Check Optional Pumpout System Controls and Compressor — Controls include an on/off switch, a 3-amp fuse, the compressor overloads, an internal thermostat, a compressor contactor, and a refrigerant high pressure cutout. The high pressure cutout is factory set to open at 161 psig (1110 kPa) and reset at 130 psig (896 kPa). Ensure the water- cooled condenser has been connected. Loosen the compressor holddown bolts to allow free spring travel. Open the compres- sor suction and discharge the service valves. Ensure oil is visi- ble in the compressor sight glass. Add oil if necessary.

See the Pumpout and Refrigerant Transfer Procedures and Optional Pumpout System Maintenance sections, pages 67 and 75, for details on the transfer of refrigerant, oil specifications, etc.

Table 9 — Control Test Menu Functions

TESTS TO BE

DEVICES TESTED

PERFORMED

 

1. CCM Thermistors

Entering Chilled Water

 

Evaporator Refrigerant Tempera-

 

ture (ICVC only)

 

Leaving Chilled Water

 

Entering Condenser Water

 

Leaving Condenser Water

 

Remote Reset Sensor

 

Comp Discharge Temp

 

Oil Sump Temp

 

Comp Motor Winding Temp

 

Space Temperature 1

 

Space Temperature 2

2. CCM Pressure

Evaporator Pressure

Transducers

Condenser Pressure

 

Oil Pump Delta P

 

Condenser Water Delta P

 

Transducer Voltage Ref

3. Pumps

Chilled Water — Confirm pressure

 

Condenser Water — Confirm

 

Delta P

4. Discrete Outputs

Oil Heater Relay

 

Hot Gas Bypass Relay

 

Tower Fan Relay Low

 

Tower Fan Relay High

 

Alarm Relay

 

Shunt Trip Relay

5. Guide Vane Actuator

Open/Close

6. Diffuser Actuator

Open/Close

7.Pumpdown Lockout When using pumpdown/lockout, observe freeze up precautions when removing charge:

 

Instructs operator which valves to

 

close and when.

 

Starts chilled water and condenser

 

water pumps and confirms flows.

 

Monitors

 

Evaporator pressure

 

Condenser pressure

 

Evaporator temperature during

 

pumpout procedures

 

Turns pumps off after pumpdown.

 

Locks out compressor.

8 Terminate Lockout

Starts pumps and monitors flows.

 

Instructs operator which valves to

 

open and when.

 

Monitors

 

Evaporator pressure

 

Condenser pressure

 

Evaporator temperature during

 

charging process

 

Terminates compressor lockout.

High Altitude Locations — Because the chiller is ini- tially calibrated at sea level, it is necessary to recalibrate the pressure transducers if the chiller has been moved to a high alti- tude location. See the calibration procedure in the Trouble- shooting Guide section.

Charge Refrigerant into Chiller

The transfer, addition, or removal of refrigerant in spring isolated chillers may place severe stress on external piping if springs have not been blocked in both up and down directions.

Always operate the condenser and chilled water pumps during charging operations to prevent freeze-ups.

The standard 19XR chiller is shipped with the refrigerant already charged in the vessels. However, the 19XR may be or- dered with a nitrogen holding charge of 15 psig (103 kPa). Evacuate the nitrogen from the entire chiller, and charge the chiller from refrigerant cylinders.

CHILLER EQUALIZATION WITHOUT A PUMPOUT UNIT

When equalizing refrigerant pressure on the 19XR chiller after service work or during the initial chiller start-up, do not use the discharge isolation valve to equalize. Either the motor cooling isolation valve or the charging hose (con- nected between the pumpout valves on top of the cooler and condenser) should be used as the equalization valve.

To equalize the pressure differential on a refrigerant isolated 19XR chiller, use the terminate lockout function of the CON- TROL TEST on the SERVICE menu. This helps to turn on pumps and advises the operator on proper procedures.

The following steps describe how to equalize refrigerant pressure in an isolated 19XR chiller without a pumpout unit.

1.Access terminate lockout function on the CONTROL TEST screen.

2.IMPORTANT: Turn on the chilled water and con- denser water pumps to prevent freezing.

3.Slowly open the refrigerant cooling isolation valve. The chiller cooler and condenser pressures will gradually equalize. This process takes approximately 15 minutes.

4.Once the pressures have equalized, the cooler isolation valve, the condenser isolation valve, and the hot gas isola- tion valve may now be opened. Refer to Fig. 29 and 30, for the location of the valves.

Whenever turning the discharge isolation valve, be sure to reattach the valve locking device. This prevents the valve from opening or closing during service work or during chiller operation.

63

Page 63
Image 63
Carrier XRV, 19XR Charge Refrigerant into Chiller, Control Test Menu Functions, Tests to be Devices Tested Performed

19XR, XRV specifications

The Carrier 19XR and 19XRV chillers are sophisticated cooling solutions that represent the forefront of HVAC technology. Designed for large commercial and industrial applications, these chillers provide exceptional performance, energy efficiency, and reliability, making them ideal for a variety of environments ranging from hospitals to manufacturing facilities.

One of the most significant features of the Carrier 19XR and 19XRV chillers is their advanced scroll compressor technology. These units employ a tandem scroll design that enhances efficiency while minimizing operational noise. This makes them ideal for urban environments where noise restrictions may be in place. Moreover, the compressors are equipped with variable speed drive options in the 19XRV model, which allows for greater energy savings by adjusting cooling output based on real-time demand.

In addition to their advanced compressors, the 19XR and 19XRV units incorporate the Carrier GreenChoice refrigerant, which has a lower global warming potential compared to traditional refrigerants. This innovative choice not only meets regulatory requirements but also contributes to sustainability goals, making these chillers a responsible choice for environmentally conscious organizations.

The units are engineered with a robust heat exchanger design, which enhances heat transfer efficiency and overall system performance. This ensures optimal operation even in extreme conditions. They feature a microprocessor-based control system that allows for precise monitoring and control of the chiller’s performance, enabling operators to make real-time adjustments to maximize energy efficiency.

The Carrier 19XR and 19XRV chillers also prioritize serviceability. The design incorporates easy access to key components, simplifying maintenance procedures and reducing downtime. This focus on maintainability extends the lifespan of the equipment, leading to lower lifecycle costs.

In terms of connectivity, these chillers are equipped with advanced Building Management System (BMS) integration capabilities. This allows for seamless monitoring and control of the chillers using a centralized platform, facilitating energy management and operational optimization.

Overall, the Carrier 19XR and 19XRV chillers stand out in the market for their blend of cutting-edge technology, energy efficiency, and user-friendly features. They are engineered to meet the demanding needs of modern commercial and industrial applications, making them a preferred choice for facility managers seeking reliable cooling solutions.