353AAV
AIR DELIVERY—CFM (WITH FILTER)
UNIT | SPEED |
|
| EXTERNAL STATIC PRESSURE (in.wc) |
|
| ||||||||
SIZE | SUPPLY | 0.1 | 0.2 | 0.3 |
| 0.4 | 0.5 | 0.6 | 0.7 |
| 0.8 | 0.9 | 1 | |
|
|
| ||||||||||||
|
| 5(Gry) | 1425 | 1385 | 1350 |
| 1305 | 1260 | 1210 | 1165 |
| 1100 | 995 | 855 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 4(Yel) | 1215 | 1165 | 1130 |
| 1085 | 1025 | 970 | 905 |
| 840 | 795 | 730 |
036040 | SIDE/BOTTOM | 3(Blu) | 1060 | 1005 | 960 |
| 910 | 845 | 790 | 715 |
| 660 | 610 | 560 |
|
| 2(Org) | 890 | 835 | 770 |
| 695 | 640 | 570 | 510 |
| 450 | 355 | 235 |
|
| 1(Red) | 880 | 675 | 570 |
| 475 | 425 | 335 | 245 |
| - | - | - |
|
| 5(Gry) | 1430 | 1390 | 1345 |
| 1300 | 1250 | 1205 | 1150 |
| 1080 | 995 | 845 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 3(Blu) | 1240 | 1200 | 1145 |
| 1100 | 1040 | 975 | 915 |
| 860 | 790 | 730 |
036060 | SIDE/BOTTOM | 4(Yel) | 1090 | 1030 | 980 |
| 935 | 850 | 800 | 730 |
| 665 | 590 | 525 |
|
| 1(Red) | 900 | 835 | 780 |
| 705 | 635 | 565 | 490 |
| 410 | 335 | 200 |
|
| 2(Org) | 805 | 620 | 440 |
| 380 | 300 | - | - |
| - | - | - |
|
| 5(Gry) | 1400 | 1360 | 1325 |
| 1285 | 1240 | 1205 | 1160 |
| 1125 | 1075 | 1000 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 3(Blu) | 1340 | 1300 | 1265 |
| 1215 | 1180 | 1135 | 1100 |
| 1055 | 1015 | 965 |
036080 | SIDE/BOTTOM | 4(Yel) | 1195 | 1160 | 1115 |
| 1065 | 1025 | 985 | 935 |
| 895 | 850 | 800 |
|
| 1(Red) | 1025 | 980 | 935 |
| 880 | 835 | 795 | 745 |
| 685 | 635 | 585 |
|
| 2(Org) | 855 | 800 | 745 |
| 680 | 635 | 560 | 515 |
| 460 | 420 | 360 |
|
| 5(Gry) | 1720 | 1695 | 1690 |
| 1655 | 1620 | 1580 | 1540 |
| 1495 | 1465 | 1415 |
|
| 3(Blu) | 1565 | 1535 | 1530 |
| 1490 | 1450 | 1420 | 1375 |
| 1335 | 1295 | 1255 |
048080 | SIDE/BOTTOM | 4(Yel) | 1330 | 1310 | 1270 |
| 1220 | 1180 | 1135 | 1095 |
| 1055 | 1010 | 970 |
|
| 2(Org) | 1210 | 1180 | 1135 |
| 1085 | 1035 | 995 | 950 |
| 910 | 865 | 810 |
|
| 1(Red) | 1110 | 1065 | 1005 |
| 960 | 910 | 865 | 820 |
| 770 | 720 | 670 |
|
| 5(Gry) | 2070 | 2020 | 1985 |
| 1925 | 1890 | 1850 | 1795 |
| 1755 | 1690 | 1610 |
|
| 3(Blu) | 1815 | 1775 | 1730 |
| 1690 | 1635 | 1595 | 1555 |
| 1500 | 1460 | 1410 |
060100 | SIDE/BOTTOM | 4(Yel) | 1580 | 1535 | 1480 |
| 1440 | 1380 | 1380 | 1340 |
| 1285 | 1235 | 1185 |
|
| 2(Org) | 1380 | 1325 | 1275 |
| 1220 | 1220 | 1165 | 1105 |
| 1060 | 1000 | 960 |
|
| 1(Red) | 1170 | 1105 | 1055 |
| 985 | 935 | 870 | 805 |
| 765 | 705 | 660 |
|
| 5(Gry) | 2250 | 2205 | 2155 |
| 2110 | 2065 | 2020 | 1970 |
| 1925 | 1870 | 1790 |
|
| 3(Blu) | 2130 | 2085 | 2030 |
| 1980 | 1925 | 1880 | 1830 |
| 1775 | 1730 | 1675 |
060120 | SIDE/BOTTOM | 4(Yel) | 1890 | 1835 | 1790 |
| 1740 | 1690 | 1640 | 1590 |
| 1535 | 1480 | 1435 |
|
| 1(Red) | 1640 | 1585 | 1525 |
| 1475 | 1425 | 1365 | 1315 |
| 1260 | 1200 | 1140 |
|
| 2(Org) | 1420 | 1370 | 1305 |
| 1255 | 1190 | 1135 | 1065 |
| 1010 | 940 | 880 |
] • Airflow shown is for bottom only return air supply with factory supplied 3/4 in. (19 mm) washable |
|
|
|
|
| |||||||||
For air delivery above 1800 CFM, see Air Delivery table for other options. |
|
|
|
|
|
|
|
|
|
| ||||
An airflow reduction of up to 7% may occur when using the factory specified 4 |
|
|
| |||||||||||
For best furnace efficiency when using the 4 | in. (110 mm) wide media filter, adjust the blower speed tap to near the | point of the rise range. |
|
For horizontal and downflow applications, use one side or bottom or bottom only as airflow reference.
12