Bryant 350MAV user manual VI. Servicing HOT Surface Igniter, Tube Routing

Page 7

14.Check furnace operation through 2 complete heat operating cycles. Check area below inducer housing, vent pipe, and condensate trap to ensure no condensate leaks occur. If leaks are found, correct the problem.

WARNING: FIRE OR EXPLOSION HAZARD

Failure to follow the safety warnings exactly could result in serious injury, death, or property damage.

Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, per- sonal injury, or loss of life.

15. Check for gas leaks.

2.Remove main furnace door.

3.Disconnect igniter wire connection.

4.Check igniter resistance.

a.Using an ohm meter, check resistance across both igniter leads in connector.

b.Cold reading should be between 45 ohms and 90 ohms.

c.If ohm reading is higher than 110 ohms, igniter is cracked and must be replaced.

5.Remove igniter assembly.

CAUTION: Allow igniter to cool before removal. Nor- mal operating temperatures exceed 2000°F.

16. Replace main furnace door.

VI. SERVICING HOT SURFACE IGNITER

The igniter does NOT require annual inspection. Check igniter resistance before removal.

1. Turn off gas and electrical supplies to furnace.

TUBE ROUTING

a.Do not remove igniter from bracket while assembly is in furnace. Using a 1/4 in. nutdriver, remove screw secur- ing bracket and igniter assembly to bottom of burner box. The screw in the bracket is always located toward outside of burner box. The screw may be hidden by inlet

Furnace is shipped from factory in upflow configuration. Pressure tube and drain tube routing MUST match the diagrams below.

Condensate Trap; Factory Installed

in Blower Shelf

(Blower access panel removed)

COLLECTOR BOX TUBE

(PINK)

COLLECTOR BOX TUBE

(GREEN)

INDUCER HOUSING (MOLDED) DRAIN TUBE (BEHIND COLLECTOR BOX DRAIN TUBE)

COLLECTOR BOX DRAIN TUBE

(BLUE)

FIELD-INSTALLED

FACTORY-SUPPLIED DRAIN TUBE

COUPLING (LEFT DRAIN OPTION)

FIELD-INSTALLED FACTORY-SUPPLIED

DRAIN TUBE

Tube location when used in UPFLOW application

Condensate Trap on LEFT

 

 

Side Optional

BURNER ENCLOSURE

 

BURNER ENCLOSURE

PRESSURE REFERENCE

 

PRESSURE REFERENCE

TUBE ASSEMBLY

 

 

TUBE ASSEMBLY

CAP

 

CAP

 

 

PLUG

COLLECTOR BOX TUBE

PLUG

 

 

 

COLLECTOR BOX DRAIN

(PINK)

 

 

 

TUBE

COLLECTOR BOX TUBE (GREEN)

 

(BLUE & WHITE STRIPED)

COLLECTOR BOX DRAIN TUBE

 

 

(BLUE & WHITE STRIPED)

CONDENSATE TRAP

COLLECTOR BOX DRAIN TUBE

 

 

 

 

(BLUE)

 

FIELD-INSTALLED

 

FACTORY-SUPPLIED

CONDENSATE TRAP

DRAIN TUBE COUPLING

 

(RIGHT DRAIN OPTION)

INDUCER HOUSING DRAIN TUBE

 

 

(VIOLET)

FIELD-INSTALLED

FACTORY-SUPPLIED 1/2-IN.

CPVC STREET ELBOWS (2)

FOR LEFT DRAIN OPTION

Condensate Trap on

Tube location when used in DOWNFLOW application

Condensate Trap on

LEFT Side

 

 

RIGHT Side

 

COLLECTOR BOX

 

PLUG

CAP

 

 

DRAIN TUBE (BLUE)

 

CAP

 

PLUGGED END

 

COLLECTOR BOX DRAIN TUBE

 

 

 

 

 

COLLECTOR BOX DRAIN

(BLUE)

COLLECTOR BOX

 

TUBE

 

 

(BLUE & WHITE STRIPED)

COLLECTOR BOX TUBE

TUBE (GREEN)

 

 

 

(PINK)

 

 

 

COLLECTOR BOX DRAIN TUBE

PLUG

 

