Johnson Controls TM9V*MP Downward Venting, Outdoor Combustion Air, Combustion AIR Supply

Page 27

701379-UIM-C-0712

DOWNWARD VENTING

In some applications, it may be necessary to run the vent pipe and air intake downwards. If this is to be done, the following rules must be fol- lowed.

• A condensate trap hose must be connected to both the air intake

pipe and the vent pipe at the lowest part of the horizontal run.

• The condensate drain trap must have a trap of a minimum of six

inches.

• The total vertical downward distance must not exceed sixteen

feet.

• The condensate drain hose must be connected to a condensate

drain pump, a open or vented drain or into the condensate drain

line from the furnace.

• The condensate drain lines must not pass through unconditioned

spaces where the temperature may fall below freezing.

Outdoor Combustion Air

Combustion Air Intake/Vent Connections

This installation requires combustion air to be brought in from outdoors. This requires a properly sized pipe (Shown in Figure 35) that will bring air in from the outdoors to the furnace combustion air intake collar on the burner box. The second pipe (Shown in Figure 35) is the furnace vent pipe.

NOTICE

An optional plastic birdscreen is shipped in the loose parts bag with every furnace. This may be installed in the intake collar to prevent any small objects from entering the furnace.

• The condensate drain line must be primed at the initial start-up

prior to the start of heating season.

16’ MAX

Connects to collar on top of burner box

Vent pipe cements into socket just above top panel

Or vent pipe may be clamped into outlet of drain coupling

6” MIN.

6” MIN.

FIGURE 35: Downward Venting

COMBUSTION AIR SUPPLY

All installations must comply with Section 5.3, Air for Combustion and Ventilation of the National Fuel Gas Code, ANSI Z223.1 or Sections 7.2, 7.3 or 7.4 of CAN/CGA B149.1 or .2 Installation Code - latest edi- tions.

This furnace is certified to be installed with one of three possible com- bustion air intake configurations.

1.OUTDOOR COMBUSTION AIR: This is a direct vent configuration where the combustion air is supplied through a PVC or ABS pipe that is connected to the PVC coupling attached to the furnace and is terminated in the same atmospheric zone as the vent. This type of installation is approved on all models. Refer to Figure 35.

2.AMBIENT COMBUSTION AIR: Combustion air is supplied from the area surrounding the furnace through openings in the furnace casing. The combustion air and the vent pipes are not terminated in the same atmospheric zone. Refer to Figure 30 for vent termina- tions. Refer to "Ambient Combustion Air Supply" for proper installa- tion. Refer to Figure 36.

3.VENTILATED COMBUSTION AIR: Combustion air is supplied through a PVC or ABS pipe that is connected to the PVC coupling attached to the burner box and is terminated in a ventilated attic or crawl space. The combustion air and the vent pipes are not termi- nated in the same atmospheric zone. Refer to Figure 38 for attic and crawl space termination. Only the combustion air intake may terminate in the attic. The vent must terminate outside.

FIGURE 36: Direct Vent Air Intake Connection and Vent Connection

The combustion air intake pipe should be located either through the wall (horizontal or side vent) or through the roof (vertical vent). Care should be taken to locate side vented systems where trees or shrubs will not block or restrict supply air from entering the terminal.

Also, the terminal assembly should be located as far as possible from a swimming pool or a location where swimming pool chemicals might be stored. Be sure the terminal assembly follows the outdoor clearances listed in Section #1 “Outdoor Air Contaminants.”

Ambient Combustion Air Supply

This type installation will draw the air required for combustion from within the space surrounding the appliance and from areas or rooms adjacent to the space surrounding the appliance. This may be from within the space in a non-confined location or it may be brought into the furnace area from outdoors through permanent openings or ducts. It is not piped directly into the furnace. A single, properly sized pipe from the furnace vent connector to the outdoors must be provided. It is recom- mended that the supplied intake coupling and 18” (46 cm) of pipe be attached to the furnace to prevent accidental blockage of the combus- tion air intake.

