Johnson Controls TM9V*MP Combustion AIR and Vent Piping Assembly, Combustion AIR / Venting, Elbow

Page 24

701379-UIM-C-0712

 

A

A

 

 

A

A

 

STANDARD ELBOW

LONG (SWEEP) ELBOW

FIGURE 28: Dimensions

TABLE 9: Elbow Dimensions

Elbow

"A" Dimension

2" Standard

2-5/16"

3" Standard

3-1/16"

2" Sweep

3-1/4"

3" Sweep

4-1/16"

Dimensions are those required in Standard ASTM D-3311.

TABLE 10: Equivalent Length of Fittings

Fitting

Equivalent Length

2" 90° sweep elbow

5 feet of 2" pipe

2" 45° sweep elbow

2-1/2 feet of 2" pipe

2" 90° standard elbow

7 feet of 2" pipe

2" 45° standard elbow

3-1/2 feet of 2" pipe

3" 90° sweep elbow

5 feet of 3" pipe

3" 45° sweep elbow

2-1/2 feet of 3" pipe

3" 90° standard elbow

7 feet of 3" pipe

3" 45° standard elbow

3-1/2 feet of 3" pipe

4" 90° elbow (sweep or standard)

5 feet of 4" pipe

4" 45° elbow (sweep or standard)

2-1/2 feet of 4" pipe

2" corrugated connector

10 feet of 2" pipe

3" corrugated connector

10 feet of 3" pipe

4" corrugated connector

10 feet of 4" pipe

Example:

An 80,000 BTUH furnace requires 32 feet of pipe and five 90º elbows. Using 2" pipe and standard elbows, the total equivalent length will be:

32 feet of 2" pipe =

32 equivalent feet

5 - 90º standard 2" elbows = (5 x 7) =

35 equivalent feet

Total =

67 equivalent feet of 2" pipe

This exceeds the 65 foot maximum equivalent length of 2" pipe allowed for that model and is thus not acceptable.

By using sweep elbows, the total equivalent length will be:

32 feet of 2" pipe =

32 equivalent feet

5 - 90º sweep 2" elbows = (5 x 5) =

25 equivalent feet

Total =

57 equivalent feet of 2" pipe

This is less than the 65 foot maximum equivalent length of 2" pipe allowed for that model and is thus acceptable.

Alternatively, using 3" pipe and standard elbows, the total equivalent length will be:

32 feet of 3" pipe =

32 equivalent feet

5 - 90º standard 3" elbows = (5 x 7) =

35 equivalent feet

Total =

67 equivalent feet of 3" pipe

This is less than the 90 foot maximum equivalent length of 3" pipe allowed for that model and is thus acceptable.

TABLE 11: Combustion Air Intake and Vent Connection Size at Furnace (All Models)

FURNACE VENT CONNECTION SIZES

Furnace Input

All

Intake Pipe Size

2” (5.1 cm)

Vent Pipe Size

2” (5.1 cm)

Furnace vent pipe connections are sized for 2” (5.1 cm). pipe. Any pipe size change must be made outside the furnace casing in a verti- cal pipe section to allow proper drainage of condensate. An offset using two 45º (degree) elbows will be required for plenum clearance when the vent is increased to 3” (7.6 cm).

Accessory concentric vent / intake termination kits 1CT0302 and 1CT0303, and for Canadian applications 1CT0302-636 and 1CT0303-636 are available and approved for use with these fur- naces. Horizontal sidewall vent terminations kits 1HT0901 & 1HT0902 are also approved for use with these furnaces.

COMBUSTION AIR AND VENT PIPING ASSEMBLY

The final assembly procedure for the combustion air and vent piping is as follows:

1.Cut piping to the proper length beginning at the furnace.

2.Deburr the piping inside and outside.

3.Chamfer (bevel) the outer edges of the piping.

4.Dry-fit the vent piping assembly from the furnace to the outside ter- mination checking for proper fit support and slope.

5.Dry-fit the combustion air piping assembly checking for proper fit, support and slope on the following systems:

a.Sealed combustion air systems from the furnace to the outside termination.

b.Ventilated combustion air systems from the furnace to the attic or crawl space termination.

Solvent cements are flammable and must be used in well-ventilated areas only. Keep them away from heat, sparks and open flames. Do not breathe vapors and avoid contact with skin and eyes.

6.Disassemble the combustion air and vent piping, apply cement primer and the cement per the manufactures instructions. Primer and cement must conform to ASTM D2564 for PVC, or ASTM D2235 for ABS piping.

7.All joints must provide a permanent airtight and watertight seal.

8.Support the combustion air and vent piping such that it is angled a minimum of 1/4” per foot (21 mm/m) so that condensate will flow back towards the furnace. Piping should be supported with pipe hangers to prevent sagging.

9.Seal around the openings where the combustion air and / or vent piping pass through the roof or sidewalls.

COMBUSTION AIR / VENTING

The vent must be installed with the minimum required clearances, and must comply with local codes and requirements.

