace all components in reverse order. Reconnect all wiring.

GAS PIPING LEAK CHECK

FIRE OR EXPLOSION HAZARD

Failure to follow the safety warnings exactly could result in serious injury, death or property damage.

Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, personal injury or loss of life.

Burner ignition may not be satisfactory on first startup due to resid- ual air in the gas line or until gas manifold pressure is adjusted. The ignition control will make three attempts to light before locking out.

It is recommended that when the gas supply is first connected to the furnace, the ground union be loosened until the odor of gas is detected. When gas is detected, immediately tighten the union and check for gas leaks. Allow five minutes for any gas to dissipate before continuing with the startup procedure. Be sure that proper ventilation is available to dilute and carry away any vented gas.

With furnace in operation, check all of the pipe joints, gas valve connec- tions and manual valve connections for leakage using an approved gas detector, a non-corrosive leak detection fluid or other leak detection methods. Take appropriate action to stop any leak. If a leak persists, replace the faulty component.

The furnace and its equipment shutoff valve must be disconnected from the gas supply during any pressure testing of that system at test pres- sures in excess of 1/2 PSI (3.45 kPa).

The furnace must be isolated from the gas supply piping system by closing the equipment shutoff valve during any pressure testing of the gas supply system.

SETUP TEST MODE

During normal operation, the furnace input rate can vary between 50% and 100% of full nameplate input, making it difficult to check for proper operation. To help with the furnace startup process, the control has a TEST MODE available that allows the furnace input rate to stay at a constant input rate. To access this TEST MODE perform the following sequence:

1.With power to the board on and with no thermostat calls (no call for heating, cooling or continuous fan), push and hold the TEST but- ton on the board for one second. The LED on the board will glow red.

2.Release the TEST button. The LED on the board will flash a rapid green signal, indicating that TEST MODE is activated.

3.Turn the thermostat to call for heat (R & W signal).

4.The furnace will light and operate at high (100%) firing rate. The furnace firing rate should be checked at this level to confirm that the furnace is not overfired or underfired.

5.To run the furnace at minimum rate (50%), press the ERROR but- ton once. The LED will flash one green flash to confirm.

6.To run the furnace at a middle rate (70%), press the ERROR but- ton twice within a five-second period. The LED will flash green two times to confirm.

7.To again operate the furnace at maximum (100%) rate, press the ERROR button three times within a five-second period. The LED will flash green three times to confirm.

8.If the thermostat call for heat is removed, the LED will flash a rapid green signal, indicating that the furnace is still in TEST MODE.

9.When startup tests are completed, turning off power to the board will take the furnace out of TEST MODE and will restore normal operation. The furnace will automatically return to normal opera- tion after 150 minutes if power is not cycled.

CALCULATING THE FURNACE INPUT (NATURAL GAS)

NOTE: Burner orifices are sized to provide proper input rate using natu- ral gas with a heating value of 1030 BTU/Ft3 (38.4 MJ/m3). If the heat- ing value of your gas is significantly different, it may be necessary to replace the orifices.

NOTE: DO NOT set manifold pressure less than 3.2 in wc or more than

3.8in wc for natural gas at sea level. If manifold pressure is outside this range, change main burner orifices.

DO NOT bottom out gas valve regulator adjusting screw. This can result in unregulated manifold pressure and result in excess over- fire and heat exchanger failures.

NOTE: If orifice hole appears damaged or it is suspected to have been redrilled, check orifice hole with a numbered drill bit of correct size. Never redrill an orifice. A burr-free and sqaurely aligned orifice hole is essential for proper flame characteristics.

DO NOT bottom out gas valve regulator adjusting screw. This can result in unregulated manifold pressure and result in excess over- fire and heat exchanger failures.

Verify natural gas input rate by clocking meter.

1.Turn off all other gas appliances and pilots.

2.Run furnace for a minimum of 3 minutes in heating operation.

3.Measure time (in sec) for gas meter to complete 1 revolution and note reading. The 2 cubic feet dial provides a more accurate mea- surement of gas flow.

4.Refer to Table 10, "Gas Rate (CU FT/HR) at Full Input" for cubic feet of gas per hour.

5.Multiply cubic feet per hour by heating valve (BTU/cu ft) to obtain input.

If clocked rate does not match the input rate from the unit nameplate. follow steps in next section to adjust the manifold pressure. Repeat steps 2 - 5 until correct input is achieved.

Be sure to relight any gas appliances that were turned off at the start of this input check.