COMBUSTION AIR

Vent pipe cements

 

into socket just

 

above top panel

Or vent pipe may be clamped into outlet of drain coupling

FIGURE 37: Combustion Airflow Path Through The Furnace Casing

Johnson Controls Unitary Products

27

Image 27
Contents List of Tables Models TM9V*MPList of Sections List of FiguresSection I Safety Specific Safety Rules and PrecautionsSafety Requirements Codes and Standards Combustion AIR Quality List of ContaminantsFurnace Location and Clearances InspectionDuct Flanges Floor Base and Ductwork Installation DownflowSection II Ductwork Ductwork General InformationCoil Flange Installation Coil InstallationCOIL/FURNACE Assembly MC/FC/PC Series Coils Furnace Assembly MC & FC Series CoilsCritical Coil Projection Downflow Duct ConnectorsCoil / Furnace Assembly HC Series Coils Bottom Return and Attic InstallationsDownflow Application Horizontal ApplicationSection III Filters Filter InstallationCabinet Dimensions Inches Attempt to install filters inside the furnaceSide Return GAS SafetyGAS Piping Installation Section IV GAS PipingManifold Pressures in. w.c Manifold Pressures kPa High Altitude Pressure Switch ConversionGAS Orifice Conversion for Propane LP High Altitude GAS Orifice ConversionSupply Voltage Connections Section V Electrical PowerElectrical Power Connections LOW Voltage Control Wiring ConnectionsAC 9A TWO Stage Variable Speed Furnace OD Models AC 24C ID Models OD Models Single Stage Thermostat Accessory ConnectionsElectronic AIR Cleaner Connection Humidifier ConnectionTypical. Combustion Pipe Drain Tee Condensate Drain TerminationWill cause the furnace Airflow Horizontal Left Horizontal Right Inducer AS Received Right ConfigurationModel Input Pipe Size Maximum Combustion AIR and Vent SafetySection VII Combustion AIR and Vent System Combustion AIR/VENT Pipe SizingFitting Equivalent Length Combustion AIR and Vent Piping AssemblyCombustion AIR / Venting ElbowHome Layout Vent ClearancesVent System Vent Applications and TerminationVenting Multiple Units Ambient Combustion Air Supply Downward VentingOutdoor Combustion Air Combustion AIR SupplyFree Area Combustion Air Source From OutdoorsDampers, Louvers and Grilles Canada Only Air Supply Openings and DuctsVentilated Combustion Air Termination Ventilated Combustion AirIgnition System Sequence Section Viii START-UP AdjustmentsVent Blower Rotation GAS Piping Leak CheckSeconds For Revolution Cu FtRevolution Inlet GAS Pressure Range Adjustment of Manifold GAS Pressure & Input RateRead the inlet gas pressure Read the manifold gas pressureVariable Speed Motors Adjustment of Temperature RiseAdjustment of FAN Control Settings Heating Indoor Fan Off DelayHigh / LOW Heat CFM High / LOW Speed Cooling and Heat Pump CFMSection X Normal Operation and Diagnostics Section IX Safety ControlsTroubleshooting Furnace Control DiagnosticsHeating Cycle Diagnostic Fault Code Storage and Retrieval Section XI Replacement Parts List Replacement Part Contact InformationDescription XII Wiring DiagramWiring Diagram York International Corp York Drive Norman, OK

TM9V*MP specifications

Johnson Controls has long been a leader in providing innovative comfort solutions, and their TM9V*MP series of variable speed air handlers is a testament to their commitment to efficiency and performance. These products are designed to optimize heating and cooling in both residential and commercial applications, ensuring superior indoor air quality and comfort year-round.

One of the standout features of the TM9V*MP series is its variable speed technology. Unlike traditional single-speed systems, the TM9V*MP adjusts its airflow according to real-time heating and cooling demands. This not only enhances comfort by maintaining consistent temperatures but also significantly reduces energy consumption. The variable speed motor operates quietly and efficiently, making it ideal for both living environments and workplaces.

In terms of design, the TM9V*MP is engineered for ease of installation and maintenance. It comes in a compact size that allows for flexible positioning within existing ductwork, making retrofits simpler for contractors. Additionally, the modular design allows for easy access to internal components, which facilitates hassle-free servicing and maintenance.

The unit also features a robust filtration system that works in tandem with a range of air quality technologies. This includes optional media filters that capture allergens and particulates, ensuring that the air quality within a space is not only comfortable but also healthy. The integration of advanced technologies, such as integrated Wi-Fi capabilities, provides users with the ability to monitor and adjust settings remotely via smartphones or tablets.

Moreover, the TM9V*MP series is compatible with a wide range of communication protocols, enabling seamless connectivity with smart home systems. This means that users can create customized comfort profiles and take advantage of energy-saving features automatically.

Durability is another key characteristic of the TM9V*MP series. Built with high-quality materials and subjected to rigorous testing, these air handlers are designed to endure even the most demanding conditions while providing reliable performance over time.

In summary, Johnson Controls' TM9V*MP series offers an array of features that cater to modern comfort demands. With its variable speed technology, user-friendly design, air quality enhancements, and strong connectivity options, it stands out as a prime choice for both residential and commercial HVAC applications, setting a high standard for efficiency and indoor comfort.