Honeywell PRO-2200 Mounting Options, Suggested Installation Sequence, See diagram to follow

Page 14
(See diagram to follow.)

14

Installation Guide

PRO-2200 Two Reader Module PRO22R2

Relays 1 and 3 are rated for and normally used to control the door locks associated with readers 1 and 2 respectively. While Relays 1 and 3 are sized to handle the typical loads generated by electrical locks, load switching can cause abnormal contact wear and premature contact failure. Switching of inductive loads (i.e., strike) also causes EMI (electromagnetic interference) which may interfere with normal operation of other equip- ment. To minimize premature contact failure and to increase system reliability, contact protection circuit is highly recommended. The following two circuits are suggested. Locate the protection circuit as close to the load as possible (within 12 inches [30cm]), as the effectiveness of the circuit will decrease as the distance from the load increases.

(See diagram to follow.)

Relays 2 and 4 are dry-circuit level signal relays typically used to indicate the status of the door lock. Relays 5 and 6 are general-purpose relay outputs and are not available when the board is rack mounted.

Use sufficiently large gauge of wires for the load current to avoid voltage loss.

Mounting Options

This board can be mounted on-edge in the rack-mount enclosure provided by Northern Computers or it can be mounted flat against any surface using standoffs under the mounting holes provided in each of the four corners of this board.

When this board is rack-mounted, the connectors for two general-purpose inputs, two general-purpose outputs, and two dedicated inputs are not accessible and should not be used.

The most common reason for mounting a board flat is that it is being installed remotely to be located near the door(s) being monitored. In this case it will be mounted in its own enclosure creating the need to monitor cabinet tamper and power fault detection inputs. The two additional general-purpose inputs and outputs provided allow for the monitoring of extra alarm sensors and control of local horns or other equipment.

Suggested Installation Sequence

1.Set Jumpers and DIP switches.

2.Mount this board in the appropriate enclosure. If this board is being mounted in a rack, the component side of the board is to the right when facing the rack.

3.Connect the communications and power supply to the circuit boards with the Power Supply Harness.

WARNING: DO NOT CONNECT THE POWER SUPPLY TO THE AC SOCKET UNTIL ALL WIRING HAS BEEN INSTALLED AND RECHECKED.

4. Connect wiring to the reader interfaces as appropriate.

Image 14
Contents A division of Northern Computers, Inc PRO-2200 Two Reader Module Installation ManualPart Number PRO22R2 Page Contents Warnings and Cautions Fire Safety and Liability NoticePage Product Liability Mutual Indemnification Unpacking ProcedureDisclaimer To ship equipment back to Engineered Systems Limited WarrantyShipping Instructions PRO-2200Two Reader Module PRO22R2 ConfidentialityInstallation Guide Setting Set UpDescription DefaultInstallation Guide Dipswitch Settings= Default PRO-2200Two Reader Module PRO22R2Communications PowerLED Operation MODEFor wiring to a reader port Reader WiringFor Wiring to an RS-485port Single Wire Reader LED Control Configuration Alarm Contact WiringControl Output Wiring LED OutputSee diagram to follow Suggested Installation SequenceMounting Options Inputs SpecificationPrimary power 12VDC±10% 400mA Relay contacts Reader interfacePower VDC Wiring Diagram for Connectors 1 throughInstallation Guide Separate - Power VDC Supply +PRO-2200Two Reader Module PRO22R2 Wiring Diagram for Connectors 6 throughInstallation Guide Installation Guide PRO-2200Two Reader Module PRO22R2Page Honeywell Security & Data Collection 2700 Blankenbaker Pkwy, Suite Louisville, KY