Johnson Controls TM9V*MP Section II Ductwork, Ductwork General Information, Duct Flanges

Page 5

701379-UIM-C-0712

SECTION II: DUCTWORK

DUCTWORK GENERAL INFORMATION

The duct system’s design and installation must:

1.Handle an air volume appropriate for the served space and within the operating parameters of the furnace specifications.

2.Be installed in accordance of National Fire Protection Association as outlined in NFPA standard 90B (latest editions) or applicable national, provincial, state, and local fire and safety codes.

3.Create a closed duct system. For residential and non-HUD Modular Home installations, when a furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.

4.Complete a path for heated or cooled air to circulate through the air conditioning and heating equipment and to and from the condi- tioned space.

The cooling coil must be installed in the supply air duct, downstream of the furnace. Cooled air may not be passed over the heat exchanger.

When the furnace is used with a cooling coil, the coil must be installed parallel with, or in the supply air side of the furnace to avoid condensa- tion in the primary heat exchanger. When a parallel flow arrangement is used, dampers or other means used to control airflow must be ade- quate to prevent chilled air from entering the furnace. If manually oper- ated, the damper must be equipped with means to prevent the furnace or the air conditioner from operating unless the damper is in full heat or cool position.

When replacing an existing furnace, if the existing plenum is not the same size as the new furnace then the existing plenum must be removed and a new plenum installed that is the proper size for the new furnace. If the plenum is shorter than 12” (30.5 cm) the turbulent air flow may cause the limit controls not to operate as designed, or the limit con- trols may not operate at all.

The duct system is a very important part of the installation. If the duct system is improperly sized the furnace will not operate properly.

The ducts attached to the furnace plenum, should be of sufficient size so that the furnace operates at the specified external static pressure and within the air temperature rise specified on the nameplate.

The minimum plenum height is 12” (30.5 cm). The furnace will not operate properly on a shorter plenum height. The minimum recom- mended rectangular duct height is 4” (10.2 cm) attached to the ple- num.

The duct system must be properly sized to obtain the correct airflow for the furnace size that is being installed.

Refer to Table 7 or the furnace rating plate for the correct rise range and static pressures.

If the ducts are undersized, the result will be high duct static pres- sures and/or high temperature rises which can result in a heat exchanger OVERHEATING CONDITION. This condition can result in premature heat exchanger failure, which can result in personal injury, property damage, or death.

If a matching cooling coil is used, it may be placed directly on the fur- nace outlet and sealed to prevent leakage. If thermoplastic evaporator ‘A’ coil drain pans are to be installed in the upflow/horizontal configura- tion, then extra 2” (5.1 cm) minimum spacing may be needed to ensure against drain pan distortion.

On all installations without a coil, a removable access panel is recom- mended in the outlet duct such that smoke or reflected light would be observable inside the casing to indicate the presence of leaks in the heat exchanger. This access cover shall be attached in such a manner as to prevent leaks.

DUCT FLANGES

Four flanges are provided to attach ductwork to the furnace. These flanges are rotated down for shipment. In order to use the flanges, remove the screw holding an individual flange, rotate the flange so it is in the upward position and reinstall the screw then repeat this for all 4 flanges.

If the flanges are not used, they must remain in the rotated down posi- tion as shipped.

For duct attachment,

Factory

if needed.

installed

FIGURE 1: Duct Attachment

DUCTWORK INSTALLATION AND SUPPLY PLENUM CONNECTION - UPFLOW/HORIZONTAL

Attach the supply plenum to the furnace outlet. The use of an approved flexible duct connector is recommended on all installations. This connection should be sealed to prevent air leakage. The sheet metal should be crosshatched to eliminate any popping of the sheet metal when the indoor fan is energized.

FLOOR BASE AND DUCTWORK INSTALLATION - DOWNFLOW

Installations on combustible material or directly on any floors must use a combustible floor base shown in Figure 8. Follow the instructions supplied with the combustible floor base accessory. This combustible floor base can be replaced with a matching cooling coil, properly sealed to prevent leaks. Follow the instructions supplied with the cooling coil cabinet for installing the cabinet to the duct con- nector. Plug intake and vent pipe holes in bottom panel and move grommet to desired vent side exit.

Downflow Air Conditioning Coil Cabinet

The furnace should be installed with coil cabinet part number specifi- cally intended for downflow application. If a matching cooling coil is used, it may be placed directly on the furnace outlet and sealed to pre- vent leakage. For details of the coil cabinet dimensions and installation requirements, refer to the installation instructions supplied with the coil cabinet.

Attach the air conditioning coil cabinet to the duct connector, and then position the furnace on top of the coil cabinet. The connection to the fur- nace, air conditioning coil cabinet, duct connector, and supply air duct must be sealed to prevent air leakage.

