TROUBLESHOOTING THE MILLIVOLT GAS CONTROL SYSTEM

Note: Before troubleshooting the gas control system, be sure external gas shut off valve (located at gas supply inlet) is in the “ON” position.

Important: Valve system troubleshooting should only be accomplished by a qualified service technician.

 

SYMPTOM

POSSIBLE CAUSES

CORRECTIVE ACTION

 

 

 

 

 

1.

Spark ignitor will not light

A. Defective ignitor

Check for spark at electrode and pilot; if no spark and

 

pilot after repeated

(no spark at electrode).

electrode wire is properly connected, replace ignitor.

 

triggering of ignitor button.

 

 

 

 

 

B. Defective or misaligned electrode

Using a match, light pilot. If pilot lights, turn off pilot and

 

 

 

 

 

 

at pilot (spark at electrode).

trigger the ignitor button again. If pilot lights, an improper gas

 

 

 

 

mixture caused the bad lighting and a longer purge period is

 

 

 

 

recommended. If pilot will not light – check gap at electrode

 

 

 

 

and pilot – should be ¹⁄₈" to have a strong spark. If gap

 

 

 

 

measures ¹⁄₈", replace pilot (Figure 10 on page 8- SIT, Figure

 

 

 

 

11 on page 8- Honeywell).

 

 

 

 

 

 

 

 

C. Gas supply pressure errant.

Check inlet gas pressure. It should be within the limits as

 

 

 

 

marked on the rating plate.

 

 

 

 

 

 

 

 

D. Pilot orifice plugged.

Clean or replace pilot orifice.

 

 

 

 

2.

Pilot will not stay lit after

A. Defective pilot generator

Check pilot flame, it must impinge on thermocouple (Figure

 

carefully following the

(thermocouple).

10 on page 8- SIT, Figure 11 on page 8- Honeywell). Clean

 

lighting instructions.

 

and/or adjust pilot for maximum flame impingement on

 

 

 

 

thermocouple. Ensure that the connection between the valve

 

 

 

 

and thermocouple are tight and secure.

 

 

 

 

3.

Pilot burning, no gas to

A. Wall switch or wires defective.

Check wall switch and wires for proper connections. Jumper

 

burner, Valve knob “ON,”

 

wire across terminals at wall switch, if burner comes on,

 

Wall Switch “ON.”

 

replace defective wall switch. If okay, jumper wires across wall

 

 

 

 

switch wires at valve, if burner comes on, wires are faulty or

 

 

 

 

connections are bad.

 

 

 

 

 

 

 

 

B. Thermopile may not be generating

Check thermopile with millivolt meter. Take reading at thermo-

 

 

 

sufficient millivoltage.

pile terminals of gas valve. Should read 325 millivolts mini-

 

 

 

 

mum with optional wall switch “OFF.” Replace faulty thermo-

 

 

 

 

pile if reading is below specified minimum.

 

 

 

 

 

 

 

 

C. Plugged burner orifice.

Check burner orifice for stoppage and remove.

 

 

 

 

 

 

 

 

4.

Frequent pilot/burner outage

A. Pilot flame may be too low or

Clean and/or adjust pilot flame for maximum flame impinge-

 

problem.

blowing (high) causing the pilot/

ment on thermocouple (Figure 10 on page 8- SIT, Figure 11

 

 

 

valve safety to drop out.

on page 8- Honeywell).

 

 

 

 

 

Image 16
Contents Retain These Instructions For Future Reference DR-500 Model ShownDT-500CEN DR-600CEP DR-500CEP DT-800CENTable of Contents CongratulationsOperation and Care of Your Appliance Gas Controls/Control Compartment AccessBD-R Variable Flame Height Adjustment When IT is HOTGlass Cleaning MaintenanceMaintenance Schedule Maintenance Task Accomplishing Person ProcedureRefer to SIT Millivolt, Figure Refer to D, DT, DR-500, 8 DFront Glass Enclosure Panel, Removal and Installation Burner AdjustmentsReinstall the top louver assembly or radiant panel AdjustmentLog Placement Fire shown with optional Brick Liner KitDT, DR-600 Model DT, DR-500 ModelGlowing Embers Rockwool Placement Electronic Appliance CheckoutWarranty Replacement PartsProduct Reference Information LHPAccessory Components Clean Face Panel Kits Model No Catalog No Brick Liner Kits Catalog NoLouver Kits Catalog No Door Frame Kits Catalog NoLighting Instructions Honeywell and SIT Millivolt GAS Valve Lighting InstructionsTo Turn OFF GAS to Appliance What to do if YOU Smell GASPour Fermer LE GAZ QUI Alimente L’APPAREIL Instructions DallumagePosition d’arrêt OFF Lighting Instructions Electronic What to do if YOU Smell GASTo Shut OFF Front ViewInstructions D’ALLUMAGE Electronic Instructions D’ALLUMAGEPour Éteindre L’APPAREIL Pour Fermer LE GAZ QUI Alimente L’APPAREILSymptom Possible Causes Corrective Action On page 8- HoneywellTroubleshooting the Electronic Ignition System Check vent system for obstructionsReplacement Parts List GAS Controls SIT MillivoltGAS Controls Honeywell Millivolt GAS Controls ElectronicDR, DR-800 3431 DT, DR-500725,032M REV. H 11/2004