24

Johnson Controls Unitary Products

Image 24
Contents Models TM9V*MP List of SectionsList of Figures List of TablesSection I Safety Specific Safety Rules and PrecautionsSafety Requirements Combustion AIR Quality List of Contaminants Codes and StandardsInspection Furnace Location and ClearancesFloor Base and Ductwork Installation Downflow Section II DuctworkDuctwork General Information Duct FlangesCoil Installation COIL/FURNACE Assembly MC/FC/PC Series CoilsFurnace Assembly MC & FC Series Coils Coil Flange InstallationDownflow Duct Connectors Coil / Furnace Assembly HC Series CoilsBottom Return and Attic Installations Critical Coil ProjectionHorizontal Application Downflow ApplicationFilter Installation Cabinet Dimensions InchesAttempt to install filters inside the furnace Section III FiltersGAS Safety GAS Piping InstallationSection IV GAS Piping Side ReturnHigh Altitude Pressure Switch Conversion GAS Orifice Conversion for Propane LPHigh Altitude GAS Orifice Conversion Manifold Pressures in. w.c Manifold Pressures kPaSection V Electrical Power Electrical Power ConnectionsLOW Voltage Control Wiring Connections Supply Voltage ConnectionsAC 9A TWO Stage Variable Speed Furnace OD Models AC 24C ID Models OD Models Accessory Connections Electronic AIR Cleaner ConnectionHumidifier Connection Single Stage ThermostatCondensate Drain Termination Typical. Combustion Pipe Drain TeeWill cause the furnace Airflow Horizontal Left Right Configuration Horizontal Right Inducer AS ReceivedCombustion AIR and Vent Safety Section VII Combustion AIR and Vent SystemCombustion AIR/VENT Pipe Sizing Model Input Pipe Size MaximumCombustion AIR and Vent Piping Assembly Combustion AIR / VentingElbow Fitting Equivalent LengthVent Clearances Home LayoutVent System Vent Applications and TerminationVenting Multiple Units Downward Venting Outdoor Combustion AirCombustion AIR Supply Ambient Combustion Air SupplyCombustion Air Source From Outdoors Dampers, Louvers and Grilles Canada OnlyAir Supply Openings and Ducts Free AreaVentilated Combustion Air Ventilated Combustion Air TerminationSection Viii START-UP Adjustments Vent Blower RotationGAS Piping Leak Check Ignition System SequenceSeconds For Revolution Cu FtRevolution Adjustment of Manifold GAS Pressure & Input Rate Read the inlet gas pressureRead the manifold gas pressure Inlet GAS Pressure RangeAdjustment of Temperature Rise Adjustment of FAN Control SettingsHeating Indoor Fan Off Delay Variable Speed MotorsHigh / LOW Speed Cooling and Heat Pump CFM High / LOW Heat CFMSection IX Safety Controls Section X Normal Operation and DiagnosticsTroubleshooting Furnace Control DiagnosticsHeating Cycle Diagnostic Fault Code Storage and Retrieval Section XI Replacement Parts List Replacement Part Contact InformationDescription XII Wiring DiagramWiring Diagram York International Corp York Drive Norman, OK

TM9V*MP specifications

Johnson Controls has long been a leader in providing innovative comfort solutions, and their TM9V*MP series of variable speed air handlers is a testament to their commitment to efficiency and performance. These products are designed to optimize heating and cooling in both residential and commercial applications, ensuring superior indoor air quality and comfort year-round.

One of the standout features of the TM9V*MP series is its variable speed technology. Unlike traditional single-speed systems, the TM9V*MP adjusts its airflow according to real-time heating and cooling demands. This not only enhances comfort by maintaining consistent temperatures but also significantly reduces energy consumption. The variable speed motor operates quietly and efficiently, making it ideal for both living environments and workplaces.

In terms of design, the TM9V*MP is engineered for ease of installation and maintenance. It comes in a compact size that allows for flexible positioning within existing ductwork, making retrofits simpler for contractors. Additionally, the modular design allows for easy access to internal components, which facilitates hassle-free servicing and maintenance.

The unit also features a robust filtration system that works in tandem with a range of air quality technologies. This includes optional media filters that capture allergens and particulates, ensuring that the air quality within a space is not only comfortable but also healthy. The integration of advanced technologies, such as integrated Wi-Fi capabilities, provides users with the ability to monitor and adjust settings remotely via smartphones or tablets.

Moreover, the TM9V*MP series is compatible with a wide range of communication protocols, enabling seamless connectivity with smart home systems. This means that users can create customized comfort profiles and take advantage of energy-saving features automatically.

Durability is another key characteristic of the TM9V*MP series. Built with high-quality materials and subjected to rigorous testing, these air handlers are designed to endure even the most demanding conditions while providing reliable performance over time.

In summary, Johnson Controls' TM9V*MP series offers an array of features that cater to modern comfort demands. With its variable speed technology, user-friendly design, air quality enhancements, and strong connectivity options, it stands out as a prime choice for both residential and commercial HVAC applications, setting a high standard for efficiency and indoor comfort.