Bryant 350MAV user manual Service

Page 13
327884-101 REV. A

SERVICE

If status code recall is needed, briefly remove then reconnect one main limit wire to display stored status code. On RED LED boards do not remove power or blower door before initiat- ing status code recall. After status code recall is completed component test will occur.

LED CODE

STATUS

CONTINUOUS OFF - Check for 115VAC at L1 & L2, & 24VAC at SEC-1 & SEC-2. CONTINUOUS ON - Control has 24VAC power.

RAPID FLASHING - Line voltage (115VAC) polarity reversed. If twinned, refer to twinning kit instructions.

EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WITH THE FIRST

DIGIT DETERMINED BY THE NUMBER OF SHORT FLASHES AND THE SECOND DIGIT BY

THE NUMBER OF LONG FLASHES.

11NO PREVIOUS CODE - Stored status code is erased automatically after 72 hours. On RED LED boards stored status codes can also be erased when power

(115 VAC or 24 VAC) to control is interrupted.

12 BLOWER ON AFTER POWER UP (115 VAC or 24 VAC) -Blower runs for 90 seconds, if unit is powered up during a call for heat (R-W closed) or R-W opens during blower on-delay.

13LIMIT CIRCUIT LOCKOUT - Lockout occurs if the limit or flame rollout switch is open longer than 3 minutes.

- Control will auto reset after three hours.

- Refer to #33.

14IGNITION LOCKOUT - Control will auto-reset after three hours. Refer to #34.

21GAS HEATING LOCKOUT - Control will NOT auto reset.

Check for: - Mis-wired gas valve

-Defective control (valve relay)

22ABNORMAL FLAME-PROVING SIGNAL - Flame is proved while gas valve is de-energized. Inducer will run until fault is cleared. Check for:

 

- Leaky gas valve

- Stuck-open gas valve

23

PRESSURE SWITCH DID NOT OPEN Check for:

 

- Obstructed pressure tubing. - Pressure switch stuck closed.

24

SECONDARY VOLTAGE FUSE IS OPEN Check for:

 

- Short circuit in secondary voltage (24VAC) wiring.

31

PRESSURE SWITCH DID NOT CLOSE OR REOPENED - If open longer than

 

five minutes, inducer shuts off for 15 minutes before retry. Check for:

 

- Excessive wind - Proper vent sizing

- Defective inducer motor

 

- Low inducer voltage (115VAC)

- Defective pressure switch

 

- Inadequate combustion air supply

- Restricted vent

- Disconnected or obstructed pressure tubing - Low inlet gas pressure (if LGPS used)

If it opens during blower on-delay period, blower will come on for the selected blower off-delay.

33LIMIT CIRCUIT FAULT - Indicates a limit, or flame rollout is open. Blower will

run for 4 minutes or until open switch remakes whichever is longer. If open longer than 3 minutes, code changes to lockout #13. If open less than 3 minutes status code #33 continues to flash until blower shuts off. Flame rollout switch

requires manual reset. Check for: - Restricted vent

 

- Proper vent sizing

- Loose blower wheel

- Excessive wind

- Dirty filter or restricted duct system.

 

- Defective blower motor or capacitor. - Defective switch or connections. - Inadequate combustion air supply (Flame Roll-out Switch open).

34IGNITION PROVING FAILURE - Control will try three more times before lockout #14 occurs. If flame signal lost during blower on-delay period, blower will come on for the selected blower off-delay. Check for: - Control ground continuity

-Flame sensor must not be grounded

-Oxide buildup on flame sensor (clean with fine steel wool).

-Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal).

- Gas valve defective or gas valve turned off

- Manual valve shut-off

-Defective Hot Surface Ignitor

-Low inlet gas pressure

-Inadequate flame carryover or rough ignition

-Green/Yellow wire MUST be connected to furnace sheet metal

45CONTROL CIRCUITRY LOCKOUT Auto-reset after one hour lockout due to;

- Gas valve relay stuck open - Flame sense circuit failure - Software check error

Reset power to clear lockout. Replace control if status code repeats.

COMPONENT TEST

To initiate the component test sequence, shut OFF the room thermostat or disconnect the "R" thermostat lead. Briefly short the TEST/TWIN terminal to the "Com 24V" ter- minal. Status LED will flash code and then turn ON the inducer motor. The inducer motor will run for the entire component test. The hot surface ignitor, blower motor FAN speed (AMBER LED boards only) blower motor HEAT speed, and blower motor COOL speed will be turned ON for 10-15 seconds each. Gas Valve and Humidifier will not be turned on.

A02154

Fig. 17—Service Label

—13—

Image 13
Contents Safety Considerations Table of ContentsCare and Maintenance Electrostatic Discharge ESD PrecautionsGeneral II. Blower Motor and Wheel Maintenance Cleaning AND/OR Replacing AIR FilterSpeed Selection III. Cleaning BurnersPrimary Heat Exchangers IV. Cleaning Heat ExchangersFlushing Collector BOX and Drainage System Cleaning Inlet Openings of Primary Heat ExchangersTube Routing VI. Servicing HOT Surface IgniterVIII. Checking Heat Tape Operation if Applicable VII. Electrical Controls and WiringIX. Winterizing Troubleshooting Wiring DiagramControl Center Inducer Housing Drain Tube PCB Service Troubleshooting Guide A02204b