Honeywell PRO-2200 installation manual LED Operation, Power, Communications, Mode

Page 11
LED Operation

PRO-2200 Two Reader Module PRO22R2

Installation Guide

11

LED Operation

The Reader board uses two on-board LEDs D79 & D80 to provide status information during its Power-up sequence as well as normal operation.

MODE

LED

LED

DESCRIPTION

D79

D80

 

 

 

 

 

 

 

ON

OFF

Start Power-up, hardware setup

 

 

 

 

Power-up

OFF

ON

Testing RAM

 

 

 

Sequence

ON

ON

Testing ROM and completing initialization

 

 

 

 

 

 

FLASH

ON

LED D79 flashes 4 times after

 

Power-up is completed

 

 

 

 

 

 

 

 

 

 

This is the processor heart-beat LED. It flashes once

 

 

 

every second. A short ON time (~20% duty cycle)

 

FLASH

 

indicates the board is off-line or has lost serial

Normal

 

communication with the Controller board. A long ON

 

 

 

 

time (~80% duty cycle) indicates the board is online

Operation

 

 

 

 

and communicating with the Controller board.

 

 

 

 

 

 

 

 

 

FLASH

Flash when there is activity on its Serial Port.

 

 

 

 

In addition to the status LEDs, there are 6 additional relay status LEDs on board. When any relay is energized or ON, its corresponding status LED will become ON also. The LED will remain ON for as long as the relay is energized. The assignment for each relay status LED is shown in the following table.

RELAY#

1

2

3

4

5

6

LED

D73

D75

D74

D76

D77

D78

Power

The Two Reader Board accepts 12 VDC with an operating range of 10 to 16 VDC and consumes 400mA of current. Locate power source as close to this board as possible. Connect power with minimum of 18AWG wire. The input voltage is regulated to 5 VDC. The regulated voltage or the 12 VDC (pass through) is available for powering the readers. The selection is made via jumpers and is available at both reader connectors.

NOTE: POLARITY for 12 VDC power is important. Make sure the +12 VDC is connected to the terminal labeled +12V and the return is connected to the terminal labeled GND.

Communications

The Two Reader Board communicates to host controller via an RS-485 interface. The interface allows for multi-drop communication of up to 4,000 feet (1,200 m) total per port. Use two twisted pair (minimum 24AWG) with shield for communication. The default speed of this port is 38.4Kbps but it can be downgraded to 19.2Kbps or 9.6Kbps if the line conditions or receiving equipment require it (see jumper and DIP switch settings).

Image 11
Contents A division of Northern Computers, Inc PRO-2200 Two Reader Module Installation ManualPart Number PRO22R2 Page Contents Fire Safety and Liability Notice Warnings and CautionsPage Product Liability Mutual Indemnification Unpacking ProcedureDisclaimer To ship equipment back to Engineered Systems Limited WarrantyShipping Instructions PRO-2200Two Reader Module PRO22R2 ConfidentialityInstallation Guide Default Set UpDescription SettingPRO-2200Two Reader Module PRO22R2 Dipswitch Settings= Default Installation GuideMODE PowerLED Operation CommunicationsFor wiring to a reader port Reader WiringFor Wiring to an RS-485port LED Output Alarm Contact WiringControl Output Wiring Single Wire Reader LED Control ConfigurationSee diagram to follow Suggested Installation SequenceMounting Options Reader interface SpecificationPrimary power 12VDC±10% 400mA Relay contacts InputsSeparate - Power VDC Supply + Wiring Diagram for Connectors 1 throughInstallation Guide Power VDCPRO-2200Two Reader Module PRO22R2 Wiring Diagram for Connectors 6 throughInstallation Guide PRO-2200Two Reader Module PRO22R2 Installation GuidePage 2700 Blankenbaker Pkwy, Suite Louisville, KY Honeywell Security & Data Collection