Johnson Controls Unitary Products

21

Image 21
Contents Models Section I SafetyList of Sections List of FiguresSafety Requirements Specific Safety Rules and PrecautionsAnce to a 50 HZ Power Supply or a Voltage Above 130 Volts Combustion AIR Quality List of ContaminantsInspection Codes and StandardsSection II Ductwork Furnace Location and ClearancesDuctwork General Information COIL/FURNACE Assembly MC/FC/PC Series Coils Floor Base and Ductwork Installation DownflowFurnace Assembly MC & FC Series Coils Coil Flange InstallationCoil / Furnace Assembly HC Series Coils Furnace Assembly PC Series CoilsDownflow Duct Connectors Critical Coil ProjectionAttic Installation Bottom Return and Attic InstallationsSuspended Furnace / Crawl Space Installation Horizontal ApplicationAttempt to install filters inside the furnace Filter InstallationSection III Filters Side ReturnGAS Piping Installation GAS SafetySection IV GAS Piping GAS Conversion for Propane LPSection V Electrical Power Electrical Power ConnectionsHigh Altitude Natural GAS Orifice Conversion Supply Voltage Connections LOW Voltage Control Wiring ConnectionsAIR Conditioner Connections Zoning OperationID Models ThermostatModulating TWO Stage AIR Furnace Conditioner UIM-A-0508 Single Stage Heat Pump Modulating Furnace OD ModelsThermostat TWO Stage Heat Pump Modulating FurnaceSection VII Vent System Section VI Twinning and StagingDampers, Louvers and Grilles Canada Only Combustion Air Source From OutdoorsAir Supply Openings and Ducts Free AreaVent and Supply Outside Air Safety Check Procedure Section Viii START-UP AdjustmentsVentilated Combustion Air NOx Screen Removal Lo-NOx Models OnlySetup Test Mode GAS Piping Leak CheckCalculating the Furnace Input Natural GAS Revolution Cu Ft Seconds ForAdjustment of Temperature Rise Adjustment of Manifold GAS PressureAdjustment of FAN Control Settings Section IX Safety ControlsBlower Door Safety Switch Rollout Switch ControlsFurnace Control Diagnostics Section X Normal Operation and DiagnosticsPressure Controls Limit ControlsDiagnostic Fault Code Storage and Retrieval Fabricated Parts Section XI Replacement Parts ListJohnson Controls Unitary Products York Drive Norman, OK Section XII Wiring Diagram

LM8M/LMLM*MP, TM8M/TMLM*MP, CM8M/CMLM*MP, YM8M/YMLM*MP specifications

Johnson Controls TM8M/TMLM*MP, YM8M/YMLM*MP, LM8M/LMLM*MP, and CM8M/CMLM*MP are advanced temperature controllers designed for a wide range of applications in heating, ventilation, and air conditioning (HVAC) systems. These models stand out due to their robust features, cutting-edge technologies, and specific characteristics that cater to both residential and commercial environments.

One of the main features of the TM8M/TMLM*MP series is its user-friendly interface that incorporates a large, easy-to-read display. This allows for quick adjustments and monitoring of temperature settings, making it accessible for both skilled technicians and everyday users. The intuitive design ensures that users can efficiently navigate through various settings and configurations.

Another notable characteristic is the flexibility of these controllers. The series supports multiple sensor configurations, enabling the integration of both wired and wireless sensors. This adaptability allows users to customize their climate control systems according to specific needs and room layouts, ultimately enhancing comfort and energy efficiency.

The TM8M/TMLM*MP and its counterparts are equipped with sophisticated algorithms that optimize energy consumption. By utilizing predictive maintenance and intelligent analytics, these controllers can adjust settings dynamically based on real-time data. This not only helps in reducing operational costs but also prolongs the lifespan of HVAC equipment.

Incorporating advanced communication protocols is a hallmark of the Johnson Controls series. The TM8M and CM8M models support modern systems such as BACnet and Modbus, allowing seamless integration with building management systems (BMS). This compatibility ensures that users can maintain centralized control over multiple systems, enhancing overall operational efficiency.

Additionally, the series is robustly constructed to withstand harsh environmental conditions. Its durable casing and reliable components ensure long-term performance, making it suitable for a variety of settings, including industrial facilities and commercial properties.

Safety features are also integral to the design of the TM8M/TMLM*MP and related models. Built-in safeguards protect against over-temperature and other potential hazards, ensuring reliability and peace of mind for operators.

In summary, Johnson Controls TM8M/TMLM*MP, YM8M/YMLM*MP, LM8M/LMLM*MP, and CM8M/CMLM*MP controllers represent a convergence of user-friendly design, advanced technology, flexibility, and safety. Their ability to adapt to diverse applications while optimizing energy use makes them a critical component in modern HVAC systems, ensuring comfort and efficiency in every environment.