DSCover Satellite Products PC1555MX UL Listed Commercial and Residential Installations

Page 50

[67] Fifth User Display Mask

 

 

Default

 

 

Option

ON

OFF

OFF

I

I

1

Thermostat CTRL Prompt ON

Thermostat CTRL Prompt OFF

OFF

I

I

2

Temperature Setting Prompt ON

Temperature Setting Prompt OFF

OFF

I

I

3

Occupancy Mode Prompt ON

Occupancy Mode Prompt OFF

OFF

I

I

4

Thermostat Mode Prompt ON

Thermostat Mode Prompt OFF

OFF

I

I

5

Fan Control Prompt ON

Fan Control Prompt OFF

OFF

I

I

6

For Keypad View Prompt ON

For Keypad View Prompt OFF

OFF

I

I

7-8

For future use

 

[68] Sixth User Display Mask

 

 

Default

 

 

Option

ON

OFF

OFF

I

I

1

Occupancy Mode Auxiliary Prompt ON

Occupancy Mode Auxiliary Prompt OFF

OFF

I

I

2

Occupancy Mode Day Prompt ON

Occupancy Mode Day Prompt OFF

OFF

I

I

3

Occupancy Mode Away Prompt ON

Occupancy Mode Away Prompt OFF

OFF

I

I

4

Occupancy Mode Night Prompt ON

Occupancy Mode Night Prompt OFF

OFF

I

I

5-8

For future use

 

[97]View Software Version

[98]Initiate Global Label Broadcast

All LCD programming is done per keypad. If more than one LCD keypad are present on the system, and the PC5400 receives labels, labels pro- grammed at one keypad can be broadcast to all other LCD keypads. Perform the following procedure in order to broadcast labels:

Step 1 - Program one LCD keypad completely.

Step 2 - Make sure all LCD keypads are connected to the Keybus.

Step 3 - Enter Installer’s Programming, then enter Section [98] at the keypad that was programmed. The keypad will now broadcast all the informa- tion programmed to all the other LCD keypads on the system.

Step 4 - When the keypad is finished press the [#] key to exit.

[99] Reset LCD EEPROM to Factory Defaults

ASCII Characters

UL Listed Commercial and Residential Installations

The installation requirements listed below must be met for the follow-

Control of the Protected Premises

 

 

 

ing grades of service.

In order to have a UL Certificated system the protected area is to be

Grade A Local

under the responsibility of one ownership and management (i.e. one

business

under one name). This may

be a group of

buildings

The installation must have a bell UL Listed for mecantile local alarms

attached

or

unattached with different

addresses but

under

the

(AMSECO MBL10B with model AB-12 bell housing).

responsibility

of someone having mutual interest. The

person

of

The digital communicator must be enabled.

The control panel must be in the Attack Resistant Enclosure (DSC

mutual interest is not the alarm installing company.

 

 

Model CMC-1).

Bell Location

 

 

 

Swinger shutdown must be disabled.

The alarm sounding device (bell) must be located where it can be

Grade B Central Station and Police Connect

heard by the person or persons responsible for maintaining the secu-

rity system during the daily arming cycle.

 

 

 

The installation must have a bell UL Listed for mecantile local alarms

 

 

 

Protection of the Control Unit

 

 

 

(AMSECO MBL10B with model AB-12 bell housing).

 

 

 

The digital communicator must be enabled.

The local control and the local power supply must be protected by

Ringback must be enabled.

one of the following ways:

 

 

 

The control panel must be in the Attack Resistant Enclosure (DSC

• The control unit and audible alarm device power supply must be

Model CMC-1).

in a protected area which is armed 24 hours a day.

 

 

Swinger shutdown must be disabled.

• Each partition shall arm the area protecting the control unit and

Grade C Central Station

the audible alarm device power supply. This may require dupli-

cate protection armed by each partition. Access to this protected

The digital communicator must be enabled.

area, without causing an alarm, will require that all partitions be

Ringback must be enabled.

disarmed.

The control panel must be in the Attack Resistant Enclosure (DSC

Model CMC-1).

In all cases described above, the protected area for the control unit

Swinger shutdown must be disabled.

must be programmed as not bypassable.

Casual Users

All Commercial Installations

The installer should caution the user(s) to not give system information

• The entry delay must not exceed 60 seconds

to casual users (e.g. codes, bypass methods, etc. to baby-sitters or

• The exit delay must not exceed 60 seconds.

service people). Only the One-Time Use codes should be given to

• The minimum bell cutoff time is 15 minutes.

casual users.

Residential Installations

User Information

• The entry delay must not exceed 45 seconds

The installer should advise the users and note in the user instruction

• The exit delay must not exceed 60 seconds.

manual:

• The minimum bell cutoff time is 4 minutes.

• Service organization name and telephone number

Programming

• The programmed exit time

The notes in the programming sections describing the system config-

• The programmed entry time

urations for UL Listed installations must be implemented.

