DSCover Satellite Products PC1555MX Fire Zone Wiring, 11 24-Hr Auxiliary Input Wiring PGM2

Page 10

To enable normally closed loops, programming section [013], option [1] must be ON.

NOTE: This option should only be selected if Normally Closed (NC) detection devices or contacts are being used.

Single End Of Line (EOL) Resistors (5600)

To enable panel detection of single end of line resistors, pro- gramming section [013], Options [1] and [2] must be OFF.

NOTE: This option should be selected if either Normally Closed (NC) or Normally Open (NO) detection devices or con- tacts are being used.

Double End of Line (DEOL) Resistors

Double End of Line resistors allow the panel to determine if the zone is in alarm, tampered or faulted.

To enable panel detection of double end of line resistors, pro- gramming section [013], Option [1] must be OFF and option [2] must be ON.

NOTE: If the Double EOL supervision option is enabled, all hardwire zones on the main panel must be wired for Double EOL resistors, except for Fire and 24 Hour Supervisory zones.

NOTE: Do not wire DEOL resistors on keypad zones.

NOTE: Do not use DEOL resistors for Fire zones or 24 Hour Supervisory zones. Do not wire Fire zones to keypad zone ter- minals if the DEOL supervision option is selected.

2.10 Fire Zone Wiring

4-Wire Smoke Detectors

All fire zones must be wired according to the following dia- gram:

2-Wire Smoke Detectors (50/300 only)

The following 2-wire smoke detectors may be used: ESL429AT and DSC MN220. If PGM2 has been programmed for a 2-wire Smoke Detector connection, the detectors must be wired according to the following diagram:

NOTE: If PGM2 is programmed for 2-wire smoke support, the connector JP1 on the main board must be removed.

NOTE: 2-wire smoke detectors are not supported on 50/50 version of the panel.

2.11 24-Hr Auxiliary Input Wiring (PGM2)

If PGM2 has been programmed for 24-hour operation, the zone must be wired according to the following diagram:

NOTE: If PGM2 is pro- grammed for 24-Hr Auxil- iary Input support, the connector JP1 on the main board must be removed.

NOTE: This option can only be selected if Normally Closed (NC) detection devices or contacts are being used.

NOTE: Only one NC contact can be connected to each zone. Wiring multiple detection devices or contacts on a single loop is not allowed.

The following chart shows zone status under certain conditions:

Loop Resistance

Loop Status

0(shorted wire, loop shorted)

Fault

5600(contact closed)

Secure

Infinite (broken wire, loop open)

Tamper

11200(contact open)

Violated

End of Line Resistors. . . . . . . . . . . . . . . . . . Section [013]: [1]

Double End of Line Resistors . . . . . . . . . . . Section [013]: [2]

2.12 LINKS Zone Wiring*

LINKS Support

When using the LINKS1000 cellular communicator, con- nect the LINKS to the main panel according to the fol- lowing diagram:

WWW.DIYALARMFORUM.COM

*Not investigated by UL.

6

 

