Weil-McLain Series 2 manual 13b Ratings, Doe

Page 67

GOLD CGi Gas-Fired Water Boiler — Boiler Manual

13b Ratings

 

 

 

 

 

 

 

 

 

 

 

 

DOE

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 10 

Boiler ratings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Boiler

 

DOE

0–2,000 feet

2,000–4,500 feet

 

Net

Boiler

 

DOE

Vent

model

 

Heating

altitude

altitude

 

I=B=R

water

 

Seasonal

size

number

 

capacity

 

 

 

 

 

ratings

content

 

efficiency

 

 

Input

Output

Input

Output

 

 

 

 

 

(Btuh)

 

(Btuh)

(gallons)

 

(% A.F.U.E)

 

 

 

 

(Btuh)

(Btuh)

(Btuh)

(Btuh)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Note 1)

 

(Note 2)

 

 

 

 

 

(Note 3)

 

 

 

(Note 4)

 

 

 

 

 

 

 

 

 

 

 

 

 

CGi-25

 

42,000

50,000

42,000

45,000

38,000

 

37,000

1.5

 

84.0

3"

 

 

 

 

 

 

 

 

 

 

 

 

 

CGi-3

 

57,000

67,000

57,000

60,000

51,000

 

50,000

1.5

 

84.3

3"

 

 

 

 

 

 

 

 

 

 

 

 

 

CGi-4

 

85,000

100,000

85,000

90,000

76,000

 

74,000

2.1

 

84.0

3"

 

 

 

 

 

 

 

 

 

 

 

 

 

CGi-5

 

112,000

133,000

112,000

120,000

101,000

 

97,000

2.7

 

83.7

3"

 

 

 

 

 

 

 

 

 

 

 

 

 

CGi-6

 

140,000

167,000

140,000

150,000

126,000

 

122,000

3.3

 

83.3

3"

 

 

 

 

 

 

 

 

 

 

 

 

 

CGi-7

 

167,000

200,000

167,000

180,000

150,000

 

145,000

3.8

 

83.0

3"

 

 

 

 

 

 

 

 

 

 

 

 

 

CGi-8

 

194,000

233,000

194,000

210,000

175,000

 

169,000

4.4

 

82.7

3"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. Add “PIN” for natural gas boiler - “PIL” for propane gas boiler.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2. Based on standard test procedures prescribed by the United States Department of Energy.

 

 

 

 

 

 

 

 

 

 

 

 

Notes

 

3. Net I=B=R ratings are based on net installed radiation of sufficient quantity for the requirements of the building

 

and nothing need be added for normal piping and pickup. Ratings are based on a piping and pickup allowance

 

 

of 1.15. An additional allowance should be made for unusual piping and pickup loads.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4. CGi boilers require special venting, consistent with Category I or III boiler. Use only the vent materials and

 

 

methods specified in this manual. Vent diameter shown above is for direct exhaust venting. See Table 3,

 

 

page 14, for vent diameter when chimney draft venting.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CGi boilers for residential radiant panel systems, converted gravity heating systems or other low water tempera- ture applications should be installed with balancing valves and bypass piping equal to the supply and return size to avoid excessive flue gas condensation due to lower operating water temperatures. For alternate piping, contact your Weil-McLain sales office. CSA design certified for installation on combustible flooring. Tested for 50 psi working pressure.

Part Number 550-110-710/0107

67

 