Johnson Controls Unitary Products

5

Image 5
Contents List of Sections Models TM9V*MPList of Figures List of TablesSafety Requirements Section I SafetySpecific Safety Rules and Precautions Codes and Standards Combustion AIR Quality List of ContaminantsFurnace Location and Clearances InspectionSection II Ductwork Floor Base and Ductwork Installation DownflowDuctwork General Information Duct FlangesCOIL/FURNACE Assembly MC/FC/PC Series Coils Coil InstallationFurnace Assembly MC & FC Series Coils Coil Flange InstallationCoil / Furnace Assembly HC Series Coils Downflow Duct ConnectorsBottom Return and Attic Installations Critical Coil ProjectionDownflow Application Horizontal ApplicationCabinet Dimensions Inches Filter InstallationAttempt to install filters inside the furnace Section III FiltersGAS Piping Installation GAS SafetySection IV GAS Piping Side ReturnGAS Orifice Conversion for Propane LP High Altitude Pressure Switch ConversionHigh Altitude GAS Orifice Conversion Manifold Pressures in. w.c Manifold Pressures kPaElectrical Power Connections Section V Electrical PowerLOW Voltage Control Wiring Connections Supply Voltage ConnectionsAC 9A TWO Stage Variable Speed Furnace OD Models AC 24C ID Models OD Models Electronic AIR Cleaner Connection Accessory ConnectionsHumidifier Connection Single Stage ThermostatTypical. Combustion Pipe Drain Tee Condensate Drain TerminationWill cause the furnace Airflow Horizontal Left Horizontal Right Inducer AS Received Right ConfigurationSection VII Combustion AIR and Vent System Combustion AIR and Vent SafetyCombustion AIR/VENT Pipe Sizing Model Input Pipe Size MaximumCombustion AIR / Venting Combustion AIR and Vent Piping AssemblyElbow Fitting Equivalent LengthHome Layout Vent ClearancesVenting Multiple Units Vent SystemVent Applications and Termination Outdoor Combustion Air Downward VentingCombustion AIR Supply Ambient Combustion Air SupplyDampers, Louvers and Grilles Canada Only Combustion Air Source From OutdoorsAir Supply Openings and Ducts Free AreaVentilated Combustion Air Termination Ventilated Combustion AirVent Blower Rotation Section Viii START-UP AdjustmentsGAS Piping Leak Check Ignition System SequenceRevolution Seconds ForRevolution Cu Ft Read the inlet gas pressure Adjustment of Manifold GAS Pressure & Input RateRead the manifold gas pressure Inlet GAS Pressure RangeAdjustment of FAN Control Settings Adjustment of Temperature RiseHeating Indoor Fan Off Delay Variable Speed MotorsHigh / LOW Heat CFM High / LOW Speed Cooling and Heat Pump CFMSection X Normal Operation and Diagnostics Section IX Safety ControlsHeating Cycle TroubleshootingFurnace Control Diagnostics Diagnostic Fault Code Storage and Retrieval Description Section XI Replacement Parts ListReplacement Part Contact Information Wiring Diagram XII WiringDiagram York International Corp York Drive Norman, OK

TM9V*MP specifications

Johnson Controls has long been a leader in providing innovative comfort solutions, and their TM9V*MP series of variable speed air handlers is a testament to their commitment to efficiency and performance. These products are designed to optimize heating and cooling in both residential and commercial applications, ensuring superior indoor air quality and comfort year-round.

One of the standout features of the TM9V*MP series is its variable speed technology. Unlike traditional single-speed systems, the TM9V*MP adjusts its airflow according to real-time heating and cooling demands. This not only enhances comfort by maintaining consistent temperatures but also significantly reduces energy consumption. The variable speed motor operates quietly and efficiently, making it ideal for both living environments and workplaces.

In terms of design, the TM9V*MP is engineered for ease of installation and maintenance. It comes in a compact size that allows for flexible positioning within existing ductwork, making retrofits simpler for contractors. Additionally, the modular design allows for easy access to internal components, which facilitates hassle-free servicing and maintenance.

The unit also features a robust filtration system that works in tandem with a range of air quality technologies. This includes optional media filters that capture allergens and particulates, ensuring that the air quality within a space is not only comfortable but also healthy. The integration of advanced technologies, such as integrated Wi-Fi capabilities, provides users with the ability to monitor and adjust settings remotely via smartphones or tablets.

Moreover, the TM9V*MP series is compatible with a wide range of communication protocols, enabling seamless connectivity with smart home systems. This means that users can create customized comfort profiles and take advantage of energy-saving features automatically.

Durability is another key characteristic of the TM9V*MP series. Built with high-quality materials and subjected to rigorous testing, these air handlers are designed to endure even the most demanding conditions while providing reliable performance over time.

In summary, Johnson Controls' TM9V*MP series offers an array of features that cater to modern comfort demands. With its variable speed technology, user-friendly design, air quality enhancements, and strong connectivity options, it stands out as a prime choice for both residential and commercial HVAC applications, setting a high standard for efficiency and indoor comfort.