| M | 1 | OFF | ON |
|
| |||
O | P | 3 | ||
F |
|
|
| |
|
|
|
| |
F |
| 2 | OR |
|
| C |
| ||
|
|
| ||
| ON |
|
| |
|
|
|
| |
|
|
|
| 13 |
ON
|
| 14 |
|
|
| M | 1 | OFF | ON |
O | P | 3 | ||
F |
|
|
| |
|
|
|
| |
F |
| 2 | OR |
|
| C |
| ||
|
|
| ||
| ON |
|
| |
|
|
|
|
11.After 15 to 70 sec, the gas valve permits gas to flow to the main burners where it is ignited. Hot flames begin to warm the furnace’s heat exchanger. After a time delay of approximately 45 sec, the fur- nace blower is switched on.
NOTE: If the main burners fail to ig- nite, the furnace control system will go through 3 more ignition cycles. Then, if burners fail to ignite, the system will lockout. If lockout occurs, or the blower doesn’t come
12.Set your thermostat to the tempera- ture that satisfies your comfort re- quirements. SUGGESTION: Setting the thermostat back a few
When the room temperature drops below the temperature selected on the thermostat, the furnace will be switched on automatically. When the room temperature reaches the degree selected on the thermostat, the furnace will be switched off automatically.
Some thermostats have a “fan’’ mode with 2 selections: AUTO or ON. When set on AUTO, the furnace blower cy-
16 |
15 |
17 |
cles on and off, controlled by the ther- mostat. In the ON position, the furnace blower runs continuously except for a
SHUTTING DOWN YOUR FURNACE
Should you ever suspect a malfunction in your furnace, you will need to turn the furnace off. The following proce- dures must be followed:
OP
E
N
18 | 19 |
5
1.Set your room thermostat to the lowest temperature setting. (See Fig. 20.)
2.Close the external manual gas valve. (See Fig. 8 on page 4.)
3.Turn OFF the electrical supply to your furnace. (See Fig. 21.)
4.Remove the control access door on your furnace. (See Fig. 10 or 11.) On upflow furnaces, removing the blower access door is not required.