 

(BLUE & WHITE STRIPED)

 

INDUCER HOUSING DRAIN

COLLECTOR BOX TUBE

 

 

(GREEN)

COLLECTOR BOX

 

TUBE (VIOLET)

 

 

 

 

COLLECTOR BOX EXTENSION TUBE

EXTENSION TUBE

 

 

 

COLLECTOR BOX

 

BURNER ENCLOSURE PRESSURE

 

 

REFERENCE TUBE ASSEMBLY

CONDENSATE TRAP

EXTENSION TUBE

 

DRAIN TUBE COUPLING

CONDENSATE TRAP

 

 

BURNER ENCLOSURE PRESSURE

COLLECTOR BOX

 

 

TUBE (PINK)

DRAIN TUBES ROUTED IN

COLLECTOR BOX

REFERENCE TUBE ASSEMBLY

 

 

FRONT OF GAS VALVE

EXTENSION DRAIN TUBE

INDUCER HOUSING DRAIN TUBE (VIOLET)

 

 

GAS VALVE

 

 

 

 

Tube location when used on

 

Tube location when used on

 

 

HORIZONTAL - LEFT application

 

HORIZONTAL - RIGHT application

 

 

 

 

 

 

COLLECTOR BOX DRAIN TUBE

COLLECTOR BOX DRAIN TUBE

COLLECTOR BOX EXTENSION TUBE

(BLUE & WHITE STRIPED)

(BLUE)

COLLECTOR BOX TUBE (PINK)

PLUG

 

 

 

CAP

COLLECTOR BOX

PLUG

AUXILIARY "J" BOX RELOCATED HERE

BURNER ENCLOSURE

TUBE (GREEN)

 

 

 

PRESSURE REFERENCE

 

 

TUBE ASSEMBLY

 

 

COLLECTOR BOX

INDUCER HOUSING

CAP

DRAIN TUBE

EXTENSION TUBE

BURNER ENCLOSURE

(VIOLET)

PRESSURE REFERENCE

 

 

 

TUBE ASSEMBLY

CONDENSATE TRAP

 

COLLECTOR BOX

 

 

 

DRAIN TUBE (BLUE)

COLLECTOR BOX

COLLECTOR BOX

 

DRAIN TUBE

COLLECTOR BOX TUBE (PINK)

TUBE (GREEN)

EXTENSION TUBE

 

 

 

COLLECTOR BOX EXTENSION DRAIN TUBE

COUPLING

RELOCATE TUBE BETWEEN BLOWER

COLLECTOR BOX DRAIN TUBE

CONDENSATE TRAP

 

 

SHELF AND INDUCER HOUSING FOR

 

 

(BLUE AND WHITE STRIPED)

 

 

 

040,060, AND 080 HEATING INPUT

INDUCER HOUSING DRAIN TUBE (VIOLET)

NOTE:

 

FURNACES

 

 

 

 

 

 

 

 

1.All tubing must be connected securely and routed to avoid kinks and traps.

2.Pressure tubing must always slope away from pressure switch to collector box connection as shown.

3. HORIZONTAL-LEFT installations require the collector box pressure tube to be relocated between the inducer housing and the blower shelf to

324999-201 REV. C

prevent a trap. Refer to the Installation Instructions for further details.

 

A00308

Fig. 8—Furnace Pressure and Drain Tubing Diagram

—7—

Image 7
Contents Safety Considerations Table of ContentsCare and Maintenance Electrostatic Discharge ESD PrecautionsGeneral II. Blower Motor and Wheel Maintenance Cleaning AND/OR Replacing AIR FilterSpeed Selection III. Cleaning BurnersPrimary Heat Exchangers IV. Cleaning Heat ExchangersFlushing Collector BOX and Drainage System Cleaning Inlet Openings of Primary Heat ExchangersTube Routing VI. Servicing HOT Surface IgniterVIII. Checking Heat Tape Operation if Applicable VII. Electrical Controls and WiringIX. Winterizing Troubleshooting Wiring DiagramControl Center Inducer Housing Drain Tube PCB Service Troubleshooting Guide A02204b
Related manuals
Manual 12 pages 42.74 Kb