Image 10
Contents Installation Manual See Back Cover for New FeaturesLimited Warranty Table of Contents PC1555MX Wiring Diagram Specifications System IntroductionAdditional Devices Out of the BoxGetting Started Installation StepsTerminal Descriptions Example of Keybus Wiring Wire Routing for Power & Non-Power LimitedKeybus Operation & Wiring Zone Input Terminals Z1 to Z6Keypad Assignment Current Ratings Modules & AccessoriesZone Wiring Supervision11 24-Hr Auxiliary Input Wiring PGM2 Fire Zone WiringLinks Zone Wiring Links Answer Keypad ZonesLinks Supervision 24 Hour Supervisory Assigning Keypad ZonesArming and Disarming Keypad CommandsCommands Auto Bypass Stay ArmingTo view trouble conditions from an LED keypad Alarm MemoryTrouble Display Door Chime On/OffAccess Code Attributes Master Code Access CodeSupervisor Codes Access Code 41 Viewing the Event Buffer from an LCD KeypadFunction Keys Features Available for the LCD5500Z Programming Decimal Data How to ProgramInstaller’s Programming Programming HEX DataPage Programming Security Codes Program DescriptionsZone Programming Zone Attributes Communicator Dialing Communicator Account NumbersAssigning Keypad Zones Communicator Telephone NumbersZone Restorals Openings/Closings by Wireless KeyAC Failure Trouble Alarm Code Closings Arming CodesAdditional Notes on Contact ID Pulse FormatsContact ID Pager FormatDownloading PGM Output OptionsArmed Status Keypad Buzzer Follower ModeTLM and Alarm Ready To ArmTelephone Line Monitor TLM BellFire, Auxiliary and Panic Keys Transmission DelayTest Transmission Arming/Disarming OptionsEvent Buffer Entry/Exit Delay OptionsSwinger Shutdown Keypad Lockout OptionsLoop Response Keypad BlankingKeypad Backlighting Keypad TampersWalk Test Installer Resetting Factory DefaultsInstaller’s Lockout Additional System ModulesModule Name Description Location Programming WorksheetsFor the Record Keypads Keypad Type LocationZone Programming Summary Serial Number WirelessSystem Zone Label Zone Attributes Type Basic Programming DefaultKeypad Programming Function Key OptionsSystem Times Default Valid entries Programmable Output OptionsProgram PGM Option Attributes in sections 143 First System Option Code Default Off Section Page #Second System Option Code Default Off Section Program PGM Option Attributes in sections 151Fifth System Option Code Default Off Section Page # Third System Option Code Default Off Section Page #Fourth System Option Code Default Off Section Page # Zone Loop Response Options Default Off Section Page #Zone Type Zone Attribute Defaults Y = Option on N = Option OFFAdvanced System Programming Section Zone # TypePGM Attribute Defaults Y = Attribute on N = Attribute OFF PGM OptionPC5208 Main BoardPC5204 Communicator Programming Miscellaneous Closing Arming Reporting Codes 01 20 BPS, 1400 HZ handshake Default OptionMiscellaneous Opening Disarming Reporting Codes 02 20 BPS, 2300 HZ handshake PagerCommunication Variables Default Section First Communicator Option Code DefaultDefault Ffffff I I I I I Second Communicator Option Code DefaultDefault Ffff Default Option OffInternational Programming Special Installer FunctionsModule Programming Appendix a Reporting Codes SIA Format Level 2 HardcodedContact ID Zone Alarm/Restoral Event Codes as per Ademco SIA Format Automatic Zone Alarm/Restoral CodesAppendix B Programming LCD Keypads Key Options Default Second User Display Mask Default OptionThird User Display Mask Default Option Fourth User Display Mask Default OptionSixth User Display Mask Default Option UL Listed Commercial and Residential InstallationsFifth User Display Mask Default Option Reset LCD Eeprom to Factory Defaults Ascii CharactersImportant Information PC1555MX Module Compatibility Changes for PC1555MX

PC1555MX specifications

The DSCover Satellite Products PC1555MX is an advanced satellite communication device designed to meet the demands of both commercial and industrial sectors. Its high-performance capabilities are complemented by a robust design, making it an excellent choice for users who require reliable connectivity in remote or challenging environments.

At the heart of the PC1555MX is its cutting-edge satellite technology, which enables seamless communication regardless of geographical constraints. The device operates on multiple frequency bands, enhancing its versatility and ensuring optimal performance in diverse conditions. This multi-band capability allows for greater flexibility in communication, accommodating various applications from data transmission to voice calls.

One of the standout features of the PC1555MX is its impressive data transfer speeds. With advancements in modulation techniques, users can enjoy fast and efficient data upload and download rates. This makes the device particularly suitable for applications that require real-time data processing, such as telemetry, remote monitoring, and emergency response communications.

The PC1555MX also incorporates advanced encryption protocols to ensure data security during transmission. This is especially crucial for industries such as defense, security, and finance, where sensitive information must be safeguarded against potential breaches. Users can have peace of mind knowing that their communications are protected by state-of-the-art security measures.

In addition to its communication capabilities, the PC1555MX is designed with user-friendly operation in mind. Its intuitive interface allows for easy navigation and control, making it accessible even to those with limited technical expertise. Furthermore, the device is equipped with a comprehensive alert system that notifies users of any connectivity issues or performance deviations, ensuring that they remain informed and can take swift action if necessary.

Durability is another key characteristic of the DSCover PC1555MX. Built to withstand harsh environmental conditions, it features a rugged exterior that is both weather-resistant and shockproof. This level of durability makes the device suitable for deployment in various settings, from outdoor expeditions to industrial sites.

Overall, the DSCover Satellite Products PC1555MX stands out as a premier choice for satellite communication. With its advanced features, robust design, and commitment to security and performance, it effectively meets the needs of users in an increasingly connected world. Whether for business operations or emergency services, the PC1555MX ensures that critical communications remain uninterrupted.