 

WWW.DIYALARMFORUM.COM

46

Image 50
Contents Installation Manual See Back Cover for New FeaturesLimited Warranty Table of Contents PC1555MX Wiring Diagram Specifications System IntroductionAdditional Devices Out of the BoxTerminal Descriptions Installation StepsGetting Started Example of Keybus Wiring Wire Routing for Power & Non-Power LimitedKeybus Operation & Wiring Zone Input Terminals Z1 to Z6Keypad Assignment Current Ratings Modules & AccessoriesZone Wiring SupervisionLinks Zone Wiring Fire Zone Wiring11 24-Hr Auxiliary Input Wiring PGM2 Links Answer Keypad ZonesLinks Supervision 24 Hour Supervisory Assigning Keypad ZonesArming and Disarming Keypad CommandsCommands Auto Bypass Stay ArmingTo view trouble conditions from an LED keypad Alarm MemoryTrouble Display Door Chime On/OffAccess Code Attributes Master Code Access CodeSupervisor Codes Access Code 41 Viewing the Event Buffer from an LCD KeypadFunction Keys Features Available for the LCD5500Z Programming Decimal Data How to ProgramInstaller’s Programming Programming HEX DataPage Zone Programming Program DescriptionsProgramming Security Codes Zone Attributes Communicator Dialing Communicator Account NumbersAssigning Keypad Zones Communicator Telephone NumbersZone Restorals Openings/Closings by Wireless KeyAC Failure Trouble Alarm Code Closings Arming CodesAdditional Notes on Contact ID Pulse FormatsContact ID Pager FormatDownloading PGM Output OptionsArmed Status Keypad Buzzer Follower ModeTLM and Alarm Ready To ArmTelephone Line Monitor TLM BellFire, Auxiliary and Panic Keys Transmission DelayTest Transmission Arming/Disarming OptionsEvent Buffer Entry/Exit Delay OptionsSwinger Shutdown Keypad Lockout OptionsLoop Response Keypad BlankingKeypad Backlighting Keypad TampersWalk Test Installer Resetting Factory DefaultsInstaller’s Lockout Additional System ModulesModule Name Description Location Programming WorksheetsFor the Record Keypads Keypad Type LocationSystem Zone Label Zone Attributes Type Serial Number WirelessZone Programming Summary Basic Programming DefaultKeypad Programming Function Key OptionsSystem Times Default Valid entries Programmable Output OptionsProgram PGM Option Attributes in sections 143 First System Option Code Default Off Section Page #Second System Option Code Default Off Section Program PGM Option Attributes in sections 151Fifth System Option Code Default Off Section Page # Third System Option Code Default Off Section Page #Fourth System Option Code Default Off Section Page # Zone Loop Response Options Default Off Section Page #Zone Type Zone Attribute Defaults Y = Option on N = Option OFFAdvanced System Programming Section Zone # TypePGM Attribute Defaults Y = Attribute on N = Attribute OFF PGM OptionPC5204 Main BoardPC5208 Communicator Programming Miscellaneous Closing Arming Reporting Codes 01 20 BPS, 1400 HZ handshake Default OptionMiscellaneous Opening Disarming Reporting Codes 02 20 BPS, 2300 HZ handshake PagerCommunication Variables Default Section First Communicator Option Code DefaultDefault Ffffff I I I I I Second Communicator Option Code DefaultDefault Ffff Default Option OffModule Programming Special Installer FunctionsInternational Programming Appendix a Reporting Codes SIA Format Level 2 HardcodedContact ID Zone Alarm/Restoral Event Codes as per Ademco SIA Format Automatic Zone Alarm/Restoral CodesAppendix B Programming LCD Keypads Key Options Default Second User Display Mask Default OptionThird User Display Mask Default Option Fourth User Display Mask Default OptionSixth User Display Mask Default Option UL Listed Commercial and Residential InstallationsFifth User Display Mask Default Option Reset LCD Eeprom to Factory Defaults Ascii CharactersImportant Information PC1555MX Module Compatibility Changes for PC1555MX

PC1555MX specifications

The DSCover Satellite Products PC1555MX is an advanced satellite communication device designed to meet the demands of both commercial and industrial sectors. Its high-performance capabilities are complemented by a robust design, making it an excellent choice for users who require reliable connectivity in remote or challenging environments.

At the heart of the PC1555MX is its cutting-edge satellite technology, which enables seamless communication regardless of geographical constraints. The device operates on multiple frequency bands, enhancing its versatility and ensuring optimal performance in diverse conditions. This multi-band capability allows for greater flexibility in communication, accommodating various applications from data transmission to voice calls.

One of the standout features of the PC1555MX is its impressive data transfer speeds. With advancements in modulation techniques, users can enjoy fast and efficient data upload and download rates. This makes the device particularly suitable for applications that require real-time data processing, such as telemetry, remote monitoring, and emergency response communications.

The PC1555MX also incorporates advanced encryption protocols to ensure data security during transmission. This is especially crucial for industries such as defense, security, and finance, where sensitive information must be safeguarded against potential breaches. Users can have peace of mind knowing that their communications are protected by state-of-the-art security measures.

In addition to its communication capabilities, the PC1555MX is designed with user-friendly operation in mind. Its intuitive interface allows for easy navigation and control, making it accessible even to those with limited technical expertise. Furthermore, the device is equipped with a comprehensive alert system that notifies users of any connectivity issues or performance deviations, ensuring that they remain informed and can take swift action if necessary.

Durability is another key characteristic of the DSCover PC1555MX. Built to withstand harsh environmental conditions, it features a rugged exterior that is both weather-resistant and shockproof. This level of durability makes the device suitable for deployment in various settings, from outdoor expeditions to industrial sites.

Overall, the DSCover Satellite Products PC1555MX stands out as a premier choice for satellite communication. With its advanced features, robust design, and commitment to security and performance, it effectively meets the needs of users in an increasingly connected world. Whether for business operations or emergency services, the PC1555MX ensures that critical communications remain uninterrupted.