This appliance is one of the most advanced water heaters available. It provides a continuous supply of hot water at a preset temperature. This appliance is direct vent where air is brought in from the outside and combustion gases are exhausted to the outside.

While electricity, water, and gas supplies are connected, this appliance produces hot water whenever a hot water tap is open.

Ignition is electronic. There is no pilot light consuming gas while the water heater is not being used. The gas burner lights automatically when the hot water tap is

opened and goes out when the tap is closed. Installation of the temperature controller is highly recommended. The temperature controller can set the temperature within a specific range and can provide error codes to diagnose any problems.

The temperature of the outgoing hot water is constantly monitored. This appliance may adjust the water flow in order to maintain the temperature setting. The water flow may vary from summer to winter due to the difference in ground water temperature.

Sequence of Operation

1. Water

Flow Begins

 

Water Flow Sensor sends a pulse to the electronic

 

control board

 

Electronic control

board senses flow greater than

 

0.6 GPM

 

Firing Sequence

begins

Features Available on Temperature Controllers

The temperature controller is supplied with the

appliance. Dimensions (inches): 3.5 W x 4.75 H x 0.75 D.

Indicator

In Use 1

k,

J

Priority

/

 

I

 

 

"F/'C

ITemperature

In Use

2. Firing Sequence

 

 

 

 

Electronic control board monitors inlet/outlet water

 

temperature, temperature set point, and water

 

flow

rate.

 

 

 

 

Combustion fan energized. Purges combustion

 

chamber.

 

 

 

 

Spark

igniter begins sparking.

 

 

Gas control

valve

opens to minimum

fire rate.

Flame

rod

proves

ignition

 

 

Spark

igniter stops sparking

 

 

3. Normal Operation

 

 

 

Electronic

control board monitors flame rod,

 

fan motor frequency, outlet water temperature,

 

controller temperature set point and water flow

 

rate.

 

 

 

 

 

 

Gas control

valve

modulates gas input to required

 

firing

rate.

 

 

 

 

Combustion

fan speed is adjusted for the required

 

firing

rate.

 

 

 

 

Water

flow

control

valve is adjusted

as needed.

4. Shutdown

Sequence

 

 

 

Electronic

control board senses water flow rate

 

less than 0.5 GPM.

 

 

Gas control

valve

closes.

 

 

Water flow control valve resets

to

standby

 

position.

 

 

 

 

Combustion

fan runs for a short period

of time at

 

low speed.

 

 

 

 

5. Standby Mode

 

 

 

 

Electronic control board monitors water temperature

 

and remote

controls

 

 

Freeze

protection

is activated as needed.

Display F

Approx Water Temp

'-Thermostat

Features

 

 

 

Description

 

 

Error Codes

When

a fault

is detected

an error

code

 

 

flashes

at

the temperature

 

 

In Use Indicator

Indicates

that

hot water

is being

supplied

 

 

(i.e. a hot water tap is open).

 

 

ON/OFF

Button

Used to turn the water heater ON or OFF.

Priority

Button /

Indicates

that

this controller is setting

the

Indicator

 

temperature.

Priority can be switched

to

 

 

another controller by pressing its Priority

 

 

Button when no hot water is running.

 

Temperature Display

Shows

the temperature

setting.

 

 

Thermostat

Increases

or decreases

the temperature

 

 

setting.

 

 

 

 

 

 

Figure 11

22

305 & 505 Outdoor Manual

Image 22
Contents 505 Models Direct Vent Tankless Water HeatersRead and follow water heater warnings and instructions Important DefinitionsSafety Behavior and Practices Safety FeaturesDimensions Technical Safe Installation UseSafety Precautions Pressure Relief Valve FreezeMaster Protection Agreements Excessive Weight Hazard ImportantInformationAbout This Water HeaterModel Models 505++D Pressure Drop Curve Outlet Flow DataGeneral Instructions Tos120vAccoe,o22,RES..EcT Electrical ConnectionLength Pipe Size Inches Pipe Sizing Procedure ExamplePipe Sizing Table Natural Gas Pipe Sizing Table Propane GasPressure Relief Valve General InstructionsFreezing Protection Freeze Protection Piping Drawing Water HeaterRecommended Piping for Basic Installation Water Heater Recommended Piping for Circulation SystemsFor the circulation system Minimum 3/4 ColdWater Supply UneClosed Corner Guidelines Cable Length and Size LocationMounting the Controller Features Description Features Available on Temperature ControllersSequence of Operation 160F 71C 150F 66C 140F 60C 130F 54C 120F 49C 80F 27C Model Temperature Settings Available Temperature Options without a Temperature ControllerTemperature Ranges Re-setting the Maximum TemperatureFor Your Safety Read Before Operating Motors Temperature ControllerVent System Lime / Scale Build-upError Codes Code Fault RemedyThermal Fuse LC orWater Quality When I open a hot tap, I do not immediately get hot waterAccessing Operating Information Maximum LevelFlushing the Heat Exchanger ErrorCode LC or H1 Circulating PumpSW,TC......i,seF Repair Parts List 305&505OutdoorManual33 34305&505OutdoorManual 305&505OutdoorManual35 Iiiiiiiii