Kenmore 505, 305 owner manual H1 Circulating Pump, Flushing the Heat Exchanger ErrorCode LC or

Page 30

Flushing the Heat Exchanger (ErrorCode: LC or 00)

An "LC" or "00" error code indicates the unit is beginning to lime up and must be flushed. Failure to flush the appliance will cause damage to the heat exchanger. Damage caused by lime build-up is not covered by the unit'swarranty. After flushing, reset the LC fault code by

turning off the power to the unit and turning the power back on.

1.Disconnect electrical power to the water heater.

2.Close the shutoff valves on both the hot water and cold water lines (V3 and V4).

3.Connect pump outlet hose (H1) to the cold water line at service valve V2.

4.Connect drain hose (H3) to service valve Vl.

5.Pour approximately 4 gallons of virgin, food grade, white vinegar or citric acid into pail.

6.Place the drain hose (H3) and the hose (H2) to the pump inlet into the cleaning solution.

7.Open both service valves (Vl and V2) on the hot water and cold water lines.

,Operate the pump and allow the cleaning solution to circulate through the water heater for at least 45 minutes.

,Turn off the pump.

a.Rinse the cleaning solution from the water heater as follows: a. Remove the free end of the drain hose (H3) from the pail.

b.Close service valve, (V2), and open shutoff valve, (V4). Do not open shutoff valve, (V3).

c.Allow water to flow through the water heater for 5 minutes.

d.Close service valve, (Vl), and open shutoff valve, (V3).

10.Disconnect all hoses.

11.Remove the in-line filter at the cold water inlet and clean out any residue. Place filter back into unit.

13. Restore electrical power to the water heater.

I _'o n o=_l

oo

Water Heater

00

.,,I I In-line

_1 I Filtp.r-

/_1_l_Fitter

--Gas Supply

V1 - 2

! H1 Circulating Pump

Hot Water Line

H2

5 gallon pail of virgin,food grade, white vinegar(or virgin, food grade, citric acid)

KEY

I (_

3/4"

Ball Valve

Pressure

Regulator

--

3/4"

Union

Circulating

Pump

 

 

 

Check Valve

Boiler Drain Valve

 

Z_ Pressure Relief Valve [_ Solenoid Valve

Figure 14

30

305 & 505 Outdoor Manual

Image 30
Contents 505 Models Direct Vent Tankless Water HeatersRead and follow water heater warnings and instructions Important DefinitionsSafety Behavior and Practices Safety FeaturesDimensions Technical Safe Installation UseSafety Precautions Pressure Relief Valve FreezeMaster Protection Agreements Excessive Weight Hazard ImportantInformationAbout This Water HeaterModel Models 505++D Pressure Drop Curve Outlet Flow DataGeneral Instructions Tos120vAccoe,o22,RES..EcT Electrical ConnectionLength Pipe Size Inches Pipe Sizing Procedure ExamplePipe Sizing Table Natural Gas Pipe Sizing Table Propane GasGeneral Instructions Pressure Relief ValveFreezing Protection Freeze Protection Piping Drawing Water HeaterRecommended Piping for Basic Installation Water Heater Recommended Piping for Circulation SystemsFor the circulation system Minimum 3/4 ColdWater Supply UneClosed Corner Guidelines Location Cable Length and SizeMounting the Controller Features Available on Temperature Controllers Features DescriptionSequence of Operation 160F 71C 150F 66C 140F 60C 130F 54C 120F 49C 80F 27C Model Temperature Settings Available Temperature Options without a Temperature ControllerTemperature Ranges Re-setting the Maximum TemperatureFor Your Safety Read Before Operating Motors Temperature ControllerVent System Lime / Scale Build-upError Codes Code Fault RemedyThermal Fuse LC orWater Quality When I open a hot tap, I do not immediately get hot waterAccessing Operating Information Maximum LevelFlushing the Heat Exchanger ErrorCode LC or H1 Circulating PumpSW,TC......i,seF Repair Parts List 305&505OutdoorManual33 34305&505OutdoorManual 305&505OutdoorManual35 Iiiiiiiii