Superior VFGL-28MSP-4 SERIES* Possible Cause Remedy, Troubleshooting, Gas, Observed Problem

Page 11

 

TROUBLESHOOTING

GUIDE FOR VENT-FREE

GAS

PRODUCTS

 

 

 

 

 

 

 

 

 

 

 

 

 

OBSERVED PROBLEM

POSSIBLE CAUSE

 

 

 

REMEDY

 

 

 

 

 

 

 

 

 

 

 

1.

When igniter button is

A. Igniter electrode positioned wrong.

Replace igniter.

 

 

 

 

 

pressed, there is no spark

 

 

 

 

 

 

 

 

 

 

 

Replace igniter.

 

 

 

 

 

at ODS/pilot.

B. Igniter electrode broken.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C. Igniter electrode not connected to igniter cable.

Reconnect igniter cable.

 

 

 

 

 

 

 

 

 

 

 

 

D. Igniter cable pinched or wet.

Free igniter cable if pinched by any metal or tubing. Keep igniter cable dry.

 

 

 

 

 

 

 

 

 

 

 

 

E. Piezo igniter nut is loose.

Tighten nut.

 

 

 

 

 

 

 

 

 

 

 

 

F. Broken igniter cable.

Replace igniter cable.

 

 

 

 

 

 

 

 

 

 

 

 

G. Bad piezo igniter.

Replace piezo igniter.

 

 

 

 

 

 

 

 

2.

Heater produces unwanted

A. Heater burning vapors from paint, hair spray, glues, etc.

Ventilate room. Stop using odor-causing products while fireplace is running.

 

 

 

odors.

 

 

 

 

 

 

 

 

 

B. Gas leak. See Warning statement on the front page.

Locate and correct all leaks.

 

 

 

 

 

 

 

 

 

 

 

 

 

3.

Heater shuts off in use

A. Not enough fresh air is available.

Open window and/or door for ventilation.

 

 

 

(ODS operates).

 

 

 

 

 

 

 

 

 

B. Low line pressure.

Contact local gas company.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C. ODS/pilot is partially clogged.

Clean ODS/pilot.

 

 

 

 

 

 

 

 

4.

Gas odor even when control

A. Gas leak. See Warning statement on the front page.

Locate and correct all leaks (see Checking Gas Connections, page 6).

 

 

 

knob is in “OFF” position.

 

 

 

 

 

 

 

 

 

 

 

B. Control valve defective.

Replace control valve.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.

When igniter button is

 

A. Gas supply turned off or manual shut-off valve closed.

Turn on gas supply or open manual shut-off valve.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pressed, there is spark at

B. Control knob not in “PILOT” position.

Turn control knob to pilot position.

 

 

 

ODS/pilot, but no ignition.

 

 

 

 

 

 

 

 

 

C. Control knob not pressed in while in “PILOT” position.

Press in control knob while in pilot position.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D. Air in gas lines when installed.

Continue holding down control knob. Repeat igniting operation until air is

 

 

 

 

 

 

 

removed.

 

 

 

 

 

 

 

 

 

 

 

 

E. ODS/pilot is clogged.

Replace ODS/pilot assembly or get it serviced.

 

 

 

 

 

 

 

 

 

 

 

 

F. Gas regulator setting is not correct.

Replace gas regulator.

 

 

 

 

 

 

 

 

6.

ODS/pilot lights, but flame

A. Control knob not fully pressed in.

Press in control knob fully.

 

 

 

goes out when control knob

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

is released.

B. Control knob not pressed in long enough.

After ODS/pilot lights, keep control knob pressed in 30 seconds.

 

 

 

 

 

 

 

 

 

 

 

 

C. Manual shut-off valve not fully open.

Fully open manual shut-off valve.

