Flushing the Heat Exchanger (ErrorCode: LC or 00)
An "LC" or "00" error code indicates the unit is beginning to lime up and must be flushed. Failure to flush the appliance will cause damage to the heat exchanger. Damage caused by lime
turning off the power to the unit and turning the power back on.
1.Disconnect electrical power to the water heater.
2.Close the shutoff valves on both the hot water and cold water lines (V3 and V4).
3.Connect pump outlet hose (H1) to the cold water line at service valve V2.
4.Connect drain hose (H3) to service valve Vl.
5.Pour approximately 4 gallons of virgin, food grade, white vinegar or citric acid into pail.
6.Place the drain hose (H3) and the hose (H2) to the pump inlet into the cleaning solution.
7.Open both service valves (Vl and V2) on the hot water and cold water lines.
,Operate the pump and allow the cleaning solution to circulate through the water heater for at least 45 minutes.
,Turn off the pump.
a.Rinse the cleaning solution from the water heater as follows: a. Remove the free end of the drain hose (H3) from the pail.
b.Close service valve, (V2), and open shutoff valve, (V4). Do not open shutoff valve, (V3).
c.Allow water to flow through the water heater for 5 minutes.
d.Close service valve, (Vl), and open shutoff valve, (V3).
10.Disconnect all hoses.
11.Remove the
13. Restore electrical power to the water heater.
I _'o n o=_l
oo
Water Heater
00
.,,I I
•_1 I Filtp.r-
/_1_l_Fitter
--Gas Supply
V1 - 2
! H1 Circulating Pump
Hot Water Line
H2
5 gallon pail of virgin,food grade, white vinegar(or virgin, food grade, citric acid)
KEY
I (_ | 3/4" | Ball Valve | Pressure | Regulator |
3/4" | Union | Circulating | Pump | |
|
|
|
Check Valve | Boiler Drain Valve |
|
Z_ Pressure Relief Valve [_ Solenoid Valve
Figure 14
30 | 305 & 505 Outdoor Manual |