Image 67
Contents Gold CGi How it works Gold CGi Gas-Fired Induced-Draft Water Boiler Contents Please read before proceeding Installations must follow these codes 1a Prepare boiler location codes & checklistBefore locating the boiler, check the following 1b Prepare boiler location clearances 1c Prepare boiler location vent system When removing boiler from an existing common vent systemChimney or vent require- ments Products to avoid 1d Prepare boiler location air contaminationTwo openings Air supply from inside the building 1e Prepare boiler location air openingsAir openings must be provided Air opening optionsException for large spaces Exhaust fans and air moversMotorized air dampers Single air opening optionInspect orifices and burners 2a Prepare boiler placement & setupOrifice replacement procedure Place boiler/crate near positionPrepare boiler for test 2b Prepare boiler pressure testHydrostatic pressure test Drain and remove fittingsChimney draft venting 3a Venting general informationVenting chimney draft venting CGi venting methods Chimney draft or Direct exhaustObtain vent system components 3c Venting Direct exhaust components3d Venting direct exhaust vent starter Vent termination minimum clearances 3e Venting direct exhaust terminationDirect exhaust vertical venting 3f Venting direct exhaust installationUsing any termination other than one of those shown 4a Water piping general information Diaphragm-type or bladder- type expansion tank Figure 4b Water piping single-zone systemClosed-type expansion tank Piping multiple zones 4c Water piping multiple zonesZoning with circulators Primary/secondary preferred bypass piping method 4d Piping low temperature systemsTemperature gauges Valve adjustmentPrimary/secondary piping BOILER-bypass piping method Valve adjustmentBoiler-bypass piping Zoning with SYSTEM-bypass piping method Prevent chilled water from entering boiler 4e Water piping refrigeration systemPropane Gas Connecting gas supply piping to boilerGas piping Natural GasThermostat Field wiringElectrical installation must comply with Wiring connectionsDetermine if water treatment is needed Freeze protection when used7a Start-up preparation Check for gas leaksInspect system water piping Fill the system with waterInspect base insulation Start the boiler 7b Start-up operate boilerCheck system and boiler Pilot burner flame Figure 7c Start-up if boiler doesn’t startCheck burner flames Check forInstallation and service certificate Check-out procedure checklist9a Operation sequence Schematic wiring diagram 9b Operation wiring diagramsLadder wiring diagram 9c Operating instructions CGi-25 to CGi-6 9c Operating instructions CGi-25 to CGi-6 9c Operating instructions CGi-25 to CGi-8 Verify Proper Operation After Servicing 10a Service and maintenance schedule10b Service and maintenance annual start-up Inducer motor 10b Service & maintenance annual start-upBurners and base Condensate drain systemLimit controls and cutoffs Gas pipingCold fill and operating pressures Air vents and air eliminationBoiler relief valve Review with ownerAir pressure switch 11a Troubleshooting procedure11b Troubleshooting components Before troubleshootingControl module Control indicator lightsTroubleshooting the control module Control indicator lights Lockout modesControl module connections Chart 1- Troubleshooting Power light status 11c Troubleshooting control module lightsChart 2 Tstat Circ & Power lights flashing Chart 3 Press Switch & Power lights flashing Chart 4 Flame & Power lights flashing Does blower motor operate? Item 8 , Verify Sequence Section assembly Base Jacket Trim Controls 12a Replacement partsSection assembly 12b Replacement parts section assemblyBase assembly 12c Replacement parts baseDescription Weil-McLain Part number Jacket assembly 12d Replacement parts jacketBoiler Fittings shown are included with boiler 12e Replacement parts trimPropane gas components 12f Replacement parts controlsDimensional drawing 13a DimensionsDOE 13b RatingsRemoval of Combustion Chamber Lining or Base Panels Handling ceramic fiber and fiberglass materials
Related manuals
Manual 12 pages 22.83 Kb

Series 2 specifications

The Weil-McLain Series 2 is a highly regarded boiler system known for its robustness, efficiency, and ease of installation. Designed primarily for residential and light commercial applications, the Series 2 boasts a variety of features that cater to diverse heating needs.

One of the standout characteristics of the Series 2 is its cast iron construction, which provides durability and longevity. Cast iron is well-suited for heat retention, allowing the boiler to operate more efficiently and deliver consistent warmth. The Series 2 is available in multi-fuel options, accommodating both natural gas and propane, making it versatile for various installations.

Efficiency is a key feature of the Weil-McLain Series 2, with annual fuel utilization efficiency (AFUE) ratings that meet or exceed industry standards. This ensures that homeowners can enjoy not only a comfortable living environment but also reduced energy bills. The Series 2 is designed to provide optimal performance, minimizing fuel consumption while maximizing heat output.

Another innovative aspect of the Series 2 is its user-friendly control system. Equipped with advanced controls, the boiler allows for precise temperature management and can easily be integrated with existing heating systems. This adaptability is crucial for ensuring that the boiler matches the specific heating demands of any space, increasing overall comfort levels.

Installation is straightforward, thanks to the boiler's thoughtful design. The Series 2 features a compact footprint, allowing for flexible placement in various settings. Additionally, Weil-McLain provides comprehensive documentation and customer support, making it easier for technicians to install and maintain the system.

The Series 2 also includes features aimed at ease of maintenance. Its clean-out ports facilitate quick access for servicing, ensuring that the boiler remains in peak operating condition throughout its lifespan. Weil-McLain’s commitment to quality means users can expect reliable performance year after year.

Overall, the Weil-McLain Series 2 stands out as an excellent choice for those seeking a dependable, efficient, and straightforward heating solution. Its combination of durable construction, high efficiency, and user-centric design makes it a leading option in the boiler market, appealing to both homeowners and professionals alike. Whether for a new installation or a replacement, the Series 2 is poised to deliver exceptional heating performance.