 

 

 

 

 

 

 

 

 

 

 

 

D. Thermocouple connection loose at control valve.

Hand tighten until snug, then tighten ¹⁄₄ turn more.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E. Pilot flame not touching thermocouple, which allows

 

 

 

 

 

 

 

 

 

thermocouple to cool, causing pilot flame to go out. This

 

 

 

 

 

 

 

 

 

problem could be caused by one or both of the following:

1). Contact local gas company.

 

 

 

 

 

1). Low gas pressure

 

 

 

 

 

2). Dirty or partially clogged ODS/pilot

2). Replace ODS/pilot assembly or get pilot serviced.

 

 

 

 

 

 

 

 

 

 

 

 

F. Thermocouple damaged.

Replace thermocouple.

 

 

 

 

 

 

 

 

 

 

 

 

G. Control valve damaged.

Replace control valve.

 

 

 

 

 

 

 

 

7.

Burner does not light after

A. Burner orifice is clogged.

Clean burner or replace burner orifice.

 

 

 

ODS/pilot is lit.

 

 

 

 

 

 

 

 

 

B. Burner orifice diameter is too small.

Replace burner orifice.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C. Inlet gas pressure is too low.

Contact local gas company.

 

 

 

 

 

 

 

 

8.

Delayed ignition of burner.

A. Manifold pressure is too low.

Contact local gas company.

 

 

 

 

 

 

 

 

 

 

 

 

B. Burner orifice is clogged.

Clean burner or replace burner orifice.

 

 

 

 

 

 

 

 

9.

Burner backfiring during

A. Burner orifice is clogged or damaged.

Clean burner or replace burner orifice.

 

 

 

combustion.

 

 

 

 

 

 

 

 

 

 

 

B. Burner damaged.

Replace burner.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C. Gas regulator defective.

Replace gas regulator.

 

 

 

 

 

 

 

 

10.

Slight smoke or odor during

A. Vapors from paint or curing process of logs.

Problem will stop after a few hours of operation. Superior recommends

 

 

 

initial operation.

 

 

running the heater with the excess ventilation for the first few hours.

 

 

 

 

 

 

 

 

11.

Heater produces a whistling

A. Turning control knob to “HI” position when burner is cold.

Turn control knob to “LO” position and let warm up for a minute.

 

 

 

noise when burner is lit.

 

 

 

 

 

 

 

 

 

B. Air in gas line.

Operate burner until air is removed from line. Have gas line checked by local gas

 

 

 

 

 

 

 

 

 

 

 

 

company.

 

 

 

 

 

 

 

 

 

 

 

 

 

C. Dirty or partially clogged burner orifice.

Clean burner

or replace burner orifice.

 

11

 

 

 

 

 

 

 

 

 

 

Image 11
Contents Unvented Gas Log Room Heaters 903623 REV. M 12/2007 Consumer Retain this manual for future referenceFor USE only with Decorative Type Unvented Room Heaters Table of Contents Massachusetts CodesMassachusetts And New York Require- ments Combustion and Ventilation AIRExample PreinstallationCheck Gas Type ClearancesOr more Requirements for Safe InstallationNoncombustible Material Heights and Mantel Location At leastConsult all local codes InstallationQualified gas appliance installer must install this heater Periodically verify proper positioning of all logs Gas Pressure CheckAssembling the Logs LHP Cleaning and ServicingReplacement Parts Operation and Care of Your ApplianceOptional Equipment BTU/HR Unvented GAS LOG Room Heater Specification ChartUnvented GAS LOG Room Heater Technical Chart GAS TroubleshootingObserved Problem Possible Cause RemedyLighting Instructions For Your Safety Read Before LightingOperating Instructions Manual Control Models What to do if YOU Smell GASPiezo Flame Adjustment OFF position Figure Stop! Read the safety information aboveOperating Instructions Locate gas control knob and piezoTurn Control Knob to on Position Turn Control Knob to OFF Position Pilot Pilot Location18N/18P 24N/24P 28N/28P Description Replacement Parts ListReplacement Parts Page Page Orange, CA 903623 REV. M 12/2007